| 2023-04-11 16:48:59 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23010094 |
| | 19118 GLENMOOR DR |
| | |
| | |
| | NOTE: |
| | LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING. |
| | SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION |
| | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | |
| | 1-DRAWINGS SUBMITTED DON'T HAVE THE SEAL/SIGNATURE OF |
| | THE ENGINEER OF RECORD. PLANS/DOCUMENTS NEED TO HAVE |
| | THE ORIGINAL SEAL/SIGNATURE OF THE ENGINEER OF RECORD |
| | AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471 |
| | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | NOTE: THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT |
| | PLANS/DOCUMENTS WITH ENGINEER'S VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | ENGINEERS |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2- FLOOR PLAN ON SHEET S-1.0 SHOWS NEW SLABS (BY |
| | OTHERS) OUTSIDE THE NEW SLIDING GLASS DOORS. THIS IS A |
| | CONDOMINIUM. OWNER ONLY OWNS THE UNIT, THE AREA OUTSIDE |
| | THE BUILDING IS NOT OWNED BY THIS OWNER. ANY WORK |
| | OUTSIDE THIS UNIT NEED TO BE DONE BY THE OWNER OF THE |
| | PROPERTY. REVISE PLANS AS REQUIRED. DON???T INCLUDE |
| | THIS WORK. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- REVISE OCCUPANCY GROUP SPECIFIED ON SHEET S-0.0. |
| | THIS IS A CONDOMINIUM. THE OCCUPANCY CLASSIFICATION IS |
| | R2 NOT R3. REVISE AS REQUIRED. SEC. 310.4 FBC-BUILDING. |
| | |
| | 4- PROVIDE DOOR STRUCTURAL BUCK DETAIL SHOWING |
| | COMPLIANCE WITH SEC. 1710.3 FBC-BUILDING. SPECIFY |
| | STRUCTURAL BUCK SIZE AND FASTENING. |
| | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| | THE DOOR FRAME AS REQUIRED BY SEC. SEC. 1710.3 |
| | FBC-BUILDING. |
| | |
| | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR WALL |
| | FLASHING AT ALL EXTERIOR OPENINGS AS REQUIRED BY SEC. |
| | 1405.4 FBC-BUILDING. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |