| 2022-12-28 13:59:50 | THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L |
| | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| | COMMENTS: |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES |
| | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET |
| | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| | ENCLOSURE. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| | |
| | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| | BUILDING STRUCTURES. |
| | |
| | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, |
| | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS |
| | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. |
| | |
| | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | PROVIDE NON-COMBUSTIBLE CANOPY MATERIAL. |
| | PER FL STATUTE 633.202 |
| | |
| | A TENT UP TO 900 SQUARE FEET IS EXEMPT FROM THE FLORIDA |
| | FIRE PREVENTION CODE, INCLUDING THE NATIONAL CODES |
| | INCORPORATED BY REFERENCE. |
| | |