Plan Review Details - Permit 23010061
Plan Review Stops For Permit 23010061
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By cpuell Date 2023-01-05 Time 11:56 Rev Time 0.00
Received By cpuell Date 2023-01-05 Time 11:56 Sent To  
Notes
2023-01-05 11:56:38APPEARS THAT IL BELLAGIO IS MOVING FROM 600 S ROSEMARY
 AVE 170 TO 700 S ROSEMARY AVE 124. ADDRESS APPROPRIATE
 FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status N Date 2023-04-04 Cont ID  
Sent By jwitmer Date 2023-04-04 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2023-04-04 Time 10:28 Sent To  
Notes
2023-04-04 10:29:29NO ASBESTOS, CITY PLACE BUILT IN THE MID- TO LATE
 1990S.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-01-18 Cont ID  
Sent By jwitmer Date 2023-01-18 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2023-01-18 Time 07:59 Sent To  
Notes
2023-01-18 08:35:26COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By pvalenti Date 2023-05-31 Time 14:43 Rev Time 0.00
Received By pvalenti Date 2023-05-31 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-25 Cont ID  
Sent By shill Date 2023-05-25 Time 18:38 Rev Time 0.00
Received By shill Date 2023-05-25 Time 18:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-04 Cont ID  
Sent By jwitmer Date 2023-04-04 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2023-04-04 Time 09:01 Sent To  
Notes
2023-04-04 10:26:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23010061
 ADD: 700 S ROSEMARY AVE # 124
 CONT: JONATHAN ANDREW CONSTRUCTION INC.
 TEL: 305-661-9500
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 04TH/ 2023
 ACTION: PASSED/ PROVISOS:
  
 1) DEFERRED SUBMITTALS: EXTERIOR DOORS, MULLIONS,
 WINDOWS, HYDRAULIC SINGLE SWING SYSTEM, STOREFRONTS &
 PRE-ENGINEERED A/C STANDS. W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 2) BUILDING PROVISO. WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 3A) DEFERRED SUBMITTAL: NEW HYDRAULIC FOLDING DOOR
 SYSTEM.
 3B) BUILDING PROVISO: THE NEW HYDRAULIC FOLDING DOOR
 MEETS THE REQUIREMENTS FOR SLOPED GLAZING IN ACCORDANCE
 WITH 2405.2 OF THE 2020 FBC-BUILDING CODE.
  
 4) REMOVED FROM PROJECT, CANOPY.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-18 Cont ID  
Sent By jwitmer Date 2023-01-18 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2023-01-18 Time 07:59 Sent To  
Notes
2023-01-18 11:36:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23010061
 ADD: 700 S ROSEMARY AVE # 124
 CONT: JONATHAN ANDREW CONSTRUCTION INC.
 TEL: 305-661-9500
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 18TH/ 2023
 ACTION: DENIED
  
 1) SHEET 029 LS-1 THE LIFE SAFETY PLAN. THE LIFE SAFETY
 PLAN INDICATES THERE ARE 5 EXITS. EXITS 2, 4 & 5 MEET
 THE REQUIREMENTS FOR EXITS, A MEANS OF EGRESS. PLEASE
 REVIEW IN THE 2020 FBC-BUILDING CODE 1010.1.2 EGRESS
 DOORS SHALL BE OF THE PIVOTED OR SIDE HINGED SWINGING
 TYPE, ALSO SEE EXCEPTIONS. EXIT # 4 IS THE POWER
 SLIDING GLASS DOORS, THIS TYPE OF DOOR WILL ALSO NEED
 TO COMPLY WITH 1010.1.4.3. EXITS 1 & 3 ACCORDION
 HORIZONTAL DOORS DOES MEET THE INTENT OF SECTION
 1010.1.4.3. EXIT 2 & 4 MEET THE OCCUPANT LOADS STATED.
 EXITS 2 & 4 ALSO MEET THE ?? THE DIAGONAL DISTANCE
 APART FOR THE ROOM SERVED.
  
 2A) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1
 PARTITION PLAN SHOW A PRIVATE DINING ROOM, ROOMS ARE
 NOT IDENTIFIED WITH ROOM NUMBERS. THE DINING ROOM HAS
 14 SEATS AROUND THE TABLE AND ENTRY THROUGH DOOR # 07
 HIDDEN TOP AND BOTTOM TRACKS. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE1010.1.2 EXCEPTION # 9 MANUALLY
 OPERATED HORIZONTAL SLIDING DOOR ARE PERMITTED IN A
 MEANS OF EGRESS FROM SPACES WITH AN OCCUPANT LOAD OF 10
 OR LESS.
  
 2B) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1
 PARTITION PLAN SHOW A PRIVATE DINING ROOMS WITH DOOR
 OPENINGS 7 & 8. THE DOOR SCHEDULE SHEET 005 A1.2 LIST
 THESE DOOR TYPES AS DOOR TYPE 3 SLIDING DOOR ASSEMBLY
 HIDDEN TOP AND BOTTOM TRACK. PLEASE SHOW COMPLIANCE
 WITH THE 2020 FBC-ACCESSIBILITY CODE SECTION 302.2.
 OPENINGS IN THE FLOOR. THIS COMMENT HOLDS FOR ALL DOORS
 WITH BOTTOM TRACKS.
  
 3A) SHEET 029 LS-1 THE LIFE SAFETY PLAN & SHEET 001 A-1
 PARTITION PLAN SHOW A PRIVATE DINING ROOM, ROOMS ARE
 NOT IDENTIFIED WITH ROOM NUMBERS. THE PRIVATE DINING
 ROOM IN FRONT OF THE JUST ADDRESSED ABOVE HAS
 APPROXIMATELY 22 SEATS WITH TABLES AND ENTRY THROUGH
 DOOR # 08 IT APPEARS BARN STYLE DOORS. DOOR STYLE # 3
 HIDDEN TOP AND BOTTOM TRACKS. PLEASE REVIEW THE 2020
 FBC-BUILDING CODE1010.1.2 EXCEPTION # 9 MANUALLY
 OPERATED HORIZONTAL SLIDING DOOR ARE PERMITTED IN A
 MEANS OF EGRESS FROM SPACES WITH AN OCCUPANT LOAD OF 10
 OR LESS.
  
 3B) THERE APPEARS TO BE ANOTHER SET OF DOORS INTO THIS
 SPACE, THIS OPENING IS NOT IDENTIFIED WITH A DOOR
 IDENTIFICATION TAG, BUT THE PLAN SHOWS A PAIR OF SWING
 DOORS. AS SHOWN THE DOORS DO NOT TOTALLY ENCLOSE THIS
 DINING ROOM. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 4) THERE IS A THIRD PRIVATE DINING ROOM ACROSS THE MAIN
 DINING ROOM, AGAIN ROOMS DO NOT HAVE IDENTIFICATION
 TAGS, DOOR # 9 DOOR STYLE 3 HIDDEN TOP AND BOTTOM
 TRACKS. PLEASE REVIEW THE 2020 FBC-BUILDING
 CODE1010.1.2 EXCEPTION # 9 MANUALLY OPERATED HORIZONTAL
 SLIDING DOOR ARE PERMITTED IN A MEANS OF EGRESS FROM
 SPACES WITH AN OCCUPANT LOAD OF 10 OR LESS.
  
 5) SHEET 029 LS-1 THE LIFE SAFETY PLAN SHOWS THE
 ACCESSIBLE WHEELCHAIR LOCATIONS BUT NOT WITH THE
 REQUIRED CLEAR FLOOR SPACE. 2020 FBC-ACCESSIBILITY CODE
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 6A) SHEET 001 A-1 SHOWS DETAIL S/A-1.1, THIS IS THE
 DROPPED SECTION OF THE BAR FOR ACCESSIBILITY. THE
 DETAIL LACKS SHOWING CLEAR FLOOR OR GROUND SPACE
 SECTION 902.2 OF THE 2020 FBC-ACCESSIBILITY CODE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6B) BAR DETAILS WILL NEED TO SHOW COMPLIANCE WITH THE
 2020 FBC-ACCESSIBILITY CODE SECTIONS:
 306.2 TOE CLEARANCE306.2.2 MAXIMUM DEPTH 306.2.3
 MINIMUM DEPTH 306.2.4 & 306.2.5 AND
 306.3 KNEE CLEARANCE. 306.3.1-306.3.5.
  
 7A) SHEET 029 LIFE SAFETY PLAN SHOWS ACCESSIBLE SEATING
 JUST TO THE RIGHT OF EXIT # 4 ON THE EXTERIOR OF THE
 BUILDING. SHEET 001 A-1 THE PARTITION PLAN SHOWS A
 DETAIL FOR THIS AREA, DETAIL B/A-1.1. THE DETAIL
 INDICATES ON THE EXTERIOR SIDE THE HEIGHT OF THE
 COUNTERTOP IS 42 INCHES IN HEIGHT. THIS HEIGHT DOES NOT
 COMPLY WITH 902.3 HEIGHT. THE TOPS OF DINING SURFACES
 AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7B) FIXED WALL TYPE COUNTERTOP DETAILS WILL NEED TO
 SHOW COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
 306.2 TOE CLEARANCE306.2.2 MAXIMUM DEPTH 306.2.3
 MINIMUM DEPTH 306.2.4 & 306.2.5 AND
 306.3 KNEE CLEARANCE. 306.3.1-306.3.5.
  
 8) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 9) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 10) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 12) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) THE ARCHITECTURAL & STRUCTURAL SHEETS SHOW WELDED
 STEEL CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 14A) SHEET 006 A-1.2 DETAIL A SHOWS THE USE OF A NEW
 FOLDING DOOR, CROWN DOOR OR EQUAL. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. DRAWINGS & SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES
 "CODE SECTIONS SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 14B) PLEASE PROVIDE DOCUMENTATION WHERE THE NEW FOLDING
 DOOR MEETS THE REQUIREMENTS FOR SLOPED GLAZING IN
 ACCORDANCE WITH 2405.2 OF THE 2020 FBC-BUILDING CODE.
  
 15) SHEET 028 G-1 NOTES AND FINISHES. WATER CLOSET GRAB
 BARS. THE REAR GRAB BAR HEIGHT IS GIVEN 32-36 INCHES
 FROM CENTERLINE FROM FINISH FLOOR. SIDE WALL GRAB BAR
 33-36 INCHES CENTERLINE. 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 16A) I???VE LOCATED THE RESTROOM ELEVATION PLANS A-1.3-
 A-1.5. I SEE WALL TAGS FOR ROOM FINISHES BUT I DO NOT
 FIND THE KEY OR SCHEDULE TO IDENTIFY WALL AND FLOOR
 FINISHES. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 16B) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 17) SHEET 056 S1.00 STATEMENT ON FLOOR PLAN. FOUNDATION
 DESIGN FOR CANOPY STRUCTURE PENDING REACTIONS FROM
 SPECIALTY ENGINEER & COORDINATE WITH UNDERGROUND
 UTILITIES. NO INFORMATION HAS BEEN PROVIDED. CANOPY
 WILL BE UNDER SEPARATE PERMIT. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 18) SHEET 057 S1.01 THE SECOND FLOOR FRAMING PLAN FLOOR
 PENETRATIONS & 060 S2.01 DETAILS. STATEMENT ON PLANS.
 SEE MECHANICAL DRAWINGS FOR THE EXACT SHAFT SIZE AND
 LOCATION. PLEASE PROVIDE LOCATION. AND SIZE BUT ALSO
 THE MATERIAL THE PROPOSED SHAFTS ARE GOING TO BE MADE
 OF. 2020 FBC-BUILDING SECTIONS:
 713.2 CONSTRUCTION
 713.3.MATERIAL
 713.4 FIRE-RESISTANCE RATING
 713.5 CONTINUITY
  
 19) THE STRUCTURAL SHEETS HAVE NO DETAILS FOR ROOF TOP
 CURB CONNECTIONS TO THE ROOF FRAMING NOR THE ROOF TOP
 EXHAUST FANS TO THE CURB.
 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 20) 045 M-410 ROOF DUCT SUPPORT AND RAISED ROOF TOP
 MOUNTED MECHANICAL EQUIPMENT ARE TO MEET THE
 REQUIREMENTS FOUND IN TABLE 1510.10 OF THE 2020
 FBC-BUILDING CODE.
  
 21) PLEASE PROVIDE DETAILS FOR CUTTING FOR PENETRATIONS
 FOR NEW HOLES IN THE 2ND FLOOR SLAB AND ROOF DECK. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 22) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-16 Cont ID  
Sent By jleahy Date 2023-05-16 Time 16:25 Rev Time 0.00
Received By jleahy Date 2023-05-16 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-10 Cont ID  
Sent By mpeterso Date 2023-04-10 Time 11:06 Rev Time 0.00
Received By mpeterso Date 2023-04-10 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-10 Cont ID  
Sent By mpeterso Date 2023-01-10 Time 11:34 Rev Time 0.00
Received By mpeterso Date 2023-01-10 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-05-16 Cont ID  
Sent By jleahy Date 2023-05-16 Time 16:25 Rev Time 0.00
Received By jleahy Date 2023-05-16 Time 16:25 Sent To  
Notes
2023-05-16 16:26:07VOICE AND DATA AS PER PLANS JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-04-11 Cont ID  
Sent By parking Date 2023-04-11 Time 14:08 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-05-30 Cont ID  
Sent By pleduc Date 2023-05-30 Time   Rev Time 0.00
Received By pleduc Date 2023-05-30 Time 09:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-12 Cont ID  
Sent By pleduc Date 2023-05-12 Time   Rev Time 0.00
Received By pleduc Date 2023-05-12 Time 12:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By pleduc Date 2023-04-05 Time   Rev Time 0.00
Received By pleduc Date 2023-04-04 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By pleduc Date 2023-01-06 Time   Rev Time 0.00
Received By pleduc Date 2023-01-06 Time 11:47 Sent To  
Notes
2023-01-06 11:52:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF EXIT NO. 1 & EXIT NO. 3.,
 HOWEVER, THE EXITS DOORS APPEAR TO BE "BIFOLD" TYPE AND
 DO NOT APPEAR TO COMPLY WITH NFPA 101, CH 7, MEANS OF
 EGRESS.
  
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO THE
 GENERAL REQUIREMENTS OF SECTION 7.1 AND TO THE SPECIAL
 REQUIREMENTS
 OF 7.2.1
  
 7.2.1.4 SWING AND FORCE TO OPEN
  
 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY
 DOOR
 ASSEMBLY INA MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR PIVOTED SWINGING TYPE, AND SHALL BE
 INSTALLED TO BE CAPABLE OF SWINGING FROM
 ANY POSITION TO THE FULL REQUIRED WIDTH OF THE OPENING
 IN WHICH IT IS
 INSTALLED, UNLESS OTHERWISE SPECIFIED AS FOLLOWS:
 (1) DOOR ASSEMBLIES IN DWELLING UNITS, AS PROVIDED IN
 CHAPTER 24, SHALL
 BE PERMITTED.
 (2) DOOR ASSEMBLIES IN RESIDENTIAL BOARD AND CARE
 OCCUPANCIES, AS
 PROVIDED IN CHAPTERS 32 AND 33, SHALL BE PERMITTED.
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTAL-SLIDING OR
 VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES
 THAT ARE PART OF
 THE REQUIRED MEANS OF EGRESS SHALL BE PERMITTED,
 PROVIDED THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN THE
 FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE
 GENERAL PUBLIC
  
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL BE A
 READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS THAN
 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOL LOWS: THIS DOOR TO REMAIN OPEN WHEN THE SPACE
 IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED POSI TION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE SPACE
 WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE
 THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED WITH
 HORI ZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR DOOR
 ASSEMBLIES.
 (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE
 PERMITTED UNDER ANY
 OF THE FOLLOWING CONDITIONS:
 (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND
 CORREC TIONAL OCCUPANCIES, AS PROVIDED IN CHAPTERS 22
 AND 23, SHALL
 BE PERMITTED.
 (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR
 FOLDING DOOR
 ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL BE PERMITTED.
 (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43,
 HORIZONTAL SLIDING DOOR ASSEMBLIES SERVING A ROOM OR
 AREA WITH AN OCCU PANT LOAD OF FEWER THAN 10 SHALL BE
 PERMITTED, PROVIDED THAT
 ALL OF THE FOLLOWING CRITERIA ARE MET:
 I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH
 HAZARD
 CONTENTS.
 II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER
 SIDE
 WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN
 THE
 DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 LBF
 (133 N)
 TO SET THE DOOR LEAF IN MOTION AND IS NOT MORE THAN 15
 LBF
 (67 N) TO CLOSE THE DOOR ASSEMBLY OR OPEN IT TO THE
 MINI MUM REQUIRED WIDTH.
 IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE
 PROTEC TION RATING, AND, WHERE RATED, IS SELF-CLOSING
 OR AUTOMATIC CLOSING BY MEANS OF SMOKE DETECTION IN
 ACCORDANCE WITH
 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80.
 V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE
 SELF-LATCHING HAVE
 A LATCH OR OTHER MECHANISM THAT ENSURES THAT THE DOOR
 LEAF
 WILL NOT REBOUND INTO A PARTIALLY OPEN POSITION IF
 FORCEFULLY
 CLOSED.
 (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL
 AREAS, AND
 STORAGE AREAS WITH AN OCCUPANT LOAD NOT EXCEEDING 10
 CONTAIN
 ONLY LOW OR ORDINARY HAZARD CONTENTS, DOOR OPENINGS TO
 SUCH
 AREAS AND PRIVATE GARAGES SHALL BE PERMITTED TO BE
 HORIZONTAL SLIDING DOOR ASSEMBLIES.
 (5) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL
 AREAS, AND STORAGE
 AREAS WITH AN OCCUPANT LOAD NOT EXCEEDING 10 CONTAIN
 ONLY LOW OR
 ORDINARY HAZARD CONTENTS, DOOR OPENINGS TO SUCH AREAS
 AND PRIVATE
 GARAGES SHALL BE PERMITTED TO BE VERTICAL-ROLLING DOOR
 ASSEMBLIES.
 (6) REVOLVING DOOR ASSEMBLIES COMPLYING WITH 7.2.1.10
 SHALL BE
 PERMITTED.
 (7) EXISTING FUSIBLE LINK???OPERATED HORIZONTAL-SLIDING
 OR VERTICAL-ROLLING
 FIRE DOOR ASSEMBLIES SHALL BE PERMITTED TO BE USED AS
 PROVIDED IN
 CHAPTERS 39, 40, AND 42.
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATION WITH
 SPECIFIC CODE REFERENECES AND DETAILS
  
  
  
 1A) THE EXIT DOORS NOTED ABOVE ARE INDICATED WITH EXIT
 SIGNS OVER THEM.
  
 SHOULD THOSE DOES NOT MEET THE REQUIRMENTS OF EXIT
 DOORS, THOSE EXIT SIGNS SHALL BE REMOVED PER NFPA 101
 CH 7, MEANS OF EGRESS.
  
 PLEASE REVIEW AND COMPLY AS APPLICABLE.
  
  
  
 2) THERE ARE INDICATIONS THAT THE BUILDING HAS A FIRE
 SPRINKLER SYSTEM.
  
 THERE ARE NO INDICATIONS OF FIRE SPRINKLER WORK ON THE
 LIFE SAFETY, DEMO, NOR FLOOR PLAN SHEETS.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS.
  
 ANY WORK ON THE FIRE SPRINKLER, INCLUDING DEMO, SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS PER NFPA
 13.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLDGMENT ON THOSE PLAN SHEETS.
  
  
  
 3) THERE ARE INDICATIONS THAT THE BUILDING HAS A FIRE
 ALRM SYSTEM.
  
 THERE ARE INDICATIONS OF FIRE ALARM WORK ON FIRE ALARM
 PLAN SHEETS.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE
 DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS PER NFPA
 72.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLDGMENT ON THOSE PLAN SHEETS.
  
  
  
 4) THERE ARE INDICATIONS OF A MECHANICAL HOOD SYSTEM IN
 THE KITCHEN.
  
 THE HOOD AND FIRE SUPPRESSION SYSTEMS SHALL BE
 SUBMITTED & INSTALLED UNDER SEPARATE PERMITS & SHOP
 DRAWINGS PER NFPA 96
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLDGMENT ON THAT PLAN SHEETS.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2023-05-30 Cont ID  
Sent By ccole Date 2023-05-30 Time 12:01 Rev Time 0.00
Received By ccole Date 2023-05-30 Time 07:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2023-05-15 Cont ID  
Sent By ccole Date 2023-05-15 Time 12:00 Rev Time 0.00
Received By ccole Date 2023-05-15 Time 08:56 Sent To  
Notes
2023-05-15 12:03:103RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 23010061
 5/15/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEW ARE COPIED BELOW. I HAVE PROVIDED
 ADDITIONAL NOTES BELOW EACH COMMENT FOR CLARIFICATION.
 PLEASE CORRECT THE PLANS TO AVOID A PENALTY FEE OF FOUR
 TIMES THE AMOUNT OF THE PERMIT FEE- SEE FL. STATUTE
 553.80. ALSO AS PREVIOUSLY REQUESTED PROVIDE THE
 REQUESTED RESPONSE NARRATIVE FROM THE ENGINEER
 ADDRESSING ALL OF THE COMMENTS.
  
  
 1) FAILED.SHEET P-320 GAS RISER CORRECTIONS:
 A) BASED ON THE LONGEST LENGTH METHOD FOR GAS PIPE
 SIZING, THE 1/2- INCH PIPE TO THE GWH IS UNDERSIZED PER
 TABLE 402.4(2) FBC FG. THE MINIMUM SIZE REQUIRED IS
 1-1/4-INCH.
 B) PLEASE LABEL THE SIZES OF THE INDIVIDUAL SUPPLY
 PIPES TO THE COOKING APPLIANCES- SEC. 402.3 FBC FG.
 C) PLEASE CLARIFY THE PURPOSE OF THE GAS PIPING
 MANIFOLDS FOR EACH COOKING LINE- SEC. 107.2.1 WPB.
  
 2) FAILED. SHEETS P-210 & M-300: THE COMBUSTION AIR
 CALCULATIONS ARE NOT IN COMPLIANCE WITH SEC. 304.9.3
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR.
 KSF IS SUPPLYING MAKEUP AIR FOR THE HOOD EXHAUST, AND
 FCU-3 IS SUPPLYING OA FOR THE KITCHEN OCCUPANTS.
 ADDITIONAL AIR IS REQUIRED FOR COMBUSTION AIR.
  
 3) FAILED. P-210: PLEASE SHOW THE GWH INTAKE AND
 EXHAUST PIPE TERMINATION LOCATIONS ON THE PLAN- SEC.
 AND TABLE 503.8 FBC FG.
  
 4) FAILED.P-210 & M-300: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE WOOD/COAL/GAS OVEN TO VERIFY THE
 APPLIANCE MEETS CURRENT LISTING STANDARDS AND PROVIDES
 RECOMMENDATIONS FOR THE EXHAUST SYSTEM- SECS. 305.1 &
 623.1 FBC FG.
  
 A) PROVIDE AN EXHAUST VENTING DIAGRAM SHOWING THE TYPE
 AND SIZE OF VENT, VENT RUN LENGTH, AND TERMINATION
 LOCATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 16:34 Rev Time 0.00
Received By ccole Date 2023-04-04 Time 15:35 Sent To  
Notes
2023-04-05 16:35:291ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23010061
 4/5/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-320 GAS RISER CORRECTIONS:
 A) BASED ON THE LONGEST LENGTH METHOD FOR GAS PIPE
 SIZING, THE 1/2- INCH PIPE TO THE GWH IS UNDERSIZED PER
 TABLE 402.4(2) FBC FG. THE MINIMUM SIZE REQUIRED IS
 1-1/4-INCH.
 B) PLEASE LABEL THE SIZES OF THE INDIVIDUAL SUPPLY
 PIPES TO THE COOKING APPLIANCES- SEC. 402.3 FBC FG.
 C) PLEASE CLARIFY THE PURPOSE OF THE GAS PIPING
 MANIFOLDS FOR EACH COOKING LINE- SEC. 107.2.1 WPB.
  
 2) SHEETS P-210 & M-300: THE COMBUSTION AIR
 CALCULATIONS ARE NOT IN COMPLIANCE WITH SEC. 304.9.3
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING'S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR.
 KSF IS SUPPLYING MAKEUP AIR FOR THE HOOD EXHAUST, AND
 FCU-3 IS SUPPLYING OA FOR THE KITCHEN OCCUPANTS.
 ADDITIONAL AIR IS REQUIRED FOR COMBUSTION AIR.
  
 3) P-210: PLEASE SHOW THE GWH INTAKE AND EXHAUST PIPE
 TERMINATION LOCATIONS ON THE PLAN- SEC. AND TABLE 503.8
 FBC FG.
  
 4) P-210 & M-300: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE WOOD/COAL/GAS OVEN TO VERIFY THE
 APPLIANCE MEETS CURRENT LISTING STANDARDS AND PROVIDE
 RECOMMENDATIONS FOR THE EXHAUST SYSTEM- SECS. 305.1 &
 623.1 FBC FG.
  
 A) PROVIDE AN EXHAUST VENTING DIAGRAM SHOWING THE TYOE
 AND SIZE OF VENT, VNT RUN LENGTH, AND TERMINATION
 LOCATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By ccole Date 2023-01-06 Time 13:11 Rev Time 0.00
Received By ccole Date 2023-01-06 Time 10:11 Sent To  
Notes
2023-01-06 13:13:151ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23010061
 1/3/2023
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-210: COMPLETE GAS PLANS WERE NOT UPLOADED
 FOR REVIEW BUT ARE REQUIRED PER SEC. 107.3.5.1.5 WPB.
 PLEASE PROVIDE THE FOLLOWING COMPLIANCE DRAWINGS AND
 DETAILS PER FBC FG.
 A) GAS RISER- SEC. 402.1.
  
 B) COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES- SECS. 304.1.
  
 C) WATER HEATER COMBUSTION AIR AND VENTING- SECS. 503.1
 & 624.1. THE PLAN SHOWS A DIRECT VENT SYSTEM PER
 MANUFACTURER???S RECOMMENDATION. PLEASE PROVIDE A
 DIAGRAM PER THE SPECS THAT SHOWS THE TOTAL RUN LENGTHS
 OF THE 4-INCH INTAKE AND EXHAUST PIPES AND TERMINATION
 LOCATIONS. PLEASE INCLUDE THE TYPE OF INTAKE AND
 EXHAUST PIPE MATERIAL AS RECOMMENDED BY THE
 MANUFACTURER.
  
 2) THE GAS RISER DRAWING SHALL INCLUDE THE FOLLOWING
 INFORMATION:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND
 REGULATOR VENT PIPING DETAILS (IF APPLICABLE).
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-31 Cont ID  
Sent By pvalenti Date 2023-05-31 Time 16:20 Rev Time 0.00
Received By pvalenti Date 2023-05-26 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-25 Cont ID  
Sent By shill Date 2023-05-25 Time 18:38 Rev Time 0.00
Received By shill Date 2023-05-11 Time 17:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-08 Cont ID  
Sent By lmarchan Date 2023-05-08 Time 16:25 Rev Time 0.00
Received By lmarchan Date 2023-04-03 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-18 Cont ID  
Sent By aoliver Date 2023-01-18 Time 14:31 Rev Time 0.00
Received By aoliver Date 2023-01-05 Time 09:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-01-18 Cont ID  
Sent By jwitmer Date 2023-01-18 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2023-01-18 Time 07:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By pvalenti Date 2023-05-31 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2023-05-31 Time 14:22 Sent To  
Notes
2023-05-31 15:59:24PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 FBC B 107.2.1, PROVIDE SEPERATE MECHANICAL HOOD
 PERMIT/PERMITS FOR ALL OF THE HOODS. EACH HOOD WILL
 HAVE TO BE LISTED AND IDENTIFIED ON PERMIT/PERMITS AND
 PLANS.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-05-16 Cont ID  
Sent By hmoser Date 2023-05-16 Time 14:21 Rev Time 0.00
Received By hmoser Date 2023-05-16 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-04-07 Cont ID  
Sent By medwards Date 2023-04-07 Time 09:46 Rev Time 0.00
Received By medwards Date 2023-04-07 Time 09:46 Sent To  
Notes
2023-04-07 09:47:022ND REVIEW FMC
 PERMIT: 23010061
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M-300: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATION AND
 OCCUPANT DENSITY FROM FMC TABLE 403.3.1.1 AND NOT THE
 ARCHITECTS EGRESS COUNTS.
  
 2) SHEET M-300: PROVIDE THE AIR BALANCE REPORT BASED ON
 THE CORRECTED OUTDOOR AIR CALCULATIONS. THE AIR BALANCE
 DESIGN CAN ONLY TRANSFER AIR FROM OTHER SPACES THAT IS
 ABOVE THE REQUIRED AIR FOR THAT SPACE. PLEASE SHOW THE
 AMOUNT OF AIR THAT WILL BE TRANSFERRED FROM THE DINING
 AREAS INTO THE KITCHEN IN THE AIR BALANCE REPORT. THIS
 AIR SHOULD ONLY BE THAT WHICH IS ABOVE THE AMOUNT OF
 OUTDOOR AIR REQUIRED FOR THE OCCUPANTS AND THE SPACE
 FOR THE DINING ROOMS. FMC 508.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By medwards Date 2023-01-06 Time 13:14 Rev Time 0.00
Received By medwards Date 2023-01-06 Time 13:14 Sent To  
Notes
2023-01-06 13:14:571ST REVIEW FMC
 PERMIT: 23010061
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 KITCHEN HOODS:
 1) KITCHEN HOODS AND EQUIPMENT MUST BE SUBMITTED
 SEPARATELY FOR REVIEW AND PERMITTING. ADD A NOTE TO THE
 MECHANICAL DRAWINGS STATING THAT THE KITCHEN HOODS AND
 GREASE DUCTS FOR THIS PROJECT WILL REQUIRE A SEPARATE
 PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS THEY WILL
 NOT BE REVIEWED UNDER THIS PERMIT.
  
 REFRIGERATION:
 2) REFRIGERATION PLAN HAS BEEN LOCKED AND WILL NOT BE
 PRINTED WITH THIS VERSION. REFRIGERATION EQUIPMENT MUST
 BE SUBMITTED SEPARATELY FOR REVIEW AND PERMITTING. ADD
 A NOTE TO THE MECHANICAL DRAWINGS STATING THAT THE
 REFRIGERATION FOR THIS PROJECT WILL REQUIRE A SEPARATE
 PERMIT APPLICATION AND DOCUMENT SUBMITTAL AS THEY WILL
 NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) SHEET M-200: SHOW THAT THE OUTDOOR AIR TERMINATION
 LOCATION WILL MEET THE REQUIREMENTS OF THE FMC 401.4.
  
 4) SHEET M-200: PROVIDE ON THE DRAWINGS, THE LOCATION
 OF THE OUTDOOR AIR TERMINATION FOR FCU-2 AND FCU-3 AND
 SHOW THAT THE TERMINATION LOCATION COMPLIES WITH FMC
 401.4
  
 5) SHEET M-300: PROVIDE OUTDOOR AIR CALCULATIONS BASED
 ON THE OCCUPANT DENSITY OF TABLE 403.3.1.1. FMC
 403.3.1.1
  
 6) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 BASED ON THE OCCUPANCY CLASSIFICATION AND OCCUPANT
 DENSITY FOR EACH FCU ACCORDING TO THE NUMBER OF PEOPLE
 FROM FBC TABLE 403.3.1.1
  
 7) SHEET M-200: THE BATH EXHAUST FANS ARE ALL
 EXHAUSTING INTO 1 12 X 10 INCH DUCT. SHOW THIS ENTIRE
 DUCT, LENGTH AND TERMINATION LOCATION. SHOW THAT THIS
 DUCT WILL MAINTAIN THE VELOCITY REQUIRED TO EXHAUST THE
 BATHROOMS. FMC 403.3.2.3
  
