| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL36904.1-R7 MAXIMUM DESIGN PRESSURE -101.25 |
| | PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE |
| | REQUIREMENT OF -102 FOR EXPOSURE CATEGORY C AREAS WITH |
| | A GABLE ROOF; ROOF SLOPES 5/12-6/12 MEAN ROOF HEIGHT UP |
| | TO 15 FT. SELECT SYSTEM THAT MEETS OR EXCEEDS THIS |
| | REQUIREMENT. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING. |
| | 2. FBC B 107.2.1. PLEASE VERIFY: SUBMITTED ROOF DIAGRAM |
| | INDICATES ROOF SLOPE OF 5/12; GOOGLE EARTH IMAGE |
| | APPEARS TO SHOW ROOF SLOPE LESS THAN 5/12. IF LESS THAN |
| | 5/12 THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT IS |
| | -121 FOR EXPOSURE CATEGORY C AREAS WITH A GABLE ROOF; |
| | ROOF SLOPES 2/12-4/12 MEAN ROOF HEIGHT UP TO 15 FT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |