| Plan Review Stops For Permit 22120859 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-02 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-02 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2023-03-02 10:15:43 | 3RD ELECTRICAL REVIEW FAILED | | | | | | PREVIOUS COMMENTS NOT ADDRESSED AGAIN |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-06 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-06 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2023-02-06 12:22:27 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-01 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-01 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2023-02-01 14:59:05 | ELECTRIC REVIEW FAILED | | | APPLICATION STATES 4 MINI SPLIT SYSTEMS. PLANS DETAIL 2 | | | APARTMENT UNITS WITH COMPLETE ELECTRIC SYSTEM | | | . | | | PLEASE PROVIDE ELECTRICAL FLOOR PLANS WITH ONLY THE | | | ELECTRIC WORK PERFORMED UNDER THIS SUBMITTAL. | | | INDICATE ON PLANS CONDENSING AND ASSOCIATED INDOOR | | | UNITS BY APARTMENT NUMBERS. PROVIDE PLANS FOR ALL 4 | | | APARTMENT UNITS. INCLUDE ALL CONDUIT, CONDUCTOR, | | | OVERCURRENT PROTECTION SIZES AND WIRING METHODS USED. | | | | | | FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-02 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-24 |
Time |
06:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-06 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-02 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-01 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-26 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-27 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-27 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2023-02-27 08:35:53 | THE ENERGY CALCULATIONS ARE MISSING THE DESIGNERS | | | INFORMATION ON PAGE 1. | | | | | | THE DOCUMENTS SUBMITTED WILL NEED THE DIGITAL SIGNATURE | | | OF THE EOR. THERE IS A COPY OF A STAMP AND SIGNATURE ON | | | THE LATEST DRAWINGS BUT WE CANNOT ACCEPT A COPY. | | | PROVIDE THE ORIGINAL DOCUMENT OR THE ORIGINAL DIGITALLY | | | SIGNED DOCUMENTS. FS 471/481 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-03 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-03 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2023-02-03 08:22:43 | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | REQUESTED IN THE 1ST CYCLE REVIEW COMMENTS, SEE BELOW: | | | | | | 1ST REVIEW FMC | | | PERMIT: 22120859 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR EACH UNIT. FEC C403.2.1 AND FMC 312.1 | | | 2) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES | | | OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL | | | DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL. | | | FS 471/481 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-27 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-27 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2023-01-27 08:03:27 | 1ST REVIEW FMC | | | PERMIT: 22120859 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR EACH UNIT. FEC C403.2.1 AND FMC 312.1 | | | 2) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES | | | OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL | | | DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL. | | | FS 471/481 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-02-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-02-28 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-02-28 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-27 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-27 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2023-02-27 08:37:02 | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR EACH UNIT. FEC C403.2.1 AND FMC 312.1 | | | 2) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES | | | OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL | | | DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL. | | | FS 471/481 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-03 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-03 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2023-02-03 08:24:21 | PROVIDE THE ORIGINAL DIGITALLY SIGNED DOCUMENTS | | | REQUESTED IN THE 1ST CYCLE REVIEW COMMENTS. SEE BELOW: | | | | | | 1) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES | | | OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL | | | DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL. | | | FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-27 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-27 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2023-01-27 08:05:32 | 1) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES | | | OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL | | | DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL. | | | FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|