 8) SHOW THE REQUIRED DUCT DETECTORS IN THE SUPPLY DUCTS
 OF THE FCU???S. FMC 606.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-05-30 Cont ID  
Sent By ccole Date 2023-05-30 Time 12:01 Rev Time 0.00
Received By ccole Date 2023-05-30 Time 07:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-05-15 Cont ID  
Sent By ccole Date 2023-05-15 Time 11:00 Rev Time 0.00
Received By ccole Date 2023-05-15 Time 08:56 Sent To  
Notes
2023-05-15 11:00:533RD REVIEW FBC-2020 PLUMBING
 PERMIT- 23010061
 5/15/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEW ARE COPIED BELOW. I HAVE PROVIDED
 ADDITIONAL NOTES BELOW EACH COMMENT FOR CLARIFICATION.
 PLEASE CORRECT THE PLANS TO AVOID A PENALTY FEE OF FOUR
 TIMES THE AMOUNT OF THE PERMIT FEE- SEE FL. STATUTE
 553.80. ALSO AS PREVIOUSLY REQUESTED PROVIDE THE
 REQUESTED RESPONSE NARRATIVES FROM THE ARCHITECT AND
 ENGINEER ADDRESSING ALL OF THE COMMENTS.
  
 1) FAILED. P-100: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION- SEC.
 107.2.1 WPB. DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR IS REQUIRED TO BE SUBMITTED PRIOR TO THE
 MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NOTE: THE SEPARATE PERMIT APPLICATION FOR THE GREASE
 INTERCEPTOR WAS NOT SUBMITTED. THE PLUMBING PLANS FOR
 THE RESTAURANT WILL NOT BE APPROVED WITHOUT THE
 APPLICATION.
  
  
 3) FAILED. P-110 & P-200: THE PLAN SHOWS NUMEROUS
 FIXTURES WITH NON-GREASE LADEN WASTEWATER DRAINING INTO
 THE GREASE INTERCEPTOR WHICH IS PROHIBITED PER SEC.
 1003.3.1 FBC P. FIXTURES IN VIOLATION ARE THE HAND SINK
 (P67), THE ICE MAKERS (P52) (P54) THE ICE BINS (P53)
 (P55), AND THE BAR FIXTURES (B3, B6, B7, B9, B12).
  
 NOTE: NO CORRECTIONS TO THE PLANS WERE MADE. PLEASE
 COMPLY WITH THE COMMENT.
  
 5) FAILED. P-210: PLEASE PROVIDE A WATER RISER DRAWING-
 SEC. 107.3.5.1.3 WPB. THE RISER SHALL SHOW THE PIPE
 SIZES (NO SIZES WERE PROVIDED ON THE PLAN), AND
 LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS AND SUPPLY
 LINE BACKFLOW PREVENTERS FOR APPLIANCES SUCH AS
 DISHWASHERS, BEVERAGE AND COFFEE MACHINES, WATER
 FILTERS- SEC. 604.9 & 608.3 FBC P.
  
 NOTE: BACKFLOW PREVENTER LOCATIONS NOT SHOWN ON THE
 RISER DRAWING.
  
 7) FAILED. P-210: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE BATHROOM LAVATORY SINKS- SEC. 419.5
 FBC P.
  
 NOTE: NO RESPONSE TO THE COMMENT WAS PROVIDED, AND
 TEMPERED WATER NOT PROVIDED.
  
 8) FAILED. P-210: IT APPEARS THE LENGTHS OF THE HW
 SUPPLY PIPES TO THE LAVATORIES HAVE EXCEEDED THEIR
 MAXIMUM LENGTHS ALLOWABLE PER TABLE C404.1 FBC EC.
  
 NOTE: BASED ON TABLE C404.1.THE MAXIMUM LENGTHS OF THE
 HW SUPPLY PIPES TO THE LAVATORIES FROM THE HOT WATER
 SOURCE IS 2 FT. IN ORDER TO MEET COMPLIANCE THE
 RECIRCULATION LINE MUST LOOP DOWN TO EACH OF THE
 LAVATORIES AND CONNECT TO THE SUPPLY WITHIN 2 FT. OF
 THE FIXTURE. OTHERWISE, A POINT OF USE WATER HEATER
 SHALL BE PROVIDED AT EACH LAVATORY.
  
 11) FAILED. A-1.3, A-1.4, A-1.5: PLEASE PROVIDE THE
 FOLLOWING FBC ACC COMPLIANCE DETAILS FOR THE CUSTOMER
 AND EMPLOYEE RESTROOMS:
  
 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 THE WATER CLOSETS- SEC. 604.3.
 NOTE: BASED ON THE DIMENSIONS SHOWN ON SHEETS A-1.3 &
 A-1.4 IT APPEARS THE CLEAR FLOOR SPACES FOR THE WATER
 CLOSETS WILL BE OVERLAPPING THE LAVATORIES WHICH IS NOT
 PERMITTED PER SEC. 604.3.2 FBC ACC.
  
 I) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SEC. 606.2.
 NOTE: NO DETAIL PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By ccole Date 2023-04-05 Time 15:24 Rev Time 0.00
Received By ccole Date 2023-04-04 Time 15:34 Sent To  
Notes
2023-04-05 15:28:192ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23010061
 4/5/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE COPIED BELOW. I HAVE PROVIDED ADDITIONAL
 NOTES BELOW EACH COMMENT FOR CLARIFICATION.
  
 1) P-100: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION- SEC.
 107.2.1 WPB. DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR IS REQUIRED TO BE SUBMITTED PRIOR TO THE
 MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NOTE: THE SEPARATE PERMIT APPLICATION FOR THE GREASE
 INTERCEPTOR WAS NOT SUBMITTED. THE PLUMBING PLANS FOR
 THE RESTAURANT WILL NOT BE APPROVED WITHOUT THE
 APPLICATION.
  
 2) SHEET LS-1 OR P-100: PROVIDE PLUMBING FIXTURES
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES FOR THE OCCUPANCY.
  
 NOTE: RESPONSE NOT PROVIDED. IT APPEARS THE REQUIRED
 NUMBER OF WATER CLOSETS AND LAVATORIES HAVE BEEN
 PROVIDED HOWEVER DRINKING FOUNTAINS ARE REQUIRED UNLESS
 WATER WILL BE SERVED FREE OF CHARGE IN ACCORDANCE WITH
 SEC. 410.4.
  
 3) P-110 & P-200: THE PLAN SHOWS NUMEROUS FIXTURES WITH
 NON-GREASE LADEN WASTEWATER DRAINING INTO THE GREASE
 INTERCEPTOR WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC
 P. FIXTURES IN VIOLATION ARE THE HAND SINK (P67), THE
 ICE MAKERS (P52) (P54) THE ICE BINS (P53) (P55), AND
 THE BAR FIXTURES (B3, B6, B7, B9, B12).
  
 NOTE: NO CORRECTIONS TO THE PLANS WERE MADE. PLEASE
 COMPLY WITH THE COMMENT.
  
 5) P-210: PLEASE PROVIDE A WATER RISER DRAWING- SEC.
 107.3.5.1.3 WPB. THE RISER SHALL SHOW THE PIPE SIZES
 (NO SIZES WERE PROVIDED ON THE PLAN), AND LOCATIONS OF
 REQUIRED WATER HAMMER ARRESTORS AND SUPPLY LINE
 BACKFLOW PREVENTERS FOR APPLIANCES SUCH AS DISHWASHERS,
 BEVERAGE AND COFFEE MACHINES, WATER FILTERS- SEC. 604.9
 & 608.3 FBC P.
  
 NOTE: BACKFLOW PREVENTER LOCATIONS NOT SHOWN ON THE
 RISER DRAWING.
  
 7) P-210: INDICATE HOW TEMPERED WATER WILL BE DELIVERED
 FROM THE BATHROOM LAVATORY SINKS- SEC. 419.5 FBC P.
  
 NOTE: NO RESPONSE TO THE COMMENT WAS PROVIDED, AND
 TEMPERED WATER NOT PROVIDED.
  
 8) P-210: IT APPEARS THE LENGTHS OF THE HW SUPPLY PIPES
 TO THE LAVATORIES HAVE EXCEEDED THEIR MAXIMUM LENGTHS
 ALLOWABLE PER TABLE C404.1 FBC EC.
  
 NOTE: BASED ON TABLE C404.1.THE MAXIMUM LENGTHS OF THE
 HW SUPPLY PIPES TO THE LAVATORIES FROM THE HOT WATER
 SOURCE IS 2 FT. IN ORDER TO MEET COMPLIANCE THE
 RECIRCULATION LINE MUST LOOP DOWN TO EACH OF THE
 LAVATORIES AND CONNECT TO THE SUPPLY WITHIN 2 FT. OF
 THE FIXTURE. OTHERWISE, A POINT OF USE WATER HEATER
 SHALL BE PROVIDED AT EACH LAVATORY.
  
 11) A-1.3, A-1.4, A-1.5: PLEASE PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCE DETAILS FOR THE CUSTOMER AND
 EMPLOYEE RESTROOMS:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 NOTE: BASED ON THE DIMENSIONS SHOWN ON SHEETS A-1.3 &
 A-1.4 IT APPEARS THE CLEAR FLOOR SPACES FOR THE WATER
 CLOSETS WILL BE OVERLAPPING THE LAVATORIES WHICH IS NOT
 PERMITTED PER SEC. 604.3.2 FBC ACC.
  
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
 NOTE: NO DETAIL PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By ccole Date 2023-01-06 Time 12:16 Rev Time 0.00
Received By ccole Date 2023-01-06 Time 08:50 Sent To  
Notes
2023-01-06 12:21:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23010061
 1/6/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-100: PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR INSTALLATION- SEC.
 107.2.1 WPB. DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR IS REQUIRED TO BE SUBMITTED PRIOR TO THE
 MAIN PLUMBING PLAN APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEET LS-1 OR P-100: PROVIDE PLUMBING FIXTURES
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES FOR THE OCCUPANCY.
  
 3) P-110 & P-200: THE PLAN SHOWS NUMEROUS FIXTURES WITH
 NON-GREASE LADEN WASTEWATER DRAINING INTO THE GREASE
 INTERCEPTOR WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC
 P. FIXTURES IN VIOLATION ARE THE HAND SINK (P67), THE
 ICE MAKERS (P52) (P54) THE ICE BINS (P53) (P55), AND
 THE BAR FIXTURES (B3, B6, B7, B9, B12).
  
 4) P-110 & P-200: PLEASE ADD THE FLOOR DRAINS TO THE
 SCHEDULE AND INDICATE HOW TRAP SEAL PROTECTION WILL BE
 PROVIDED- SEC. 1002.4.1.1 FBC P.
  
 5) P-210: PLEASE PROVIDE A WATER RISER DRAWING- SEC.
 107.3.5.1.3 WPB. THE RISER SHALL SHOW THE PIPE SIZES
 (NO SIZES WERE PROVIDED ON THE PLAN), AND LOCATIONS OF
 REQUIRED WATER HAMMER ARRESTORS AND SUPPLY LINE
 BACKFLOW PREVENTERS FOR APPLIANCES SUCH AS DISHWASHERS,
 BEVERAGE AND COFFEE MACHINES, WATER FILTERS- SEC. 604.9
 & 608.3 FBC P.
  
 6) P-200: PROVIDE PIPE SIZES (DIAMETERS) ON THE PLAN OR
 THE NEW RISER- SEC. 604.3 FBC P.
  
 7) P-210: INDICATE HOW TEMPERED WATER WILL BE DELIVERED
 FROM THE BATHROOM LAVATORY SINKS- SEC. 419.5 FBC P.
  
 8) P-210: IT APPEARS THE LENGTHS OF THE HW SUPPLY PIPES
 TO THE LAVATORIES HAVE EXCEEDED THEIR MAXIMUM LENGTHS
 ALLOWABLE PER TABLE C404.1 FBC EC.
  
 9) P-400: PLEASE CORRECT THE NOTE INCLUDING RELIEF
 VALVE DISCHARGE PIPE TO OUTSIDE OF THE BUILDING. BASED
 ON THE WH LOCATION ON THE PLAN IT WOULD NOT BE
 POSSIBLE- SEC. 504.6 FBC P.
  
 10) P-200 & P-500: GREASE INTERCEPTOR- PROVIDE THE
 FOLLOWING DETAILS AND NOTES PER SEC.1003.3.5 FBC P.
 PLEASE NOTE SHEET P-510 WHICH IS REFERENCED ON THE
 SAINTARY ISOMETRIC BY THE GREASE INTERCEPTOR WAS NOT
 UPLOADED FOR REVIEW.
 A) PROVIDE SIZING CALCULATIONS.
 B) PROIVDE AN ENLARGED PIPING INSTALLATION DETAIL- SEC.
 1003.3.5 FBC P. TYPICAL MANUFACTURER'S GUIDELINES
 REQUIRE CLEANOUTS ON BOTH THE INLET AND OUTLET PIPES.
 THE WPB UTILITIES DEPARTMENT REQUIRES A CLEANOUT ON THE
 OIUTLET PIPE FOR SAMPLING.
  
 11) A-1.3, A-1.4, A-1.5: PLEASE PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCE DETAILS FOR THE CUSTOMER AND
 EMPLOYEE RESTROOMS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3. PLEASE INCLUDE
 THE EMPLOYEE RESTROOM.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 E) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 H) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2023-01-06 Cont ID  
Sent By ccole Date 2023-01-06 Time 12:32 Rev Time 0.00
Received By ccole Date 2023-01-06 Time 12:32 Sent To  
Notes
2023-01-06 12:34:24A SEPARATE PRIMARY PERMIT IS REQUIRED FOR INSTALLATION
 OF THE GREASE INTERCEPTOR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By pvalenti Date 2023-05-31 Time 16:20 Rev Time 0.00
Received By pvalenti Date 2023-05-31 Time 16:12 Sent To  
Notes
2023-05-30 08:20:13PLUMBING/GAS SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-16 Cont ID  
Sent By jleahy Date 2023-05-16 Time 16:48 Rev Time 0.00
Received By jleahy Date 2023-05-16 Time 16:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-10 Cont ID  
Sent By mpeterso Date 2023-04-10 Time 11:11 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
2023-04-07 09:48:32MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-04-04 15:47:59PLUMBING SIGNATURES PASSED.
2023-04-04 10:36:31ARCHITECTURAL & STRUCTURAL SHEETS DIGITALLY SIGNED &
 SEALED. JW 4/4/23.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-10 Cont ID  
Sent By mpeterso Date 2023-01-10 Time 11:39 Rev Time 0.00
Received By mpeterso Date 2023-01-10 Time 11:39 Sent To  
Notes
2023-01-10 11:40:19ALL PLANS PASSED SIGNATURE REVIEW
2023-01-06 13:15:43MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2023-05-15 Cont ID  
Sent By eschneid Date 2023-05-15 Time 12:17 Rev Time 0.25
Received By eschneid Date 2023-05-15 Time 12:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-05-08 Cont ID  
Sent By eschneid Date 2023-05-08 Time 16:20 Rev Time 0.75
Received By eschneid Date 2023-05-08 Time 15:20 Sent To  
Notes
2023-05-08 16:23:17FAILED
  
 1) UPDATED COMMENT - THE RESPONSE LETTER STATES THAT
 THE EXISTING SIGNAGE J-BOX IS ON THE FACADE OF THE
 BUILDING. SHEET A-4 DOES NOT SHOW IT ON THE FACADE OF
 THE BUILDING, BUT AT THE LEASE LINE, WHICH IS UNDER THE
 ARCADE. THE ONLY SIGN PERMITTED AT THIS LOCATION IS A
 BLADE SIGN. ALL OTHER SIGNS MUST BE MOUNTED ON THE
 OUTSIDE OF THE ARCADE. THIS PERMIT NEEDS TO CLEARLY
 INDICATE THAT THE REPLACEMENT J-BOX IS NOT VISIBLE TO
 THE PUBLIC. THIS IS REQUIRED SO THAT THE SIGN
 CONTRACTOR CAN PULL POWER FROM THE CONCEALED J-BOX.
 **** PROVIDE DETAILS (OR A PHOTO) TO VERIFY THAT THIS
 J-BOX IS NOT VISIBLE TO THE PUBLIC (I.E. IN THE
 CEILING). IF IT IS VISIBLE IT MUST BE RELOCATED TO A
 LOCATION THAT IS NOT VISIBLE.
  
 2) UPDATED COMMENT - PROVIDE VERIFICATION THAT THE NEW
 ELEVATION ON THE ARCADE PROVIDES AT LEAST 50%
 TRANSPARENCY. **** THANK YOU FOR STATING THE
 TRANSPARENCY PERCENTAGES IN THE RESPONSE COMMENTS;
 HOWEVER, THE CALCULATIONS MUST BE PROVIDED ON THE
 PLANS. ONLY THE PLAZA ELEVATION IS REQUIRED (ELEVATION
 100).
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-07 Cont ID  
Sent By eschneid Date 2023-03-07 Time 18:14 Rev Time 1.00
Received By eschneid Date 2023-03-07 Time 17:05 Sent To  
Notes
2023-03-07 17:57:18FAILED
  
 1) SHEETS A-4 AND E-300 SHOW AN EXISTING SIGNAGE J-BOX
 THAT IS UNDER THE ARCADE. PROVIDE DETAILS (OR A PHOTO)
 TO VERIFY THAT THIS J-BOX IS NOT VISIBLE TO THE PUBLIC
 (I.E. IN THE CEILING). IF IT IS VISIBLE IT MUST BE
 RELOCATED TO A LOCATION THAT IS NOT VISIBLE.
  
 2) SHEETS A-4 AND E-300 CALL OUT A J-BOX FOR A CEILING
 MOUNTED IMAGE PROJECTOR. THE ROSEMARY SQUARE SIGN PLAN
 DOES NOT PERMIT ANY TYPE OF PROJECTED SIGNAGE OR IMAGES
 ON THE EXTERIOR OF BUILDINGS. THE ONLY PROJECTIONS ARE
 PERMITTED ON THE INTERIOR OF THE SPACE. SEE COMMENT #1
 REGARDING THE VISIBILITY OF THE J-BOX BY THE PUBLIC
 BEING PROHIBITED AND PROVIDING VERIFICATION.
  
 3) SHEET E-300 SHOWS OTHER EXTERIOR J-BOXES INCLUDING
 IN THE CANOPY AND AT THE ENTRANCE TO THE WALKWAY TO THE
 SIDE OF THE TENANT SPACE. YOU MUST PROVIDE VERIFICATION
 THAT NONE OF THESE J-BOXES ARE VISIBLE TO THE PUBLIC.
  
 4) THE LIGHT FIXTURE SCHEDULE CALLS OUT DECORATIVE
 STRING LIGHTS, WHICH ARE NOT PERMITTED IN THE CITY.
  
 5) PROVIDE VERIFICATION THAT THE NEW ELEVATION ON THE
 ARCADE PROVIDES AT LEAST 50% TRANSPARENCY.
  
 6) THE CITYPLACE DRI REQUIRES THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT BE SCREENED FROM PUBLIC VIEW.
 PROVIDE DETAILS ON HOW THE FULL HEIGHT OF THE NEW
 ROOFTOP MECHANICAL EQUIPMENT WILL COMPLY WITH THIS
 REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446