Plan Review Details - Permit 23010157
Plan Review Stops For Permit 23010157
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-13 Cont ID  
Sent By cthroop Date 2023-03-13 Time 15:03 Rev Time 0.00
Received By cthroop Date 2023-03-13 Time 14:54 Sent To  
Notes
2023-03-13 15:06:062ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE AN EXISTING FLOOR PLAN OF THE ENTIRE
 STRUCTURE. IDENTIFY LOCATION OF WORK AND ADJOINING
 ROOMS. (ONLY A PARTIAL FLOOR PLAN HAS BEEN SUBMITTED
 FOR REVIEW)
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5
  
 2.IDENTIFY REQUIRED BATHROOM VENTILATION PER FBC RES
 R303.3. (IDENTIFY TYPE OF WINDOW-FIXED OR OPERABLE?)
 R303.3 BATHROOMS:
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED.
  
 4.PROVIDE SMOKE ALARMS. (IDENTIFY LOCATION OF SMOKE
 ALARMS ON FLOOR PLAN)
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 NEW COMMENT:
  
 5. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By cthroop Date 2023-02-06 Time 16:44 Rev Time 0.00
Received By cthroop Date 2023-02-06 Time 16:12 Sent To  
Notes
2023-02-06 17:01:221ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE AN EXISTING FLOOR PLAN OF THE ENTIRE
 STRUCTURE. IDENTIFY LOCATION OF WORK AND ADJOINING
 ROOMS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5
  
 2.IDENTIFY REQUIRED BATHROOM VENTILATION PER FBC RES
 R303.3.
 R303.3 BATHROOMS:
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED.
  
 4.PROVIDE SMOKE ALARMS.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-13 Cont ID  
Sent By cthroop Date 2023-03-13 Time 15:36 Rev Time 0.00
Received By cthroop Date 2023-02-27 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-06 Cont ID  
Sent By cthroop Date 2023-02-06 Time 17:01 Rev Time 0.00
Received By cthroop Date 2023-01-19 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-02-28 Cont ID  
Sent By ccole Date 2023-02-28 Time 07:38 Rev Time 0.00
Received By ccole Date 2023-02-28 Time 07:34 Sent To  
Notes
2023-02-28 07:40:442ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23010157
 2/28/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE COPIED BELOW- PLEASE COMPLY.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR PLUMBING WITH
 NOTES AND DETAILS. CLARIFY IF THE BATH FIXTURES AND
 FAUCETS WILL BE REPLACED INCLUDING THE SHOWER PAN AND
 SHOWER VALVE- SEC. 107.2.1 WPB.
  
 2) PLEASE NOTE THAT PLANS SUBMITTED FOR REVIEW AND
 PERMITTING SHALL BEAR THE PRINTED NAME AND SIGNATURE OF
 THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-20 Cont ID  
Sent By ccole Date 2023-01-20 Time 08:10 Rev Time 0.00
Received By ccole Date 2023-01-20 Time 07:44 Sent To  
Notes
2023-01-20 08:10:351ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23010157
 1/20/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR PLUMBING WITH
 NOTES AND DETAILS. CLARIFY IF THE BATH FIXTURES AND
 FAUCETS WILL BE REPLACED INCLUDING THE SHOWER PAN AND
 SHOWER VALVE- SEC. 107.2.1 WPB.
  
 2) PLEASE NOTE THAT PLANS SUBMITTED FOR REVIEW AND
 PERMITTING SHALL BEAR THE PRINTED NAME AND SIGNATURE OF
 THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-02-06 Cont ID  
Sent By cthroop Date 2023-02-06 Time 17:01 Rev Time 0.00
Received By cthroop Date 2023-02-06 Time 16:12 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved