Plan Review Details - Permit 22121339
Plan Review Stops For Permit 22121339
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-01-30 Cont ID  
Sent By cpuell Date 2023-01-30 Time 14:09 Rev Time 0.00
Received By cpuell Date 2023-01-30 Time 14:09 Sent To  
Notes
2023-01-30 14:10:07UNITS 1 AND 2 TO BE RETIRED 328 NOTTIGHANM TO REMAIN AS
 THE ONLY ADDRESS ON THE PARCEL, OWNER UNSERSTAND THAT
 THEY WILL LOSE THE SECONDARY UNIT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-01-24 Cont ID  
Sent By cpuell Date 2023-01-24 Time 14:43 Rev Time 0.00
Received By cpuell Date 2023-01-24 Time 14:43 Sent To  
Notes
2023-01-24 15:02:11THE PRIMARY BUILDING USED TO BE A DUPLEX WHICH HAD
 THREE ADDRESSES 328 NOTTINGHAM BLVD 328 NOTTINGHAM BLVD
 1 AND 328 NOTTINGHAM BLVD 2, DUE TO THE PROPOSED PLAN
 LAYOUT, I BELIEVE WE CAN RETIRE UNITS 1 AND UNIT 2 AND
 HAVE A SIGNULAR ADDRESS OF 328 NOTTHINGHAM BLVD PLEASE
 HAVE OWNER CONTACT [email protected] OR CALL
 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-05-18 Cont ID  
Sent By cthroop Date 2023-05-18 Time 10:30 Rev Time 0.00
Received By cthroop Date 2023-05-18 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-27 Cont ID  
Sent By cthroop Date 2023-04-27 Time 14:07 Rev Time 0.00
Received By cthroop Date 2023-04-27 Time 07:26 Sent To  
Notes
2023-04-27 14:13:103RD BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS FOR THE PROPOSED SINGLE HUNG WINDOWS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. SHEET 009 NAMED A2.3 PROPOSED FLOOR PLAN IS PLAN
 PAGE A2.3 PROPOSED ROOF PLAN. PLEASE RE-NAME USING
 PROPER NAMING CONVENTIONS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 3. SHEET 021 NAMED S2 FOUNDATION PLAN IS PLAN PAGE S2
 OF 6 ELEVATIONS. PLEASE RE-NAME USING PROPER NAMING
 CONVENTIONS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-09 Cont ID  
Sent By lbond Date 2023-03-09 Time 15:19 Rev Time 0.00
Received By lbond Date 2023-03-09 Time 15:19 Sent To  
Notes
2023-03-09 15:31:53BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 22121339
  
 REVIEWED: MARCH 9, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 AS PER SECTION 107.2.1
 PROVIDE SUPPORTING DOCUMENT FOR NOA OR FPA APPROVED FOR
 ALL NEW WINDOWS.
 SHEET S2 IS NAMED FOUNDATION AND SHOULD BE RENAME
 PROPERLY-A FOUNDATION PERMIT IS NOT REQUIRED BUT
 CLARIFICATION YES.
 SHEET S2.1 REVISE ROOF LINE AS BUILT AND DEMO TO MATCH
 CURRENT
 SHEET A5.0 ADJUST ROOF LINE AS BUILT WEST IS NOT
 MATCHING EXISTING CONDITIONS
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 14:30 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 13:40 Sent To  
Notes
2023-02-01 14:33:581ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 WINDOWS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. SUBMITTAL SHEET NUMBER 021 LABELED FOUNDATION PLAN
 IS PLAN PAGE S2 ELEVATIONS. PROVIDE A FOUNDATION PLAN.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-04-13 Cont ID  
Sent By mpeterso Date 2023-04-13 Time 13:42 Rev Time 0.00
Received By mpeterso Date 2023-04-13 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-08 Cont ID  
Sent By mpeterso Date 2023-03-08 Time 11:27 Rev Time 0.00
Received By mpeterso Date 2023-03-08 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By mpeterso Date 2023-01-23 Time 10:31 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 09:42 Sent To  
Notes
2023-01-23 10:46:40ELECTRIC REVIEW FAILED
  
 1) ADDITIONAL STRUCTURE DOES NOT COMPLY WITH NEC
 ARTICLE 225 OUTSIDE BRANCH CIRCUITS AND FEEDERS. PLEASE
 CORRECT AS APPLICABLE
  
 BUILDINGS OR OTHER STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S)
 NEC 225.30 NUMBER OF SUPPLIES.
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2023-02-28 Cont ID  
Sent By ccole Date 2023-02-28 Time 08:01 Rev Time 0.00
Received By ccole Date 2023-02-28 Time 07:41 Sent To  
Notes
2023-02-28 08:14:13GAS REMOVED FROM SCOPE. SEPARATE PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By ccole Date 2023-01-19 Time 07:41 Rev Time 0.00
Received By ccole Date 2023-01-18 Time 13:52 Sent To  
Notes
2023-01-19 07:42:271ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22121339
 1/19/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2: PROVIDE MORE INFORMATION ABOUT THE
 BBQ IN THE ACCESSORY STRUCTURE. INDICATE PORTABLE OR
 BUILT-IN GRILL, PORTABLE GAS TANK OR HARD PIPED SERVICE
 CONNECTION. IF THE UNIT IS TO BE HARD PIPED AND
 CONNECTED TO A NEW OR EXISTING NATURAL GAS SERVICE,
 PLEASE PROVIDE A GAS PIPING RISER DRAWING. THE RISER
 SHALL INCLUDE THE FOLLOWING INFORMATION PER SEC.
 107.3.5.3 WPB AND SECS. G2412.3 & G2412.4 FBC RES.
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) PLEASE NOTE A GAS SUB-PERMIT APPLICATION IS REQUIRED
 FOR GAS PIPING WORK- SEC. 105.1 WPB.
  
 3) PLEASE REVIEW THE MANUFACTURER???S SPECIFICATIONS
 FOR THE BBQ AND PLACE NOTES AND DIMENSIONS ON THE PLAN
 INDICATING GRILL CLEARANCES TO COMBUSTIBLE MATERIALS-
 SEC. G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-18 Cont ID  
Sent By cthroop Date 2023-05-18 Time 10:30 Rev Time 0.00
Received By cthroop Date 2023-05-01 Time 12:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-27 Cont ID  
Sent By cthroop Date 2023-04-27 Time 14:13 Rev Time 0.00
Received By cthroop Date 2023-04-12 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-09 Cont ID  
Sent By lbond Date 2023-03-09 Time 15:32 Rev Time 0.00
Received By lbond Date 2023-02-27 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 14:34 Rev Time 0.00
Received By cthroop Date 2023-01-17 Time 09:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By medwards Date 2023-04-17 Time 06:22 Rev Time 0.00
Received By medwards Date 2023-04-17 Time 06:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-18 Cont ID  
Sent By medwards Date 2023-01-18 Time 17:34 Rev Time 0.00
Received By medwards Date 2023-01-18 Time 17:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-13 Cont ID  
Sent By ccole Date 2023-04-13 Time 10:57 Rev Time 0.00
Received By ccole Date 2023-04-13 Time 10:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By ccole Date 2023-02-28 Time 08:02 Rev Time 0.00
Received By ccole Date 2023-02-28 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-18 Cont ID  
Sent By ccole Date 2023-01-18 Time 13:51 Rev Time 0.00
Received By ccole Date 2023-01-18 Time 13:13 Sent To  
Notes
2023-01-18 13:52:011ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22121339
 1/18/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY FORM R405-2020 DOES NOT LIST COMPLIANCE
 DATA FOR THE HOT WATER SYSTEMS- SEC. R403.5.6.2 & TABLE
 C404.2 FBC EC.
  
 2) P-2 & A.2.3: THE CHRONOMITE TANKLESS WATER HEATER IS
 BEING INSTALLED IN THE TRELLISED ACCESSORY STRUCTURE
 WHICH IS NOT PROTECTED FROM RAIN AND STORMWATERS.
 PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS VERIFYING
 THE UNIT CAN BE INSTALLED IN THIS LOCATION- SEC.
 107.2.1 WPB. PLEASE NOTE THE MANUFACTURER MAY REQUIRE
 THE UNIT TO BE INSTALLED IN A WEATHERTIGHT, WATERPROOF
 ENCLOSURE.
  
 3) P-2 & A.2.3: THE PLUMBING FLOOR PLAN INDICATES A
 BATHROOM IN THE TRELLISED ACCESSORY STRUCTURE. THIS
 APPEARS TO BE A PLAN ERROR, PLEASE CORRECT- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 14:28 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 14:22 Sent To  
Notes
2023-02-01 14:29:29PROVISO ON PLAN PAGE A8.1: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-27 Cont ID  
Sent By cthroop Date 2023-04-27 Time 14:07 Rev Time 0.00
Received By cthroop Date 2023-04-27 Time 07:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By ccole Date 2023-02-28 Time 08:02 Rev Time 0.00
Received By ccole Date 2023-02-28 Time 08:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By rwbrown Date 2023-01-30 Time 09:23 Rev Time 0.00
Received By rwbrown Date 2023-01-30 Time 09:23 Sent To  
Notes
2023-01-18 17:35:03MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-04-17 Cont ID  
Sent By vbroglia Date 2023-04-17 Time 16:29 Rev Time 0.00
Received By vbroglia Date 2023-04-17 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-03-06 Cont ID  
Sent By vbroglia Date 2023-03-06 Time 16:01 Rev Time 0.00
Received By vbroglia Date 2023-03-06 Time 16:01 Sent To  
Notes
2023-03-06 16:01:483/6/23 FAILED
  
 SEE PREVIOUS COMMENTS

Review Stop Z ZONING
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By VBroglia Date 2023-01-23 Time 11:37 Rev Time 0.00
Received By vbroglia Date 2023-01-23 Time 11:37 Sent To  
Notes
2023-01-23 11:47:501/23/23 FAILED
  
 1. THE VALUE OF THE CONSTRUCTION ($108,160) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($86,344) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE
 PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR
 ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO
 CONFORMITY
  
 -REASON:
 FOR THE MAJORITY OF PROPERTIES, THE EXISTING LANDSCAPE
 IS NON-CONFORMING. THE MINIMAL CHARGE FOR A PERMIT
 VALUE OF LESS THAN $2500.00 IS $125.00. THIS ALLOWS FOR
 STAFF TO REVIEW THE EXISTING MATERIAL ON SITE TO VERIFY
 THE REQUIREMENTS ARE MET AND ALSO ALLOWS FOR AN
 INSPECTION TO CONFIRM THE SITE IS IN COMPLIANCE AT THE
 CONCLUSION OF THE PROJECT.
  
 NEW SINGLE FAMILY AND ALL OTHER NEW STRUCTURES REQUIRE
 A LANDSCAPE PERMIT BE SUBMITTED OR USE THE CONDITIONAL
 APPROVAL FORM
  
  
 2. SEPARATE PERMIT REQUIRED FOR:
 FENCE/WALL, GENERATOR, MECHANICAL/AC/POOL EQUIPMENT,
 POOLS, DRIVEWAYS, IRRIGATION, LANDSCAPE, OTHER.
  
  
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  