Plan Review Details - Permit 23010109
Plan Review Stops For Permit 23010109
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By rmcdouga Date 2023-03-10 Time 11:26 Rev Time 0.00
Received By rmcdouga Date 2023-03-10 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-15 Cont ID  
Sent By rperdomo Date 2023-02-15 Time 11:52 Rev Time 0.00
Received By rperdomo Date 2023-02-15 Time 11:01 Sent To  
Notes
2023-02-15 11:52:38FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE SPECIFICATIONS OF THE 48KW DIESEL GENERATOR,
 EMERGENCY SHUT DOWN SWITCH, AND THE ATS. FBC 107.2
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By cwalker Date 2023-02-07 Time   Rev Time  
Received By cwalker Date 2023-02-07 Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2023-02-09 Cont ID  
Sent By ccole Date 2023-02-09 Time 15:42 Rev Time 0.00
Received By ccole Date 2023-02-09 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-29 Cont ID  
Sent By lmarchan Date 2023-03-29 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2023-02-06 Time 16:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-02-07 Cont ID  
Sent By medwards Date 2023-02-07 Time 10:44 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 10:44 Sent To  
Notes
2023-02-07 10:44:441ST REVIEW FMC
 PERMIT: 23010109
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS A CHANGE OUT OF AN EXISTING DIESEL
 GENERATOR? IF NOT PLEASE PROVIDE THE GENERATOR SPECS.
  
 2) HOW IS THE FUEL TANK FOR THIS GENERATOR TO BE
 FILLED? PROVIDE A MECHANICAL DRAWING SHOWING THE PIPING
 AND FILL STATION FOR THE DIESEL GENERATOR. FBC 107.3.5
  
 3) PROVIDE A SITE MAP THAT SHOWS THE DIESEL EXHAUST
 FROM THE GENERATOR IS 10 FEET FROM THE PROPERTY LINES.
 FMC 501.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-02-09 Cont ID  
Sent By ccole Date 2023-02-09 Time 15:42 Rev Time 0.00
Received By ccole Date 2023-02-09 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-10 Cont ID  
Sent By rmcdouga Date 2023-03-10 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2023-03-10 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-02-07 Cont ID  
Sent By medwards Date 2023-02-07 Time 10:45 Rev Time 0.00
Received By medwards Date 2023-02-07 Time 10:45 Sent To  
Notes
2023-02-07 10:46:28PROVIDE DRAWINGS WITH THE DESIGNERS DIGITAL SIGNATURE.
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-29 Cont ID  
Sent By ESchneid Date 2023-03-29 Time 15:59 Rev Time 0.50
Received By eschneid Date 2023-03-03 Time 15:05 Sent To  
Notes
2023-03-29 15:59:41FAILED
  
 1) PROVIDE A SURVEY SHOWING THE AREA OF WORK. THE
 SURVEY SHALL INCLUDE DIMENSIONS, EXISTING FEATURES AND
 ANY EXISTING LANDSCAPE.
  
 2) THE INSTALLATION OF A GROUND MOUNTED GENERATOR
 MODIFIES THE APPROVED SITE PLAN, WHICH REQUIRES THE
 SUBMITTAL TO AND APPROVAL BY THE PLANNING DIVISION OF A
 MINOR PLANNED DEVELOPMENT AMENDMENT. PLEASE CONTACT
 ERIC SCHNEIDER FOR A COPY OF THE APPLICAITON.
  
 3) THE PLANS SHOW THE TOTAL HEIGHT OF THE GENERATOR,
 INCLUDING THE FUEL TANK AND PAD, FROM GRADE AT 8.5
 FEET. THE FULL HEIGHT OF THE GENERATOR MUST BE
 SCREENED. PROVIDE DETAILS ON THE SCREENING. ANY NEW
 SCREEN FENCING REQUIRES A SEPARATE PERMIT WITH PLANS.
  
 4) ANY LANDSCAPE REMOVED MUST BE REPLACED ELSEWHERE IN
 THE AREA. PRIOR TO THE REMOVAL OF ANY TREES, A TREE
 ALTERATION PERMIT IS REQUIRED TO BE ISSUED.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved