Plan Review Details - Permit 22121046
Plan Review Stops For Permit 22121046
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By rmcphers Date 2023-01-20 Time 14:10 Rev Time 0.00
Received By rmcphers Date 2023-01-20 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-30 Cont ID  
Sent By mpeterso Date 2023-01-30 Time 10:34 Rev Time 0.00
Received By mpeterso Date 2023-01-30 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By clfranci Date 2023-01-20 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-24 Time 06:26 Rev Time 0.00
Received By medwards Date 2023-02-15 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-30 Cont ID  
Sent By mpeterso Date 2023-01-30 Time 10:35 Rev Time 0.00
Received By mpeterso Date 2023-01-19 Time 12:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-24 Time 06:26 Rev Time 0.00
Received By medwards Date 2023-02-24 Time 06:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By medwards Date 2023-01-23 Time 12:38 Rev Time 0.00
Received By medwards Date 2023-01-23 Time 12:38 Sent To  
Notes
2023-01-23 12:38:271ST REVIEW FMC
 PERMIT: 22121046
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M302: PLEASE SHOW THAT EACH ROOM OR SPACE
 MEETS THE RETURN AIR REQUIREMENTS OF FMC 601.5 NUMBER
 3. EXAMPLE: CONFERENCE ROOM HAS A SUPPLY AIR CFM OF 320
 BUT A RETURN AIR CFM OF 420.
  
 2) SHEET M801: BASED ON THE INFORMATION PROVIDED IN
 THIS SUBMITTAL AND TABLE 403.3.1.1 THE CONFERENCE ROOM
 OUTDOOR AIR SHOULD BE CALCULATED WITH 17 PEOPLE AND NOT
 7, THE RECEPTION AREA OUTDOOR AIR SHOULD BE CALCULATED
 WITH 6 PEOPLE AND NOT 3. THIS WILL MAKE A DIFFERENCE IN
 YOUR OUTDOOR AIR MINIMUM REQUIREMENTS. FMC 403.3.1.1
 AND TABLE 403.3.1.1
  
 3) BASED ON THE INFORMATION SUBMITTED AND FMC TABLE
 403.3.1.1. THE TOTAL MINIMUM OCCUPANT COUNT FOR THIS
 SPACE IS 28. PAGE 1 OF 1 FOR THE SYSTEM CHECKSUMS HAS
 LISTED THE DESIGN IS BASED ON 22 PEOPLE. PLEASE BASE
 THE DESIGN ON THE MINIMUM COUNT FOR THE DESIGN OF 28.
 FMC TABLE 403.3.1.1
  
 4) PROVIDE A SITE MAP SHOWING THE PROPERTY LINES ON THE
 SIDE OF THE BUILDING WHERE THE OUTDOOR AIR TERMINATION
 LOCATION IS LOCATED. FMC 401.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By ccole Date 2023-01-20 Time 12:19 Rev Time 0.00
Received By ccole Date 2023-01-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-24 Time 06:26 Rev Time 0.00
Received By medwards Date 2023-02-24 Time 06:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-20 Cont ID  
Sent By ccole Date 2023-01-20 Time 12:19 Rev Time 0.00
Received By ccole Date 2023-01-20 Time 12:19 Sent To  
Notes
***NONE***