Plan Review Details - Permit 22121208
Plan Review Stops For Permit 22121208
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-04-04 Cont ID  
Sent By ccole Date 2023-04-04 Time 09:05 Rev Time 0.00
Received By ccole Date 2023-04-04 Time 08:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-02-16 Cont ID  
Sent By jbrooks Date 2023-02-16 Time 14:19 Rev Time 0.00
Received By jbrooks Date 2023-02-16 Time 14:19 Sent To  
Notes
2023-02-16 14:20:04JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 FBC R 301 FAC9N-3. SUBMITTED
 MIAMI-DADE COUNTY NOA 20-0131.01 COVERS MULTIPLE
 ROOFING SYSTEMS TYPES A(1) THROUGH E(7). SELECT SYSTEM
 TO BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 ENGINEERED SIGNED AND SEALED CALCULATIONS MAY BE
 REQUIRED; DEPENDENT UPON SYSTEM USED. PLEASE NOTE
 ADDRESS IS LOCATED IN AN EXPOSURE C CATEGORY AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-03 Cont ID  
Sent By jbrooks Date 2023-02-03 Time 12:30 Rev Time 0.00
Received By jbrooks Date 2023-02-03 Time 08:08 Sent To  
Notes
2023-02-03 12:31:34JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 20-0902.19 HAS EXPIRED AND IS NO LONGER VALID. PLEASE
 PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOAS FOR THE PROPOSED FLAT ROOFING SYSTEM TO
 BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SECOND
 REQUEST.
 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. SUBMIT
 FASTENER DENSITY CALCULATIONS PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT, OR REGISTERED ROOF CONSULTANT IF
 APPLICABLE. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By jbrooks Date 2023-01-17 Time 13:08 Rev Time 0.00
Received By jbrooks Date 2023-01-17 Time 08:12 Sent To  
Notes
2023-01-17 13:09:40JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 20-0902.19 HAS EXPIRED AND IS NO LONGER VALID. PLEASE
 PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA???S FOR THE PROPOSED FLAT ROOFING SYSTEM
 TO BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. SUBMIT
 FASTENER DENSITY CALCULATIONS PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT, OR REGISTERED ROOF CONSULTANT IF
 APPLICABLE.
 3. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART
 OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS
 BY YOUR BUILDING INSPECTOR.
 4. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF
 DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD
 OF PROVIDING POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-16 Cont ID  
Sent By jbrooks Date 2023-02-16 Time 14:20 Rev Time 0.00
Received By jbrooks Date 2023-02-09 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-03 Cont ID  
Sent By jbrooks Date 2023-02-03 Time 12:31 Rev Time 0.00
Received By jbrooks Date 2023-01-23 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-17 Cont ID  
Sent By jbrooks Date 2023-01-17 Time 13:09 Rev Time 0.00
Received By jbrooks Date 2023-01-13 Time 16:11 Sent To  
Notes
***NONE***