| 2022-12-21 08:37:42 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL2533-R25 HAS BEEN |
| | REVISED TO FL2533-R28. PROVIDE THE FOLLOWING: COVER |
| | PAGE, EVALUATION REPORTS PAGES 1-5 TO INCLUDE |
| | LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. SELECTED SYSTEM NO. W-107 DO NOT MEET |
| | EXPOSURE CATEGORY D ZONE 3 MINIMUM DESIGN PRESSURE |
| | REQUIREMENTS OF -131.42. PROVIDE SYSTEM THAT MEETS OR |
| | EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR EXPOSURE |
| | CATEGORY D/PROVIDE SIGNED AND SEALED ENGINEERED NAILING |
| | CALCULATIONS WITH AN APPROVED SYSTEM. |
| | 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| | MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| | POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |