| 2023-01-11 14:37:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET C 600 - THERE ARE INDICATIONS OF UNDERGROUND |
| | FIRE LINES. |
| | |
| | UNDERGROUND FIRE LINE WORK SAHLL BE SUBMITTED UNDER |
| | SEPARATE PERMITS AND SHOP DRAWINGS IN COMPLIANCE WITH |
| | NFPA 24 AND MANUFACTURE SPECIFICATIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 2) SHEET LS 102 - THERE ARE INDICATIONS OF EXIT SIGNAGE |
| | IN THE MIDDLE OF CORRIDORS/EXIT ACCESS ROUTES/GARAGE |
| | ACCESS ROUTES THAT ARE SIDE MOUNTS ARE ARE NO VISABLE |
| | FROM THE ENDS/CORNERS. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS |
| | |
| | 7.10.1.9 MOUNTING LOCATION. THE BOTTOM OF NEW EGRESS |
| | MARKINGS |
| | SHALL BE LOCATED AT A VERTICAL DISTANCE OF NOT MORE |
| | THAN 6 FT 8 IN. |
| | (2030 MM) ABOVE THE TOP EDGE OF THE EGRESS OPENING |
| | INTENDED FOR DES IGNATION BY THAT MARKING. EGRESS |
| | MARKINGS SHALL BE LOCATED AT A HORI ZONTAL DISTANCE OF |
| | NOT MORE THAN THE REQUIRED WIDTH OF THE EGRESS OPENING, |
| | AS MEASURED FROM THE EDGE OF THE EGRESS OPENING |
| | INTENDED FOR DESIGNA TION BY THAT MARKING TO THE |
| | NEAREST EDGE OF THE MARKING |
| | |
| | 7.10.2 DIRECTIONAL SIGNS. |
| | 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A |
| | DIRECTIONAL INDICATOR |
| | SHOWING THE DIRECTION OF TRAVEL, SHALL BE PLACED IN |
| | EVERY LOCATION WHERE |
| | THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT IS |
| | NOT APPARENT. |
| | |
| | PLEASE REVIEW AND CORRECT AND COORDINATE WITH THE |
| | OFFICE OF THE FIRE MARSHAL VIA EMAIL PDF'S OR ZOOM FOR |
| | REVIEW. |
| | |
| | |
| | |
| | 3) SHEET LS 102 THRU 105 - THERE IS AN INDICATIONS OF A |
| | DOUBLE SWINGDOOR IN THE CENTER CORRIDOR WITH NO EXIT |
| | SIGNAGE OVER THE DOOR FROM EACH DIRECTION. |
| | |
| | PER NFPA 101 CH 7, MEANS OF EGRESS MARKING, AN EXIT |
| | SIGN IS REQUIRED OVER THE DOOR IN THE PATH OF EXIT |
| | TRAVEL. |
| | |
| | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | 7.10 MARKING OF MEANS OF EGRESS |
| | |
| | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| | WITHIN AN EXIT |
| | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| | DIRECTIONAL EXIT SIGNS |
| | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| | OBVIOUS |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 4) SHEET LS 106 - THERE ARE INDICATIONS OF A SPA DECK |
| | HOWEVER, THERE ARE NO INDICATIONS OF EXIT SIGNS ALONG |
| | THE EGRESS TRAVEL PATH AND EXIT LOCATIONS. |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 7.10 MARKING OF MEANS OF EGRESS |
| | |
| | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH |
| | WITHIN AN EXIT |
| | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR |
| | DIRECTIONAL EXIT SIGNS |
| | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT |
| | OBVIOUS |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) SHEET LS 106 - THERE ARE INDICATIONS ARE 2 |
| | HORIZONTAL EXITS WITH LARGE CAPACITIES WITH A SQ FT / 3 |
| | OCC. |
| | |
| | PER NFPA 101 , CH 12 ASSEMBY OCCUPANCIES |
| | |
| | 12.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING |
| | WITH 7.2.4 SHALL |
| | BE PERMITTED. |
| | |
| | 7.2.4.1.2* HORIZONTAL EXITS SHALL BE PERMITTED TO BE |
| | SUBSTITUTED FOR OTHER |
| | EXITS PROVIDED THAT BOTH OF THE FOLLOWING ARE MET, |
| | UNLESS OTHERWISE |
| | PERMITTED BY 7.2.4.1.3: |
| | (1) A MINIMUM OF HALF OF THE NUMBER OF EXITS FROM ANY |
| | COMPARTMENT |
| | CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN |
| | HORIZONTAL |
| | EXITS |
| | (2) A MINIMUM OF HALF OF THE EGRESS CAPACITY REQUIRED |
| | FOR ANY COMPARTMENT |
| | CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN |
| | HORIZONTAL EXITS |
| | |
| | BEFORE ANY SPACE CAN BE USED AS AN OCCUPANT |
| | ACCUMULATION AREA ON |
| | EITHER SIDE OF A HORIZONTAL EXIT, IT MUST SATISFY |
| | CERTAIN CRITERIA. SUCH A |
| | SPACE, ALTHOUGH SEPARATED WITH 2-HOUR FIRE BARRIERS |
| | CANNOT BE USED |
| | AS A HORIZONTAL EXIT UNLESS THERE IS AT LEAST ONE |
| | STANDARD TYPE OF EXIT (NOT |
| | AN ADDITIONAL HORIZONTAL EXIT) LEADING FROM THE SPACE, |
| | TO ENSURE OCCUPANTS |
| | ARE NOT TRAPPED WITHIN A FIRE COMPARTMENT WITH NO OTHER |
| | WAY OUT. |
| | ADDITIONALLY, THE COMPARTMENT MUST BE LARGE ENOUGH TO |
| | PROVIDE OCCUPANT |
| | ACCUMULATION SPACE FOR THE OCCU PANTS OF BOTH THE FIRE |
| | COMPARTMENT |
| | CONTAINING THE FIRE AND THE NON-FIRE COMPARTMENT, |
| | ALLOWING 3 SQ FT(0.28 M2 |
| | ) OF FLOOR SPACE PER PERSON. |
| | |
| | THERE APPEARS TO BE A CREATION OF EXIT STAGING TYPE |
| | ROOMS, NOT A SEPARATION OF AN AREA DIVIDED. THERE |
| | REMAINS THE ABILITY TO WALK AROUND THE EXIT STAGING |
| | ROOM DEFEATING THE PURPOSE OF A PROPOSED HORIZONTAL |
| | EXIT. |
| | |
| | THERE DOES NOT APPEAR TO BE SUFFICIENT "FLOOR SPACE", |
| | IN ADDITION TO THE PROPOSED NUMBER OF EXITS AND THEIR |
| | LOCATIONS. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND CALCULATIONS IN |
| | COMPLIANCE WITH THE REQUIREMENTS. |
| | |
| | |
| | 6) SHEET LS 107 - THERE ARE INDICATIONS ARE A |
| | HORIZONTAL EXIT WITH A LARGE CAPACITY WITH A SQ FT / 3 |
| | OCC. |
| | |
| | PER NFPA 101 , CH 12 ASSEMBY OCCUPANCIES |
| | |
| | 12.2.2.5 HORIZONTAL EXITS. HORIZONTAL EXITS COMPLYING |
| | WITH 7.2.4 SHALL |
| | BE PERMITTED. |
| | |
| | 7.2.4.1.2* HORIZONTAL EXITS SHALL BE PERMITTED TO BE |
| | SUBSTITUTED FOR OTHER |
| | EXITS PROVIDED THAT BOTH OF THE FOLLOWING ARE MET, |
| | UNLESS OTHERWISE |
| | PERMITTED BY 7.2.4.1.3: |
| | (1) A MINIMUM OF HALF OF THE NUMBER OF EXITS FROM ANY |
| | COMPARTMENT |
| | CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN |
| | HORIZONTAL |
| | EXITS |
| | (2) A MINIMUM OF HALF OF THE EGRESS CAPACITY REQUIRED |
| | FOR ANY COMPARTMENT |
| | CREATED BY HORIZONTAL EXITS IS PROVIDED BY OTHER THAN |
| | HORIZONTAL EXITS |
| | |
| | BEFORE ANY SPACE CAN BE USED AS AN OCCUPANT |
| | ACCUMULATION AREA ON |
| | EITHER SIDE OF A HORIZONTAL EXIT, IT MUST SATISFY |
| | CERTAIN CRITERIA. SUCH A |
| | SPACE, ALTHOUGH SEPARATED WITH 2-HOUR FIRE BARRIERS |
| | CANNOT BE USED |
| | AS A HORIZONTAL EXIT UNLESS THERE IS AT LEAST ONE |
| | STANDARD TYPE OF EXIT (NOT |
| | AN ADDITIONAL HORIZONTAL EXIT) LEADING FROM THE SPACE, |
| | TO ENSURE OCCUPANTS |
| | ARE NOT TRAPPED WITHIN A FIRE COMPARTMENT WITH NO OTHER |
| | WAY OUT. |
| | ADDITIONALLY, THE COMPARTMENT MUST BE LARGE ENOUGH TO |
| | PROVIDE OCCUPANT |
| | ACCUMULATION SPACE FOR THE OCCU PANTS OF BOTH THE FIRE |
| | COMPARTMENT |
| | CONTAINING THE FIRE AND THE NON-FIRE COMPARTMENT, |
| | ALLOWING 3 SQ FT(0.28 M2 |
| | ) OF FLOOR SPACE PER PERSON. |
| | |
| | THERE APPEARS TO BE A CREATION OF AN EXIT STAGING TYPE |
| | ROOM, NOT A SEPARATION OF AN AREA DIVIDED. THERE |
| | REMAINS THE ABILITY TO WALK AROUND THE EXIT STAGING |
| | ROOM DEFEATING THE PURPOSE OF A PROPOSED HORIZONTAL |
| | EXIT. |
| | |
| | THERE DOES NOT APPEAR TO BE SUFFICIENT "FLOOR SPACE", |
| | IN ADDITION TO THE PROPOSED NUMBER OF EXITS AND THEIR |
| | LOCATIONS. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND CALCULATIONS IN |
| | COMPLIANCE WITH THE REQUIREMENTS. |
| | |
| | |
| | |
| | 7) SHEET LS 108, 109, 110 & 111 - THERE ARE INDICATIONS |
| | ON THE EAST BLDG OF TWO EXIT STAIRWELLS THAT APPEAR TO |
| | BE SEPARATED BY MORE THAN 200' |
| | |
| | NFPA 14 REQUIRES THAT THE DISTANCE OF TRAVEL FROM AN |
| | OUTLET BE NO MORE THAN 130 FEET IN NON-SPRINKLERED |
| | BUILDINGS AND NO MORE THAN 200 FEET IN SPRINKLERED |
| | BUILDINGS. |
| | |
| | 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A |
| | NONSPRINKLERED |
| | FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M) |
| | OF TRAVEL |
| | DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A |
| | REQUIRED |
| | EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR |
| | OR STORY |
| | IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL |
| | DISTANCE FROM A |
| | HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT, |
| | ADDITIONAL |
| | HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED |
| | LOCATIONS, |
| | WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ. |
| | |
| | PLEASE REVIEW, CORRECT OR PROVIDE DISTANCE DIMENSIONS |
| | IN COMPLIANCE WITHE THE REQUIREMENT. |
| | |
| | |
| | |
| | 8) SHEET FP 601 - THERE APPEARS TO BE AN INDICATION OF |
| | AN ELECTRIC FIRE PUMP. |
| | |
| | NFPA 20 |
| | |
| | 9.3 ALTERNATE POWER. |
| | 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT |
| | LEAST |
| | ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE |
| | THE |
| | HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY |
| | OF THE |
| | FIRE DEPARTMENT APPARATUS |
| | 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT |
| | DESCRIBED IN |
| | 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE |
| | PROVIDED |
| | WHERE THE NORMAL SOURCE IS NOT RELIABLE. |
| | |
| | 9.3.4 WHERE PROVIDED, THE ALTERNATE SOURCE OF POWER |
| | SHALL BE |
| | SUPPLIED FROM ONE OF THE FOLLOWING SOURCES: |
| | (1) A GENERATOR INSTALLED IN ACCORDANCE WITH SECTION |
| | 9.6 |
| | (2) ONE OF THE SOURCES IDENTIFIED IN 9.2.2(1), |
| | 9.2.2(2), 9.2.2(3), |
| | OR 9.2.2(5) WHERE THE POWER IS PROVIDED INDEPENDENT OF |
| | THE |
| | NORMAL SOURCE OF POWER |
| | |
| | NFPA 70 |
| | |
| | ARTICLE 695 |
| | FIRE PUMPS |
| | |
| | (D) ON-SITE STANDBY GENERATOR AS ALTERNATE SOURCE. AN |
| | ON-SITE STANDBY GENERATOR(S) USED AS AN ALTERNATE |
| | SOURCE OF |
| | POWER SHALL COMPLY WITH (D)(1) THROUGH (D)(3). |
| | [20:9.6.2.1] |
| | (1) CAPACITY. THE GENERATOR SHALL HAVE SUFFICIENT |
| | CAPACITY |
| | TO ALLOW NORMAL STARTING AND RUNNING OF THE MOTOR(S) |
| | DRIV ING THE FIRE PUMP(S) WHILE SUPPLYING ALL OTHER |
| | SIMULTA NEOUSLY OPERATED LOAD(S). [20:9.6.1.1] |
| | AUTOMATIC SHEDDING OF ONE OR MORE OPTIONAL STANDBY |
| | LOADS IN ORDER TO COMPLY WITH THIS CAPACITY REQUIREMENT |
| | SHALL BE PERMITTED. |
| | |
| | FOR CLARIFICATION PURPOSES, PER NFPA 20 & 70 PLEASE |
| | PROVIDE THE SECONDARY POWER SUPPLY FOR THE ELECTRIC |
| | FIRE PUMP AND THE FUEL SOURCE OF THE SECONDARY POWER |
| | SUPPLY. |
| | |
| | |
| | |
| | 9) LIFE SAFETY SHEETS - THERE DOES NOT APPEAR TO BE |
| | DESIGNATED AREAS OF REFUGE AND THE APPLICABLE |
| | INDICATORS/EQUIPMENT. |
| | |
| | PER NFPA 101 CH 30 NEW APARTMENT OCCUPANCIES |
| | |
| | 30.2.2.12 AREAS OF REFUGE. |
| | 30.2.2.12.1 AREAS OF REFUGE COMPLYING WITH 7.2.12 SHALL |
| | BE PERMITTED, |
| | AS MODIFIED BY 30.2.2.12.2. |
| | 30.2.2.12.2* IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPER VISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 30.3.5, THE TWO |
| | ACCESSIBLE ROOMS OR SPACES SEPARATED FROM EACH OTHER BY |
