Plan Review Details - Permit 22121107
Plan Review Stops For Permit 22121107
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-02-21 Cont ID  
Sent By jwitmer Date 2023-02-21 Time 10:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 17:25 Rev Time 0.00
Received By jwitmer Date 2023-01-31 Time 16:00 Sent To  
Notes
2023-01-31 17:15:43TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 12:59 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 12:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-21 Cont ID  
Sent By jwitmer Date 2023-02-21 Time 10:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-02-21 10:26:22WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22121107
 ADD: 529 S FLAGLER DR # 31F
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 21ST/ 2023
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SEMI-COMPLIED. SHEET A.08 SHOWS 2 TYPES OF FINISH
 FLOORING STONE TILE AND 3 / 4 INCH ENGINEERED WOOD
 FLOORING. TESTING REPORTS FOR PROFLEX SUPER SIM 90 FOR
 TILE FLOORING BUT NO TESTING REPORTS FOR WOOD
 ENGINEERED FLOORING WERE SUBMITTED.
  
 1ST ROUND COMMENT. SHEET A.08 PROFLEX MSC DOES NOT HAVE
 TESTING FOR A 6-INCH SLAB, NO DROP CEILING. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C)(1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 (TILE & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 3C)(2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 PILL TEST (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 4) SEMI-COMPLIED. SHEET A.04 DOOR D.1 STATES METAL
 FRAME AND DOOR SLAB NO RETURN AIR THROUGH THE WALL
 SHOWN ON SHEET M.01, THE DOOR TO THE UNIT WILL NEED TO
 BE A METAL LOUVER OR THROUGH THE WALL GRILL.
 SHEET A.03 SHOWS AN A/C MECHANICAL/ WATER HEATER
 CLOSET, DOOR IS IDENTIFIED AS ID1. SHEET A.04 THE NEW
 INTERIOR DOOR SCHEDULE IS NOT FILLED OUT AS TO TYPE OF
 DOOR FRAME OR DOOR MATERIAL LOUVER OR SOLID. PLENUMS,
 LOUVERED DOORS AND FRAMES. 602.2 OF THE 2020
 FBC-MECHANICAL CODE. CONSTRUCTION. PLENUM ENCLOSURE
 CONSTRUCTION MATERIALS THAT ARE EXPOSED TO THE AIRFLOW
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 703.5
 FBC-BUILDING CODE, NONCOMPUTABILITY TEST.
  
 5-8) COMPLIED.
  
 9) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 17:14 Rev Time 0.00
Received By jwitmer Date 2023-01-31 Time 16:00 Sent To  
Notes
2023-01-31 16:07:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22121107
 ADD: 529 S FLAGLER DR # 31F
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 31ST/ 2023
 ACTION: DENIED
  
 1) THE TITLE SHEET UNDER THE HEADING CONSTRUCTION TYPE
 LIST THE BUILDING TYPE AS VB. PLEASE NOTE THIS IS
 HIGHRISE CONSTRUCTION, TYPE IA CONSTRUCTION 2020
 FBC-BUILDING TABLE 504.4/ OCCUPANCY R2.
  
 2) SHEET A.03. PLEASE NOTE THAT RECITING CODE SECTIONS
 DOES NOT SATISFY THE CODE REQUIREMENTS. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "CODE SECTIONS SHALL
 NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION".
  
 3) SHEET A.08 PROFLEX MSC DOES NOT HAVE TESTING FOR A
 6-INCH SLAB, NO DROP CEILING. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED
 FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET
 THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS
 FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C)(1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 (TILE & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 3C)(2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST???
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
  
 4) SHEET A.03 SHOWS AN A/C MECHANICAL/ WATER HEATER
 CLOSET, DOOR IS IDENTIFIED AS ID1. SHEET A.04 THE NEW
 INTERIOR DOOR SCHEDULE IS NOT FILLED OUT AS TO TYPE OF
 DOOR FRAME OR DOOR MATERIAL LOUVER OR SOLID. PLENUMS,
 LOUVERED DOORS AND FRAMES. 602.2 OF THE 2020
 FBC-MECHANICAL CODE. CONSTRUCTION. PLENUM ENCLOSURE
 CONSTRUCTION MATERIALS THAT ARE EXPOSED TO THE AIRFLOW
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 703.5
 FBC-BUILDING CODE, NONCOMPUTABILITY TEST.
  
 5) SHEET A.03 STATES ALL EXTERIOR DOORS SWING DOORS,
 SLIDING DOORS AND FIXED PANELS ARE TO BE REPLACED.
 SHEET A.04 NEW EXTERIOR DOOR SCHEDULE IS NOT FILED OUT
 TOTALLY. ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SUBMITTED FLORIDA APPROVAL 31650.1 IDENTIFY GLAZING/
 MULLIONS. PLEASE IDENTIFY IN THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER???S INSTRUCTIONS. FASTENER SIZE
 AND SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 7A) SUBMIT FIXED STOREFRONT GLAZED PANEL PRODUCT
 APPROVAL. COMPONENTS & CLADDING. PLEASE SUBMIT THE
 COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(C) PANEL WALLS: STOREFRONTS,
  
 7B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By mpeterso Date 2023-02-22 Time 11:15 Rev Time 0.00
Received By mpeterso Date 2023-02-22 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By mpeterso Date 2023-01-31 Time 10:52 Rev Time 0.00
Received By mpeterso Date 2023-01-31 Time 08:47 Sent To  
Notes
2023-01-31 11:29:57ELECTRIC REVIEW FAILED
  
 1) PLANS INDICATE ALL INTERIOR PARTITIONS AND CABINETRY
 ARE TO BE REMOVED AND REPLACED IN SAME LOCATION. THIS
 WILL REQUIRE ALL ELECTRICAL LOCATED IN THESE PARTITIONS
 TO BE MODIFIED IN SOME FASHION. PLEASE INDICATE ALL
 RECEPTACLES, LIGHT OUTLETS OR OTHER ELECTRIC ITEMS THAT
 WILL BE REPLACED, REMOVED OR MODIFIED. DETAIL HOW EACH
 DEVICE WILL BE TREATED. FBC 107.2 CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL
  
 2) PLEASE PROVIDE DETAIL ALL KITCHEN SMALL APPLIANCE
 RECEPTACLES AS REQUIRED PER NEC 210.52. A RECEPTACLE
 OUTLET SHALL BE INSTALLED AT EACH WALL COUNTERTOP AND
 WORK SURFACE THAT IS (12 IN.) OR WIDER. RECEPTACLE
 OUTLETS SHALL BE INSTALLED SO THAT NO POINT ALONG THE
 WALL LINE IS MORE THAN (24 IN.) MEASURED HORIZONTALLY
 FROM A RECEPTACLE OUTLET IN THAT SPACE. PENINSULAR
 COUNTERTOP SPACES, AT LEAST ONE RECEPTACLE OUTLET SHALL
 BE INSTALLED AT EACH PENINSULAR COUNTERTOP LONG
 DIMENSION SPACE WITH A LONG DIMENSION OF (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF (12 IN.) OR GREATER. A
 PENINSULAR COUNTERTOP IS MEASURED FROM THE CONNECTED
 PERPENDICULAR WALL
  
 3) PLEASE DETAIL ALL APPLIANCE LOCATIONS, INCLUDE WINE
 REFRIGERATOR, WATER HEATER, AC , DOUBLE OVEN, ETC.. FBC
 107.2
  
 4) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY
 WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC
 FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT
 RECEPTACLE REQUIREMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-02-16 Cont ID  
Sent By pleduc Date 2023-02-16 Time   Rev Time 0.00
Received By pleduc Date 2023-02-16 Time 09:27 Sent To  
Notes
2023-02-16 09:30:34FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-18 Cont ID  
Sent By pleduc Date 2023-01-18 Time   Rev Time 0.00
Received By pleduc Date 2023-01-18 Time 13:00 Sent To  
Notes
2023-01-18 13:14:33FIRE PROVISO:
  
 1) PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 3) SMOKE ALARMS ARE REQUIRED IN ANY NEW ROOMS/BEDROOMS
 AS REQUIRED PER NFPA 101 & 72.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-04-03 Time   Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-22 Cont ID  
Sent By mpeterso Date 2023-02-22 Time 11:17 Rev Time 0.00
Received By mpeterso Date 2023-02-15 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-01-31 Time 17:26 Rev Time 0.00
Received By amcgrego Date 2023-01-17 Time 08:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-01-31 Cont ID  
Sent By jwitmer Date 2023-01-31 Time 17:26 Rev Time 0.00
Received By jwitmer Date 2023-01-31 Time 15:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-02-01 Cont ID  
Sent By medwards Date 2023-01-20 Time 13:12 Rev Time 0.00
Received By medwards Date 2023-01-20 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By ccole Date 2023-01-20 Time 16:17 Rev Time 0.00
Received By ccole Date 2023-01-20 Time 16:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By mpeterso Date 2023-02-22 Time 11:16 Rev Time 0.00
Received By mpeterso Date 2023-02-22 Time 11:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By ccole Date 2023-01-20 Time 16:17 Rev Time 0.00
Received By ccole Date 2023-01-20 Time 16:10 Sent To  
Notes
2023-01-20 13:13:54MECHANICAL DIGITAL SIGNATURE APPROVED ME