| 2023-01-23 12:38:27 | 1ST REVIEW FMC |
| | PERMIT: 22121046 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M302: PLEASE SHOW THAT EACH ROOM OR SPACE |
| | MEETS THE RETURN AIR REQUIREMENTS OF FMC 601.5 NUMBER |
| | 3. EXAMPLE: CONFERENCE ROOM HAS A SUPPLY AIR CFM OF 320 |
| | BUT A RETURN AIR CFM OF 420. |
| | |
| | 2) SHEET M801: BASED ON THE INFORMATION PROVIDED IN |
| | THIS SUBMITTAL AND TABLE 403.3.1.1 THE CONFERENCE ROOM |
| | OUTDOOR AIR SHOULD BE CALCULATED WITH 17 PEOPLE AND NOT |
| | 7, THE RECEPTION AREA OUTDOOR AIR SHOULD BE CALCULATED |
| | WITH 6 PEOPLE AND NOT 3. THIS WILL MAKE A DIFFERENCE IN |
| | YOUR OUTDOOR AIR MINIMUM REQUIREMENTS. FMC 403.3.1.1 |
| | AND TABLE 403.3.1.1 |
| | |
| | 3) BASED ON THE INFORMATION SUBMITTED AND FMC TABLE |
| | 403.3.1.1. THE TOTAL MINIMUM OCCUPANT COUNT FOR THIS |
| | SPACE IS 28. PAGE 1 OF 1 FOR THE SYSTEM CHECKSUMS HAS |
| | LISTED THE DESIGN IS BASED ON 22 PEOPLE. PLEASE BASE |
| | THE DESIGN ON THE MINIMUM COUNT FOR THE DESIGN OF 28. |
| | FMC TABLE 403.3.1.1 |
| | |
| | 4) PROVIDE A SITE MAP SHOWING THE PROPERTY LINES ON THE |
| | SIDE OF THE BUILDING WHERE THE OUTDOOR AIR TERMINATION |
| | LOCATION IS LOCATED. FMC 401.4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |