Plan Review Details - Permit 22120745
Plan Review Stops For Permit 22120745
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-05-15 Cont ID  
Sent By pvalenti Date 2023-05-15 Time 11:12 Rev Time 0.00
Received By pvalenti Date 2023-05-15 Time 11:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-05-08 Cont ID  
Sent By jbrooks Date 2023-05-08 Time 12:46 Rev Time 0.00
Received By jbrooks Date 2023-05-08 Time 08:09 Sent To  
Notes
2023-05-08 12:46:51JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. GENERAL LIMITATION #7 IS SPECIFICALLY
 REFERRED TO IN THIS PRODUCT APPROVAL FL16039-R18.
 SUBMIT FASTENER DENSITY CALCULATIONS PREPARED, SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT, OR REGISTERED ROOF
 CONSULTANT. NOTE: THIS PROJECT IS LOCATED IN AN
 EXPOSURE CATEGORY C AREA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-03-23 Cont ID  
Sent By jbrooks Date 2023-03-23 Time 14:31 Rev Time 0.00
Received By jbrooks Date 2023-03-23 Time 13:13 Sent To  
Notes
2023-03-23 14:32:23JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL225621.11-R2 COVERS MULTIPLE INSTALLATION
 OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT
 CORRECT INSTALLATION OPTIONS FROM PAGE #3 OF THE
 EVALUATION REPORT; SELECT CORRECT LOAD TABLE FOR USE;
 CIRCLE CORRECT WIND SPEED & INSTALLATION METHODS FOR
 ZONES 1, 2 & 3. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING.
 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL16039-R18 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16039-R18 COVERS MULTIPLE ROOF SYSTEMS FOR
 WOOD DECKS; SYSTEM TYPE WA1 THRU WW8. SELECT (ONE)
 SYSTEM TYPE TO BE USED THAT MEET THE EXPOSURE CATEGORY
 C; ZONE 3 MINIMUM DESIGN PRESSURE REQUIREMENT OF
 -108.17. PLEASE SELECT SYSTEM NO. THAT MEETS OR EXCEEDS
 REQUIREMENTS OR PROVIDE SIGNED AND SEALED ENGINEERED
 NAILING CALCULATION FOR ZONE 3. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 5. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-15 Cont ID  
Sent By jbrooks Date 2023-03-15 Time 11:08 Rev Time 0.00
Received By jbrooks Date 2023-03-15 Time 10:25 Sent To  
Notes
2023-03-15 11:08:35JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL25621-R1 IS INCOMPLETE & HAS BEEN REVISED TO
 FL25621-R2, PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS
 WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER,
 STATUS, GENERAL INFORMATION ABOUT THE PRODUCT).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL25621.09-R1 IS NOT RATED FOR USE IN ZONES 1,
 2 & 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D
 HAVE EITHER FLAT ROOF OR GABLE/HIP ROOF WITH MAX SLOPE
 OF 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY AREA.
 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL11602-R15 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 4. SUBMITTED MIAMI-DADE COUNTY NOA 22-0411.12 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES C(1) THROUGH E(4).
 SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS AN
 EXPOSURE CATEGORY C AREA.
 5. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-03 Cont ID  
Sent By jbrooks Date 2023-03-03 Time 09:25 Rev Time 0.00
Received By jbrooks Date 2023-03-03 Time 07:40 Sent To  
Notes
2023-03-03 09:27:35JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL38754-R0 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT). SECOND REQUEST.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL38754.03-R0 IS NOT RATED FOR USE IN ZONE 2 &
 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D HAVE
 EITHER FLAT ROOF OR GABLE/HIP ROOF WITH MAX SLOPE OF
 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY AREA.
 SECOND REQUEST
 3. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL11602-R10 IS THE 2017 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA???S FOR THE PROPOSED
 ROOF UNDERLAYMENT SYSTEM TO BE USED. INCLUDE COVER
 PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 FOR SYSTEM USED. SECOND REQUEST.
 4. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL16039-R18 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 5. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16039-R18 COVERS MULTIPLE ROOF SYSTEMS FOR
 WOOD DECKS; SYSTEM NO. W-A-1 THRU W-W-8. SELECTED
 SYSTEM TYPE TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 6. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING. SECOND REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By jbrooks Date 2023-02-02 Time 12:47 Rev Time 0.00
Received By jbrooks Date 2023-02-02 Time 08:19 Sent To  
Notes
2023-02-02 12:49:52JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL38754-R0 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL38754.03-R0 IS NOT RATED FOR USE IN ZONE 2 &
 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D HAVE
 EITHER FLAT ROOF OR GABLE/HIP ROOF WITH MAX SLOPE OF
 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY AREA.
 3. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL11602-R10 IS THE 2017 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA???S FOR THE PROPOSED
 ROOF UNDERLAYMENT SYSTEM TO BE USED. INCLUDE COVER
 PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 FOR SYSTEM USED.
 4. FBC B 107.2.1. PLEASE CLARIFY USE. SUBMITTED FLORIDA
 DBPR PRODUCT APPROVAL FL16039-R18 IS A SINGLE PLY ROOF
 SYSTEM; APPROVED HOUSE ELEVATION PLAN A-2 SPECS A METAL
 ROOF SYSTEM.
 5. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-05-15 Cont ID  
Sent By pvalenti Date 2023-05-15 Time 11:16 Rev Time 0.00
Received By pvalenti Date 2023-05-15 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-08 Cont ID  
Sent By jbrooks Date 2023-05-08 Time 12:47 Rev Time 0.00
Received By jbrooks Date 2023-05-03 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-03-23 Cont ID  
Sent By jbrooks Date 2023-03-23 Time 14:32 Rev Time 0.00
Received By jbrooks Date 2023-03-16 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-15 Cont ID  
Sent By jbrooks Date 2023-03-15 Time 11:09 Rev Time 0.00
Received By jbrooks Date 2023-03-09 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2023-03-07 Cont ID  
Sent By aoliver Date 2023-03-07 Time 09:24 Rev Time 0.00
Received By aoliver Date 2023-02-17 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-02 Cont ID  
Sent By jbrooks Date 2023-02-02 Time 12:50 Rev Time 0.00
Received By jbrooks Date 2023-01-30 Time 10:48 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2023-03-07 Cont ID  
Sent By aoliver Date 2023-03-07 Time 08:12 Rev Time 0.00
Received By aoliver Date 2023-03-07 Time 08:12 Sent To  
Notes
2023-03-07 08:12:52APPROVED UNDER MASTER 22081317

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By shill Date 2022-12-19 Time 11:23 Rev Time 0.00
Received By shill Date 2022-12-19 Time 11:23 Sent To  
Notes
2022-12-19 11:23:52SEE MASTER REVIEW. PASS WHEN PRIVATE PROVIDER REVIEW
 UNDER MASTER HAS PASSED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-05-15 Cont ID  
Sent By pvalenti Date 2023-05-15 Time 11:13 Rev Time 0.00
Received By pvalenti Date 2023-05-15 Time 11:09 Sent To  
Notes
2023-05-15 11:15:58PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY SUBMITTAL OF ENGINEER'S
 ORIGINAL PAPER HAND SIGNED/SEALED LETTER INCLUDING THE
 WIND ZONE ANCHOR SPACING FOR THE WINDLOAD DESIGN.