2023-01-26 13:52:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 2) ADDRESS THE SIGNATURE REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-21 Cont ID  
Sent By jleahy Date 2022-12-21 Time 09:04 Rev Time 0.00
Received By jleahy Date 2022-12-21 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-09 Cont ID  
Sent By rmcdouga Date 2023-03-09 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2023-02-24 Time 06:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-26 Cont ID  
Sent By rmcdouga Date 2023-01-26 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2022-12-21 Time 06:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-09 Cont ID  
Sent By rmcdouga Date 2023-03-09 Time 10:30 Rev Time 0.00
Received By rmcdouga Date 2023-03-09 Time 10:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-26 Cont ID  
Sent By rmcdouga Date 2023-01-26 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2023-01-26 Time 13:48 Sent To  
Notes
2023-01-26 13:51:47THE GENERATOR PAD DRAWING IS REQUIRED TO BE SIGNED
 DIGITALLY BY THE ENGINEER. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
  
2022-12-21 09:05:30ELECTRICAL SIGNATURE APPROVED JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-06 Cont ID  
Sent By asangele Date 2023-03-06 Time 11:49 Rev Time 0.00
Received By asangele Date 2023-03-06 Time 11:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-30 Cont ID  
Sent By asangele Date 2022-12-30 Time 15:49 Rev Time 0.00
Received By asangele Date 2022-12-30 Time 15:49 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved