Plan Review Details - Permit 22120781
| Plan Review Stops For Permit 22120781 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-01-10 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-01-10 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2023-01-10 15:55:24 | PROVISO: ISSUED AT APPLICANT'S RISK | | | FUEL PAD TO BE AT OR ABOVE BASE FLOOD ELEVATION 10.7 | | | NAVD88 | | | SUBMIT FUEL TANK ANCHORING SHOWING RESISTANCE TO WIND | | | LOADS PRIOR TO INSTALLATION (SUBMITTAL, NO FEE) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-12-29 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-12-29 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2022-12-29 15:41:53 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 105.13 SUBMIT AN APPLICATION FOR THE FUEL TANK. | | | YOU DO NOT NEED TO UPLOAD PLANS OR HAVE A CONTRACTOR AT | | | THIS TIME. | | | | | | 2. FBC 107.2.5, SUBMIT A SITE PLAN SHOWING LOCATION OF | | | PROPOSED PAD, INCLUDING THE FLOOD ZONE LINES. IF | | | LOCATED IN A FLOOD ZONE THE TANKS WILL BE REQUIRED TO | | | EITHER BE DESIGNED TO RESIST FLOOD LOADS OR THE SLAB | | | WILL BE REQUIRED TO BE ELEVATED TO BASE FLOOD OR ABOVE. | | | FBC B 1609, 1622. | | | | | | 3. FBC B CHAPTER 16, PROPOSED TANKS WILL BE REQUIRED TO | | | RESIST WIND LOADS AND POSSIBLY FLOOD LOADS DEPENDING ON | | | LOCATION AND ELEVATION. WHEN RESUBMITTING, CONFIRM THAT | | | THE ANCHORING OF THE TANKS WILL BE INCLUDED IN THE FUEL | | | PERMIT INFORMATION. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-09 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-09 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-12-28 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-12-28 |
Time |
|
Rev Time |
|
| Received By |
bdolan |
Date |
2022-12-28 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2022-12-28 13:31:34 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS FOR FINAL APPROVAL. | | | | | | CAPT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-18 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-12-22 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2022-12-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-30 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-30 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-12-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-12-29 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-12-29 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-01-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2023-01-18 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2023-01-18 |
Time |
13:16 |
Sent To |
|
|
| Notes |
|
|
|