| Plan Review Stops For Permit 23010183 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-13 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-13 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-14 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-14 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2023-02-14 11:27:20 | POOL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SIGNED AND SEALED DRAWINGS RP-1, RP-2, RP-3, RP-5, | | | RP-6 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-01 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-01 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2023-02-01 15:10:37 | POOL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE POOL ENGINEERING POOL DESIGN | | | DRAWINGS FBC R4501.6.1 | | | | | | 2) PLEASE SHOW THE DISTANCE FROM THE EAST SIDE OF THE | | | POOL AND DECK TO THE PROPERTY LINE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-03-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-03-16 |
Time |
21:19 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-03-16 |
Time |
19:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-02-16 |
Time |
20:26 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-02-15 |
Time |
23:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2023-01-19 |
Time |
19:33 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2023-01-19 |
Time |
19:31 |
Sent To |
|
|
| Notes |
| 2023-01-19 19:33:14 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO ELECTRICAL PLAN SUBMITTED FOR POOL | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-03-21 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-03-21 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-02-27 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-27 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-01 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-09 |
Time |
08:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-13 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-13 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-15 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-15 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2023-02-15 14:42:31 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23010183 | | | 2/15/2023 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET RP-3 (POOL PIPING PLAN) DOES NOT HAVE A | | | VERIFIABLE DIGITAL SIGNATURE AND SEAL BY THE ENGINEER | | | OF RECORD- SEC. 471.025 AND SEC. 61G15-23.005 FLORIDA | | | ADMINISTRATIVE CODE. THE POOL PLUMBING FOR THE PERMIT | | | WILL BE APPROVED WHEN THE DIGITALLY SIGNED AND SEALED | | | PLAN IS SUBMITTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-17 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-17 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2023-01-17 15:31:58 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23010183 | | | 1/17/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) POOL PLANS HAVE NOT BEEN SUBMITTED FOR REVIEW AS | | | REQUIRED BY SECS. 107.2.1 & 107.3.5.4 WPB. PLEASE | | | SUBMIT COMPLETE PLANS INCLUDING A POOL PLUMBING SITE | | | PLAN THAT SHOWS THE PIPING RUNS FROM THE POOL TO THE | | | RECIRCULATION EQUIPMENT. | | | A) PROVIDE A PIPING DIAGRAM OR SCHEMATIC DRAWING | | | SHOWING THE PRESSURE AND SUCTION PIPE SIZES AND FPM | | | FLOWS- SEC. R4501.6.3 FBC RES. | | | B) PROVIDE POOL AND SPA SPECIFICATIONS INCLUDING THE | | | POOL SIZE, DEPTH, AREA, VOLUME IN GALLONS, DESIGN FLOW | | | RATE, SYSTEM FLOW RATE, AND TURNOVER TIME- SEC. | | | R4501.6.1 FBC RES. | | | C) PROVIDE A RECIRCULATION EQUIPMENT SCHEDULE THAT | | | INCLUDES THE MAKES AND MODELS OF THE PUMP, FILTER, | | | CHLORINATOR, HEATER (IF APPLICABLE), AND UNBLOCKABLE | | | DRAIN ASSEMBLY INCLUDING FLOW RATE- SECS. R4501.6.2, | | | R4501.6.6, R4501.7.2, R4501.20 & R4501.21.3 FBC RES. | | | D) PROVIDE TDH CALCULATIONS, AND THE PUMP CURVE ON THE | | | PLAN MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE | | | SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & | | | R4501.7.2 & R4501.7.3 FBC RES. | | | | | | 2) PROVIDE ON THE PLAN A LIST OF CONFORMANCE STANDARDS | | | IN COMPLIANCE WITH SEC. R4501.6.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-13 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-13 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-14 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-14 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2023-02-14 11:29:00 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SIGNED AND SEALED DRAWINGS RP-1, RP-2, RP-3, RP-5, | | | RP-6 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-01 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-01 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2023-02-01 15:12:49 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-03-21 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-03-21 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-02-27 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-27 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-20 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-01-20 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-01-20 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2023-01-20 09:32:18 | FAILED | | | 1/20/2023 | | | | | | PLEASE LABEL THE REAR AND SIDE SETBACK OF THE POOL. | | | | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] | | | | | | |
|
|