| | SMOKE-RESISTIVE PARTITIONS IN ACCORDANCE WITH THE |
| | DEFINITION OF AREA OF REFUGE IN 3.3.23 |
| | SHALL NOT BE REQUIRED |
| | |
| | NFPA 101 CH 7, MEANS OF EGRESS |
| | |
| | 7.2.12.1 GENERAL. |
| | 7.2.12.1.1 AN AREA OF REFUGE USED AS PART OF A REQUIRED |
| | ACCESSIBLE MEANS |
| | OF EGRESS IN ACCORDANCE WITH 7.5.4; CONSISTING OF A |
| | STORY IN A BUILDING |
| | THAT IS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED |
| | AUTOMATIC SPRIN KLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7; AND HAVING AN ACCESSIBLE |
| | STORY THAT IS ONE OR MORE STORIES ABOVE OR BELOW A |
| | STORY OF EXIT DISCHARGE |
| | SHALL MEET THE FOLLOWING CRITERIA: |
| | (1) EACH ELEVATOR LANDING SHALL BE PROVIDED WITH A |
| | TWO-WAY COMMU NICATION SYSTEM FOR COMMUNICATION BETWEEN |
| | THE ELEVATOR LANDING |
| | AND THE FIRE COMMAND CENTER OR A CENTRAL CONTROL POINT |
| | APPROVED |
| | BY THE AUTHORITY HAVING JURISDICTION. |
| | (2) DIRECTIONS FOR THE USE OF THE TWO-WAY COMMUNICATION |
| | SYSTEM, |
| | INSTRUCTIONS FOR SUMMONING ASSISTANCE VIA THE TWO-WAY |
| | COMMUNI CATION SYSTEM, AND WRITTEN IDENTIFICATION OF |
| | THE LOCATION SHALL BE |
| | POSTED ADJACENT TO THE TWO-WAY COMMUNICATION SYSTEM. |
| | (3) THE TWO-WAY COMMUNICATION SYSTEM SHALL INCLUDE BOTH |
| | AUDIBLE |
| | AND VISIBLE SIGNALS |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS |
| | AND CODE REFERENCES FOR NOT PROVIDING THEM. |
| | |
| | |
| | 10) RENTAL ELEVATOR PRIVATE LOBBY - THERE DOES NOT |
| | APPEAR TO BE EXIT SIGNAGE OVER THE EXIT DOOR OF THE |
| | LOBBY. |
| | |
| | PER NFPA 101 CH 30 & 7 EXIT ACCESS SHALL PROVIDE |
| | MARKINGS OVER EXIT DOORS. |
| | |
| | 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS |
| | REQUIRING MORE |
| | THAN ONE EXIT |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS |
| | AND CODE REFERENCES FOR NOT PROVIDING THEM. |
| | |
| | |
| | 11) EAST FLOOR PLANS - THERE ARE INDICATIONS OF EXIT |
| | TRAVEL DISTANCES OF THE LARGER UNITS THAT APPEAR TO |
| | EXCEED THE MAX TRAVEL DISTANCE. |
| | |
| | THE BLUE LINE INDICATORS SHOW A STARTING POINT IN AN |
| | AREA THAT WOULD BE SHORTER THAN AN AREA ON THE SAME |
| | BALCONY THAT APPEARS TO BE LONGER AND EXCEEDING THE MAX |
| | TRAVEL DISTANCE OF 125' |
| | |
| | PER NFPA 101 CH 30 |
| | |
| | 30.2.6 TRAVEL DISTANCE TO EXITS. TRAVEL DISTANCE SHALL |
| | BE MEASURED IN |
| | ACCORDANCE WITH SECTION 7.6 |
| | |
| | 30.2.6.2 TRAVEL DISTANCE WITHIN A DWELLING UNIT |
| | (APARTMENT) TO A CORRIDOR |
| | DOOR SHALL NOT EXCEED 125 FT (38 M) IN BUILDINGS |
| | PROTECTED THROUGHOUT |
| | BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN |
| | ACCORDANCE WITH 30.3.5 |
| | |
| | 7.6.1* THE TRAVEL DISTANCE TO AN EXIT SHALL BE MEASURED |
| | ON THE FLOOR OR |
| | OTHER WALKING SURFACE AS FOLLOWS: |
| | (1) ALONG THE CENTERLINE OF THE NATURAL PATH OF TRAVEL, |
| | STARTING FROM THE |
| | MOST REMOTE POINT SUBJECT TO OCCUPANCY |
| | (2) CURVING AROUND ANY CORNERS OR OBSTRUCTIONS, WITH A |
| | 12 IN. (305 MM) |
| | CLEARANCE THEREFROM |
| | (3) TERMINATING AT ONE OF THE FOLLOWING: |
| | (A) CENTER OF THE DOORWAY |
| | (B) OTHER POINT AT WHICH THE EXIT BEGINS |
| | (C) SMOKE BARRIER IN AN EXISTING DETENTION AND |
| | CORRECTIONAL OCCU PANCY AS PROVIDED IN CHAPTER 23. |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC DETAILS |
| | AND CODE REFERENCES FOR NOT PROVIDING THEM. |
| | |
| | |
| | 12) SHEET M 101 A, 102 A, 103 A, 104 A, 106 A, 107 A, |
| | 109 A, 110 A B , 111 A B, 112 A B, 113 A B- THERE |
| | APPEARS TO BE INDICATIONS OF VENTILATION SHAFTS |
| | BREACHING FIRE RATED WALLS/CORRIDORS THAT DO NOT |
| | INDICATE FIRE/SMOKE DAMPERS |
| | |
| | (SHEET 105 A INDICIATES A F/SD AT THE CENTER CORRIDOR |
| | UNIT BUT NOT THE OTHER FLOORS NOTED.) |
| | |
| | PER NFPA 101 AND 90 A |
| | |
| | 8.3.5.7 OPENINGS FOR AIR-HANDLING DUCTWORK. OPENINGS IN |
| | FIRE BARRIERS FOR AIR-HANDLING DUCTWORK OR AIR MOVEMENT |
| | SHALL |
| | BE PROTECTED IN ACCORDANCE WITH 9.2.1 |
| | |
| | 8.4.6 AIR-TRANSFER OPENINGS. |
| | 8.4.6.1 GENERAL. THE PROVISIONS OF 8.4.6 SHALL GOVERN |
| | THE MATERIALS |
| | AND METHODS OF CONSTRUCTION USED TO PROTECT AIR |
| | TRANSFER OPENINGS IN SMOKE PARTITIONS. |
| | |
| | 8.5.5 DUCTS AND AIR-TRANSFER OPENINGS. |
| | 8.5.5.1 GENERAL. THE PROVISIONS OF 8.5.5 SHALL GOVERN |
| | THE MA TERIALS AND METHODS OF CONSTRUCTION USED TO |
| | PROTECT DUCTS AND |
| | AIR-TRANSFER OPENINGS IN SMOKE BARRIERS. |
| | |
| | 8.5.5.4 INSTALLATION, TESTING, AND MAINTENANCE. |
| | 8.5.5.4.1 AIR-CONDITIONING, HEATING, VENTILATING |
| | DUCTWORK, |
| | AND RELATED EQUIPMENT, INCLUDING SMOKE DAMPERS AND |
| | COMBI NATION FIRE AND SMOKE DAMPERS, SHALL BE INSTALLED |
| | IN ACCOR DANCE |
| | WITH NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR |
| | CONDITIONING AND VENTILATING SYSTEMS, NFPA 90B, |
| | STANDARD FOR THE |
| | INSTALLATION OF WARM AIR HEATING AND AIR-CONDITIONING |
| | SYSTEMS, NFPA 105, STANDARD FOR SMOKE DOOR ASSEMBLIES |
| | AND OTHER OPENING |
| | PROTECTIVES, OR NFPA 80, STANDARD FOR FIRE DOORS AND |
| | OTHER OPENING PROTECTIVES, AS APPLICABLE |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE CLARIFICATIONS |
| | WITH SPECIFIC JUSTIFICATION INCLUDING CODE REFERENCES. |
| | |
| | |
| | 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |