Plan Review Details - Permit 23010049
Plan Review Stops For Permit 23010049
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-09 Cont ID  
Sent By cwalker Date 2023-01-09 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-01-09 10:24:11FIRE PROVISO COMMENTS:
  
 (1) A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR EACH
 EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION
 SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE
 EXTINGUISHER.
  
 (2) UPON ACTIVATION OF AN AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM, AN AUDIBLE ALARM OR VISUAL INDICATOR SHALL BE
 PROVIDED TO SHOW THE SYSTEM HAS ACTIVATED.
  
  
 (3) AT LEAST ONE MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 10 FT. AND A MAXIMUM OF 20 FT.
 FROM THE PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH
 OF EGRESS.
  
 (4) INSTRUCTIONS FOR MANUALLY OPERATING THE FIRE
 EXTINGUISHING SYSTEM SHALL BE POSTED CONSPICUOUSLY IN
 THE KITCHEN AND SHALL BE REVIEWED WITH EMPLOYEES BY THE
 MANAGEMENT.
  
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 09:18 Rev Time 0.00
Received By medwards Date 2023-01-05 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 09:18 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 09:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 09:18 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 09:18 Sent To  
Notes
***NONE***