Plan Review Details - Permit 23010039
Plan Review Stops For Permit 23010039
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2023-05-02 Cont ID  
Sent By cpuell Date 2023-05-02 Time 12:58 Rev Time 0.00
Received By cpuell Date 2023-05-02 Time 12:58 Sent To  
Notes
2023-05-02 12:59:23APPLICANT VERIFIED THAT THE WORK WAS ON 504 37TH ST AND
 UPDATED DOCUMENTS.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2023-04-18 Cont ID  
Sent By cpuell Date 2023-04-18 Time 15:10 Rev Time 0.00
Received By cpuell Date 2023-04-18 Time 15:10 Sent To  
Notes
2023-04-18 15:11:19PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-02-04 Cont ID  
Sent By cpuell Date 2023-02-04 Time 06:53 Rev Time 0.00
Received By cpuell Date 2023-02-04 Time 06:53 Sent To  
Notes
2023-02-04 06:53:28PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-01-13 Cont ID  
Sent By cpuell Date 2023-01-13 Time 10:47 Rev Time 0.00
Received By cpuell Date 2023-01-13 Time 10:47 Sent To  
Notes
2023-01-13 10:48:12INCORRECT ADDRESS THE SOUTH BUILLDING ON THIS PARCEL
 HAS THE ADDRESS OF 504 37TH ST, PLEASE UPDATE TO
 REFLECT THE CORRECT ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-26 Cont ID  
Sent By cthroop Date 2023-06-26 Time 17:13 Rev Time 0.00
Received By cthroop Date 2023-06-26 Time 17:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-11 Cont ID  
Sent By cthroop Date 2023-04-11 Time 13:11 Rev Time 0.00
Received By cthroop Date 2023-04-11 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-23 Cont ID  
Sent By cthroop Date 2023-02-23 Time 09:49 Rev Time 0.00
Received By cthroop Date 2023-02-23 Time 08:20 Sent To  
Notes
2023-02-23 09:50:432ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1. CORRECTED
  
 2. PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 WINDOWS AND EXTERIOR DOORS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPEC. SHEET OF A FLUID APPLIED MEMBRANE.
 R703.4
 APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED
 MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING
 SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTRUCTIONS.
  
 4. PROVIDE A REPAIR DETAIL FOR DAMAGED RAFTERS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-27 Cont ID  
Sent By cthroop Date 2023-01-27 Time 12:35 Rev Time 0.00
Received By cthroop Date 2023-01-27 Time 12:15 Sent To  
Notes
2023-01-27 12:53:141ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. THE INCORRECT ADDRESS IS ON THE PLANS. THE CORRECT
 ADDRESS FOR THIS STRUCTURE IS 504 37TH ST.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 2. PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 WINDOWS AND EXTERIOR DOORS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPEC. SHEET OF A FLUID APPLIED MEMBRANE.
 R703.4
 APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED
 MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING
 SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTRUCTIONS.
  
 4. PROVIDE A REPAIR DETAIL FOR DAMAGED RAFTERS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-06-13 Cont ID  
Sent By rperdomo Date 2023-06-13 Time 16:11 Rev Time 0.00
Received By rperdomo Date 2023-06-13 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-23 Cont ID  
Sent By rperdomo Date 2023-05-23 Time 15:50 Rev Time 0.00
Received By rperdomo Date 2023-05-23 Time 15:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-05-08 Cont ID  
Sent By rperdomo Date 2023-05-08 Time 15:36 Rev Time 0.00
Received By rperdomo Date 2023-05-08 Time 15:22 Sent To  
Notes
2023-05-08 15:37:47FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 NOTES:
  
 1. ELECTRICAL DRAWINGS ARE ON PAGE 5.
  
 2. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED, WITHIN
 SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-12 Cont ID  
Sent By rperdomo Date 2023-01-12 Time 12:56 Rev Time 0.00
Received By rperdomo Date 2023-01-12 Time 12:03 Sent To  
Notes
2023-01-12 14:43:06FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 NOTES:
  
 1. ELECTRICAL DRAWINGS ARE ON PAGE 5.
  
 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 3. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER
 NEC 440.14 OR IRC E4101.5
 DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN
 SIGHT FROM AND READILY ACCESSIBLE??? FROM THE
 AIR-CONDITIONING EQUIPMENT.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-06-27 Cont ID  
Sent By fmittner Date 2023-06-27 Time 08:54 Rev Time 0.00
Received By fmittner Date 2023-06-27 Time 08:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-04-24 Cont ID  
Sent By amhamilt Date 2023-04-24 Time 14:53 Rev Time 0.00
Received By amhamilt Date 2023-04-24 Time 14:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By amhamilt Date 2023-01-30 Time 11:29 Rev Time 0.00
Received By amhamilt Date 2023-01-30 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-06-27 Cont ID  
Sent By cthroop Date 2023-06-27 Time 09:02 Rev Time 0.00
Received By cthroop Date 2023-06-09 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-30 Cont ID  
Sent By hmoser Date 2023-05-30 Time 16:48 Rev Time 0.00
Received By hmoser Date 2023-05-16 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 15:26 Rev Time 0.00
Received By jgomez Date 2023-04-27 Time 15:09 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-24 Cont ID  
Sent By cpuell Date 2023-04-24 Time 15:06 Rev Time 0.00
Received By cpuell Date 2023-04-03 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-23 Cont ID  
Sent By cthroop Date 2023-02-23 Time 09:50 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-31 Cont ID  
Sent By aoliver Date 2023-01-31 Time 09:46 Rev Time 0.00
Received By aoliver Date 2023-01-05 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2023-06-21 Cont ID  
Sent By cmontell Date 2023-06-21 Time 13:07 Rev Time 0.00
Received By cmontell Date 2023-06-21 Time 12:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2023-05-30 Cont ID  
Sent By hmoser Date 2023-05-30 Time 16:31 Rev Time 0.00
Received By hmoser Date 2023-05-30 Time 16:31 Sent To  
Notes
2023-05-30 16:40:00PLAN DENIED
 1) REFER TO SECTION R302.5.2 DUCT PENETRATION
 NO OPENING INTO THE THE GARAGE. 2020 FBC RESIDENTIAL.
 2) REFER TO SECTION M1602.3 BALANCED RETURN AIR.
 2020 FBC RESIDENTIAL.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 14:23 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 14:23 Sent To  
Notes
2023-05-02 14:24:034TH REVIEW FMC
 PERMIT: 23010039
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SCOPE OF WORK ON THE MECHANICAL DRAWING
 INDICATES THERE TO BE ENERGY CALCS AND LOAD SIZING
 CALCS FOR THE MECHANICAL, THESE WERE NOT IN THIS
 SUBMITTAL. PLEASE SUBMIT THESE IN THE NEXT REVIEW
 CYCLE.
  
 2) LABEL EACH ROOM OF THE HOME ON THE MECHANICAL
 DRAWING. IT IS UNCLEAR TO THIS REVIEWER IF THE GARAGE
 HAS BEEN CONVERTED INTO CONDITIONED SPACE. IF IT IS
 STILL A GARAGE REMOVE THE SUPPLY AIR FROM THE GARAGE AS
 THE MECHANICAL SYSTEM CANNOT SUPPLY AIR TO THE GARAGE.
 FRC M1601.6
  
 3) PROVIDE A RETURN AIR PATH FROM THE BEDROOM BACK TO
 THE AHU WHEN THE BEDROOM DOORS ARE CLOSED. FRC M1602.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-04-06 Cont ID  
Sent By medwards Date 2023-04-06 Time 13:43 Rev Time 0.00
Received By medwards Date 2023-04-06 Time 13:43 Sent To  
Notes
2023-04-06 13:44:57PLEASE RESPOND TO PREVIOUS MECHANICAL REVIEW CYCLE
 COMMENTS BELOW:
  
 PLEASE ADDRESS 1ST CYCLE REVIEW COMENTS BELOW:
  
 1ST REVIEW FMC
 PERMIT: 23010039
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS A GARAGE BEING CONVERTED TO LIVING SPACE? IF
 SO PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL
 EQUIPMENT SIZING CALCULATIONS.
  
 2) THE APPLICATION SUBMITTED INDICATES THE SCOPE OF
 WORK IS TO REPLACE ROTTED STUCCO AND WOOD RAFTERS.
 SHEET 1: IN THE SCOPE OF WORK UNDER MECHANICAL THE WORD
 NONE IS THERE INDICATING NO MECHANICAL WORK FOR THIS
 PROJECT. THE SAME SHEET SHOWS A CONDENSER TO THE RIGHT
 OF THE GARAGE. SHEET 2 SHOWS AN AHU TO BE HUNG FROM THE
 TRUSSES IN THE GARAGE. THE KITCHEN SHOWS A HOOD ABOVE
 THE RANGE. SHEET S-1 IS LABELED MECHANICAL PLAN BUT
 THERE IS NO MECHANICAL ON THIS STRUCTURAL PAGE. PROVIDE
 A COMPLETE SCOPE OF WORK FOR THE MECHANICAL SYSTEM
 INCLUDING DRAWINGS FOR THIS PROJECT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-02-02 Cont ID  
Sent By medwards Date 2023-02-02 Time 10:56 Rev Time 0.00
Received By medwards Date 2023-02-02 Time 10:56 Sent To  
Notes
2023-02-02 10:57:17PLEASE ADDRESS 1ST CYCLE REVIEW COMENTS BELOW:
  
 1ST REVIEW FMC
 PERMIT: 23010039
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS A GARAGE BEING CONVERTED TO LIVING SPACE? IF
 SO PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL
 EQUIPMENT SIZING CALCULATIONS.
  
 2) THE APPLICATION SUBMITTED INDICATES THE SCOPE OF
 WORK IS TO REPLACE ROTTED STUCCO AND WOOD RAFTERS.
 SHEET 1: IN THE SCOPE OF WORK UNDER MECHANICAL THE WORD
 NONE IS THERE INDICATING NO MECHANICAL WORK FOR THIS
 PROJECT. THE SAME SHEET SHOWS A CONDENSER TO THE RIGHT
 OF THE GARAGE. SHEET 2 SHOWS AN AHU TO BE HUNG FROM THE
 TRUSSES IN THE GARAGE. THE KITCHEN SHOWS A HOOD ABOVE
 THE RANGE. SHEET S-1 IS LABELED MECHANICAL PLAN BUT
 THERE IS NO MECHANICAL ON THIS STRUCTURAL PAGE. PROVIDE
 A COMPLETE SCOPE OF WORK FOR THE MECHANICAL SYSTEM
 INCLUDING DRAWINGS FOR THIS PROJECT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By medwards Date 2023-01-06 Time 14:21 Rev Time 0.00
Received By medwards Date 2023-01-06 Time 14:21 Sent To  
Notes
2023-01-06 14:21:371ST REVIEW FMC
 PERMIT: 23010039
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS A GARAGE BEING CONVERTED TO LIVING SPACE? IF
 SO PROVIDE THE ENERGY CALCULATIONS AND MECHANICAL
 EQUIPMENT SIZING CALCULATIONS.
  
 2) THE APPLICATION SUBMITTED INDICATES THE SCOPE OF
 WORK IS TO REPLACE ROTTED STUCCO AND WOOD RAFTERS.
 SHEET 1: IN THE SCOPE OF WORK UNDER MECHANICAL THE WORD
 NONE IS THERE INDICATING NO MECHANICAL WORK FOR THIS
 PROJECT. THE SAME SHEET SHOWS A CONDENSER TO THE RIGHT
 OF THE GARAGE. SHEET 2 SHOWS AN AHU TO BE HUNG FROM THE
 TRUSSES IN THE GARAGE. THE KITCHEN SHOWS A HOOD ABOVE
 THE RANGE. SHEET S-1 IS LABELED MECHANICAL PLAN BUT
 THERE IS NO MECHANICAL ON THIS STRUCTURAL PAGE. PROVIDE
 A COMPLETE SCOPE OF WORK FOR THE MECHANICAL SYSTEM
 INCLUDING DRAWINGS FOR THIS PROJECT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-06-12 Cont ID  
Sent By ccole Date 2023-06-12 Time 12:13 Rev Time 0.00
Received By ccole Date 2023-06-12 Time 12:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-02-02 Cont ID  
Sent By rwbrown Date 2023-02-02 Time 08:23 Rev Time 0.00
Received By rwbrown Date 2023-02-02 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-06 Cont ID  
Sent By rwbrown Date 2023-01-06 Time 12:03 Rev Time 0.00
Received By rwbrown Date 2023-01-06 Time 12:02 Sent To  
Notes
2023-01-06 12:03:541ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - THE PAGE MARKED
 "PLUMBING PLAN" DOES NOT HAVE PLUMBING DETAILS, BUT
 ONLY ELECTRICAL. PLEASE CLARIFY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-06-26 Cont ID  
Sent By cthroop Date 2023-06-26 Time 17:13 Rev Time 0.00
Received By cthroop Date 2023-06-26 Time 17:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-05-30 Cont ID  
Sent By hmoser Date 2023-05-30 Time 16:41 Rev Time 0.00
Received By hmoser Date 2023-05-30 Time 16:41 Sent To  
Notes
2023-05-30 16:47:46ARCHITECT MUST DIDITALLY SIGN EACH DRAWING SUBMITTED
 FS. 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-05-09 Cont ID  
Sent By jgomez Date 2023-05-09 Time 15:26 Rev Time 0.00
Received By jgomez Date 2023-05-09 Time 15:10 Sent To  
Notes
2023-05-09 15:26:31SIGNATURE REVIEW COMMENTS
  
 1- SAME COMMENTS FROM PREVIOUS REVIEW APPLY. ONLY SHEET
 2 AND SHEET 4 WERE SUBMITTED AS HARDCOPIES AND THEY
 HAVE THE ARCHITECT'S ORIGINAL SEAL/SIGNATURE.
 ALL DRAWINGS NEED TO HAVE THE ARCHITECT'S ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHATER 481 F.S. WHEN
 SUBMITING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-31 Cont ID  
Sent By pvalenti Date 2023-03-31 Time 16:04 Rev Time 0.00
Received By pvalenti Date 2023-03-31 Time 16:04 Sent To  
Notes
2023-03-31 16:20:35PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW DENIED:
  
 PLAN SHEETS LABELED IN PROJECT DOX AS 002 SH2 FLOOR
 PLAN AND 017 4 SCHEDULE-FLASHING ARE OK FOR SIGNATURES
 AS THEY WERE SUBMITTED IN PAPER FORM WITH ORIGINAL HAND
 SIGNATURES AND SEALS.
 HOWEVER, THE PLAN SHEETS LABELED IN PROJECT DOX AS 004,
 005, 008, 010, & 015 ARE NOT SIGNED/SEALED PLAN SHEETS.
 THESE PLAN SHEETS NEED TO HAVE DESIGN PROFESSIONAL'S
 VERIFIABLE SIGNATURES AND SEALS.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-02-02 Cont ID  
Sent By medwards Date 2023-02-02 Time 10:59 Rev Time 0.00
Received By medwards Date 2023-02-02 Time 10:59 Sent To  
Notes
2023-02-02 11:01:02ARCHITECT MUST DIGITALLY SIGN EACH DRAWING SUBMITTED,
 NONE ARE DIGITALLY SIGNED. FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-27 Cont ID  
Sent By cthroop Date 2023-01-27 Time 12:34 Rev Time 0.00
Received By cthroop Date 2023-01-27 Time 12:15 Sent To  
Notes
2023-01-27 12:35:171ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By Ahamilto Date 2023-01-30 Time 11:30 Rev Time 0.00
Received By amhamilt Date 2023-01-30 Time 11:30 Sent To  
Notes
2023-01-30 11:31:19GARAGE UNIT APPROVED PER GREEN CARD