| Plan Review Stops For Permit 23010062 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-30 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-30 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-13 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-01-13 15:31:20 | ELECTRIC REVIEW FAILED | | | 1) PROVIDE PANEL SCHEDULE AND LOAD CALCULATION FOR | | | UPSTREAM ELECTRIC PANEL. PROVIDE A NEUTRAL CALCULATION | | | IF REDUCED SIZE CONDUCTOR IS USED. NEC 215.5 | | | 2) CORRECT #4 CU CONDUCTOR SIZE TO NEW 100 AMP ELECTRIC | | | SUB PANEL TO COMPLY WITH NEC 310.15. #4 CU CONDUCTOR | | | RATED AT 85 AMPS, NEXT SIZE STANDARD BREAKER IS 90 AMP. | | | NEC 310.15 AND NEC 240.6 | | | 3) PROVIDE FLOOR PLAN DETAILING ALL ELECTRICAL EQIPMENT | | | LOCATIONS. FBC 107.2 | | | 4) INCLUDE ON ALL CONTRACTOR PREPARED DRAWINGS THE | | | NAME, LICENSE NUMBER AND SIGNATURE OF THE CONTRACTOR . | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-03 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-02 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-30 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-26 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-13 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-10 |
Time |
12:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-03 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-03 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-01-27 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-01-27 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2023-01-27 06:39:33 | 2ND PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | PREVIOUS COMMENTS NOT ADDRESSED. | | | | | | 1. SECOND REQUEST ---- 2017 WPB AMEND 107.3.5.3 (12) - | | | PLEASE SUBMIT A SIMPLE FLOOR PLAN SHOWING THE LOCATION | | | OF THE WATER HEATER. IF THE LOCATION OF THE TANKLESS IS | | | IN A DIFFERENT LOCATION THAN THE OLD TANK WATER HEATER, | | | THEN SHOW THE NEW AND OLD LOCATIONS AND THE ROUTING OF | | | THE NEW WATER LINES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-01-12 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-01-12 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2023-01-12 10:37:58 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMEND 107.3.5.3 (12) - PLEASE SUBMIT A | | | SIMPLE FLOOR PLAN SHOWING THE LOCATION OF THE WATER | | | HEATER. IF THE LOCATION OF THE TANKLESS IS IN A | | | DIFFERENT LOCATION THAN THE OLD TANK WATER HEATER, THEN | | | SHOW THE NEW AND OLD LOCATIONS AND THE ROUTING OF THE | | | NEW WATER LINES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
N |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-03 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-30 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-30 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-13 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-13 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2023-01-13 15:34:54 | CONTRACTOR PREPARED DRAWINGS REQUIRE NAME, LICENSE | | | NUMBER AND SIGNATURE OF CONTRACTOR | | | | | | THE DESIGNER OF RECORD WHO PREPARED DRAWINGS SHALL | | | PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 WPB, | | | AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|