| Plan Review Stops For Permit 22120701 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2023-01-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-09 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-09 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2023-01-09 08:23:08 | ELECTRIC IS UNDER PERMIT 22110943 MP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-27 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-27 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2022-12-27 14:32:32 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE ELECTRICAL PLANS DETAILING ELECTRICAL | | | OUTLETS TO BE INSTALLED, INCLUDE CONDUCTOR SIZES, GFI | | | PROTECTION, AND PANEL SCHEDULE AS APPLICABLE. NEC 215.5 | | | AND NEC 210.8(B)(5) | | | 2) PLAN SUBMITTED DETAILS A PE TITLE BLOCK WITHOUT THE | | | REQUIRED SIGNATURE AN SEAL.SEE SIGNATURE REVIEW | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-01-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-12 |
Time |
10:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2023-01-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-04 |
Time |
12:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-27 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-16 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-13 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-13 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-06 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-06 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2023-01-06 07:55:03 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22120496 | | | 1/6/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AAV SHALL NOT BE USED TO VENT THE SOLIDS | | | INTERCEPTOR- SEC. 918.8 FBC P. PLEASE REVIEW THE | | | MANUFACTURER???S INSTALLATION GUIDELINES FOR ACCEPTABLE | | | VENTING METHODS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-12-19 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-12-19 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2022-12-19 12:51:04 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 2210701 | | | 12/19/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A2: THE PLAN SHEET IS FAILED BECAUSE IT IS AN | | | ENGINEER' S PLAN THAT HAS BEEN COPIED AND MARKED UP BY | | | THE CONTRACTOR. THE APPLICANT CAN EITHER SUBMIT A | | | DRAWING PREPARED AND SIGNED BY THE PLUMBING CONTRACTOR, | | | OR HAVE THE ENGINEER PROVIDE A REVISED DIDITALLY SIGNED | | | AND SEALED PLAN WITH THE NEW DETAILS- SECTION 107.2.1 | | | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | | | | | 2) A2: THE APPLICATION INDICATES A GARBAGE DISPOSAL | | | WILL BE INSTALLED HOWEVER THE DISPOSAL IS NOT NOTED ON | | | THE PLAN- SEC. 107.2.1 WPB. PLEASE NOTE THAT THE | | | DISPOSAL SHALL DISCHARGE INTO A SOLIDS INTERCEPTOR | | | PRIOR TO DRAINING INTO THE GREASE INTERCEPTOR- SEC. | | | 1003.3.2 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-13 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-13 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-10 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-10 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2023-01-10 14:17:53 | 2ND SIGNATURE REVIEW. | | | 1/10/23 | | | | | | THE HAND DRAWN PLUMBING DETAILS PREPARED BY THE | | | CONTRACTOR CANNOT BE PLACED ON THE LICENSED ENGINEER'S | | | APPROVED ELECTRICAL PLAN. PLANS SUBMITTED | | | FOR PERMITTING AND PUBLIC RECORD THAT BEAR A FL. | | | LICENSED ENGINEEER'S TITLE BLOCK SHALL BE DIGITALLY | | | SIGNED AND SEALED BY THE ENGINEER PER FL. STATUTE | | | 471..025 & SEC. 61G15-23.005 FAC. THE CONTRACTOR SHALL | | | PROVIDE HIS OWN PLAN FOR THE PROPOSED PROJECT- FL | | | STATUTE 471.003(2)(H) & 471.025. | | | | | | CHRISTOPHER L. COLE | | | 401 CLEMATIS C STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | [email protected] | | | | | | | | | 1ST SIGNATURE REVIEW FAILED | | | | | | 1) PLAN SUBMITTED DETAILS A PE TITLE BLOCK WITHOUT THE | | | REQUIRED SIGNATURE AN SEAL.. PLEASE CORRECT AS OUTLINED | | | BELOW | | | | | | . | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-27 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-27 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2022-12-27 14:34:25 | SIGNATURE REVIEW FAILED | | | | | | 1) PLAN SUBMITTED DETAILS A PE TITLE BLOCK WITHOUT THE | | | REQUIRED SIGNATURE AN SEAL.. PLEASE CORRECT AS OUTLINED | | | BELOW | | | | | | . | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|