| Plan Review Stops For Permit 22120680 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-21 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-21 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2023-07-21 09:42:29 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | 5TH REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT | | | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE | | | PRODUCT APPROVAL. | | | | | | 2) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - | | | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 3) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) | | | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-05-15 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-05-15 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2023-05-15 14:37:14 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | 4TH REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT | | | VENTS) - R806.1 VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | 2) A SMOKE DETECTOR IS REQUIRED IN THE HALLWAY NEAR THE | | | BEDROOMS - FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE | | | INSTALLED IN THE FOLLOWING LOCATIONS: | | | | | | A).IN EACH SLEEPING ROOM. | | | | | | B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING | | | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL | | | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR | | | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN | | | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE | | | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR | | | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL | | | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. | | | | | | D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET | | | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A | | | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS | | | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY | | | SECTION R314.3. | | | | | | 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT | | | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE | | | PRODUCT APPROVAL. | | | | | | 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - | | | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) | | | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-21 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-21 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2023-04-21 12:55:42 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | 3RD REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT | | | VENTS) - R806.1 VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | 2) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS - | | | FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN | | | THE FOLLOWING LOCATIONS: | | | | | | A).IN EACH SLEEPING ROOM. | | | | | | B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING | | | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL | | | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR | | | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN | | | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE | | | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR | | | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL | | | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. | | | | | | D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET | | | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A | | | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS | | | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY | | | SECTION R314.3. | | | | | | 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT | | | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE | | | PRODUCT APPROVAL. | | | | | | 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - | | | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) | | | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-30 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-30 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2023-03-30 08:52:26 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT | | | VENTS) - R806.1 VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | 2) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS - | | | FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN | | | THE FOLLOWING LOCATIONS: | | | | | | A).IN EACH SLEEPING ROOM. | | | | | | B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING | | | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL | | | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR | | | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN | | | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE | | | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR | | | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL | | | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. | | | | | | D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET | | | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A | | | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS | | | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY | | | SECTION R314.3. | | | | | | 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT | | | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE | | | PRODUCT APPROVAL. | | | | | | 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - | | | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) | | | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 6) DRAWING SP-1 DOES NOT SHOW AS DIGITALLY SIGNED IN | | | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX | | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED | | | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-23 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-23 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2023-02-23 09:21:00 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION - R806.1 | | | VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | 2) DRAWING SP-1 THE INCORRECT DOOR SIZE IS SHOWN ON THE | | | DOOR SCHEDULE - PLEASE CORRECT. | | | | | | 3) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS - | | | FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 4) PLEASE SHOW THE EXTERIOR WINDOW AND DOOR FLASHING - | | | FBC R703.1.1 WATER RESISTANCE. | | | THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND | | | CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION | | | OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A | | | WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS | | | REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO | | | THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR | | | CLADDING. | | | EXCEPTIONS: 1. A WEATHER-RESISTANT EXTERIOR WALL | | | ENVELOPE SHALL NOT BE REQUIRED OVER CONCRETE OR MASONRY | | | WALLS DESIGNED IN ACCORDANCE WITH CHAPTER 6 AND FLASHED | | | IN ACCORDANCE WITH SECTION R703.4. | | | | | | 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT | | | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE | | | PRODUCT APPROVAL. | | | | | | 6) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) - | | | PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 7) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857) | | | - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE | | | PRODUCT APPROVAL. | | | | | | 8) PLEASE SHOW THE EXISTING FLOOR PLAN - SHOWING THE | | | USE FOR EACH ROOM - THE NEW ADDITION CANNOT BLOCK AN | | | EMERGENCY EGRESS FOR AN EXISTING BEDROOM - FBC R310.1 | | | EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED. | | | BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM | | | SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE | | | AND RESCUE OPENING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-07-31 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2023-05-25 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-05-25 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-05-25 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-05-02 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-05-02 |
Time |
13:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-03 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-03 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-02-06 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-02-06 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2023-02-06 12:26:30 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. REVIEW EXISTING MAIN PANEL "A" SCHEDULE PROVIDED | | | (VA, TRIP, WIRE) TO BE IN ACCORDANCE WITH NEC 220, 240, | | | 310.15(B)(16) | | | | | | 2. PROVIDE MAIN PANEL SCHEDULE WITH EXISTING AND NEW | | | LOAD ALONG WITH THE LOAD CALCULATION. NEC 220, NEC | | | 408.4(A) | | | | | | 3. PROVIDE INFORMATION OF THE SERVICE. NEC 230 | | | | | | 4. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON | | | MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN | | | ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315 | | | | | | 5. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2023-07-17 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-07-06 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-07-06 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-05-12 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-05-03 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-04-20 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-04-19 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-03-27 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-23 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-27 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-23 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-23 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2023-02-23 09:21:59 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
| Sent By |
jbaker |
Date |
2023-07-25 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
jbaker |
Date |
2023-07-25 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-02 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-02 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-03 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-03 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2023-04-03 15:58:58 | THE ENERGY CALCULATIONS SUBMITTED THIS CYCLE IS FOR THE | | | ENTIRE HOUSE WHICH IS 1472 SQUARE FEET. THE MECHANICAL | | | DRAWING SHOWS THE NEW MECHANICAL SYSTEM IS FOR THE | | | ADDITION ONLY. PROVIDE AN ENERGY CALCULATION FOR THE | | | NEW ADDITION ONLY. | | | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS THAT WERE | | | ASKED FOR IN THE FIRST CYCLE REVIEW WAS NOT SUBMITTED. | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS ADDITION. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-30 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-30 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2023-01-30 15:51:42 | 1ST REVIEW FMC | | | PERMIT: 22120680 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS NEW | | | ADDITION INCLUDING THE ENERGY CALCULATIONS, MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS AND A MECHANICAL DRAWING | | | SHOWING THE DESIGNED SYSTEM. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-01-30 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-01-30 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-21 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-21 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2023-07-21 09:43:14 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-05-15 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-05-15 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2023-05-15 14:37:50 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2023-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-21 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-21 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2023-04-21 12:58:02 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-30 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-30 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2023-03-30 08:53:30 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-23 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-23 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2023-02-23 09:22:34 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
F |
Date |
2023-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-07-21 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-07-21 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2023-07-21 09:45:02 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SP-1, E101, M1 DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-05-15 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-05-15 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2023-05-15 14:42:30 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SP-1, E101 DO NOT SHOW AS DIGITALLY SIGNED | | | IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-04-21 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-04-21 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-30 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-30 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2023-03-30 08:59:38 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SP-1, M1, E101 DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-23 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-23 |
Time |
09:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2023-07-27 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-07-27 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-07-27 |
Time |
17:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2023-07-06 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-07-06 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-07-06 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-05-03 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-05-03 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
2023-04-19 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-04-19 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
AVolcy |
Date |
2023-02-07 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
2023-02-07 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|