Plan Review Details - Permit 22120680
Plan Review Stops For Permit 22120680
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 09:40 Sent To  
Notes
2023-07-21 09:42:29SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 5TH REVIEW
  
 CORRECTIONS NEEDED -
  
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE
 PRODUCT APPROVAL.
  
 2) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) -
 PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 3) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857)
 - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-05-15 Cont ID  
Sent By rmcphers Date 2023-05-15 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2023-05-15 Time 14:34 Sent To  
Notes
2023-05-15 14:37:14SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 4TH REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT
 VENTS) - R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 2) A SMOKE DETECTOR IS REQUIRED IN THE HALLWAY NEAR THE
 BEDROOMS - FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE
 INSTALLED IN THE FOLLOWING LOCATIONS:
  
 A).IN EACH SLEEPING ROOM.
  
 B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE
 PRODUCT APPROVAL.
  
 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) -
 PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857)
 - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-21 Cont ID  
Sent By rmcphers Date 2023-04-21 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2023-04-21 Time 12:53 Sent To  
Notes
2023-04-21 12:55:42SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 3RD REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT
 VENTS) - R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 2) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS -
 FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN
 THE FOLLOWING LOCATIONS:
  
 A).IN EACH SLEEPING ROOM.
  
 B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE
 PRODUCT APPROVAL.
  
 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) -
 PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857)
 - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-30 Cont ID  
Sent By rmcphers Date 2023-03-30 Time 08:53 Rev Time 0.00
Received By rmcphers Date 2023-03-30 Time 08:43 Sent To  
Notes
2023-03-30 08:52:26SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION (SOFFIT
 VENTS) - R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 2) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS -
 FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 FBC R314.3 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN
 THE FOLLOWING LOCATIONS:
  
 A).IN EACH SLEEPING ROOM.
  
 B).OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 C).ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 D).SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE
 PRODUCT APPROVAL.
  
 4) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) -
 PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 5) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857)
 - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 6) DRAWING SP-1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 08:27 Sent To  
Notes
2023-02-23 09:21:00SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED ROOF VENTILATION - R806.1
 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
 2) DRAWING SP-1 THE INCORRECT DOOR SIZE IS SHOWN ON THE
 DOOR SCHEDULE - PLEASE CORRECT.
  
 3) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS -
 FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 4) PLEASE SHOW THE EXTERIOR WINDOW AND DOOR FLASHING -
 FBC R703.1.1 WATER RESISTANCE.
 THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND
 CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION
 OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A
 WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS
 REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO
 THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR
 CLADDING.
 EXCEPTIONS: 1. A WEATHER-RESISTANT EXTERIOR WALL
 ENVELOPE SHALL NOT BE REQUIRED OVER CONCRETE OR MASONRY
 WALLS DESIGNED IN ACCORDANCE WITH CHAPTER 6 AND FLASHED
 IN ACCORDANCE WITH SECTION R703.4.
  
 5) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTES IN THE
 PRODUCT APPROVAL.
  
 6) PRODUCT APPROVAL PROVIDED FOR THE DOOR (FL0237) -
 PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 7) PRODUCT APPROVAL PROVIDED FOR THE WINDOWS (FL21857)
 - PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE
 PRODUCT APPROVAL.
  
 8) PLEASE SHOW THE EXISTING FLOOR PLAN - SHOWING THE
 USE FOR EACH ROOM - THE NEW ADDITION CANNOT BLOCK AN
 EMERGENCY EGRESS FOR AN EXISTING BEDROOM - FBC R310.1
 EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE
 AND RESCUE OPENING.

Review Stop E ELECTRICAL
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rperdomo Date 2023-07-31 Time 10:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-05-25 Cont ID  
Sent By rperdomo Date 2023-05-25 Time 14:36 Rev Time 0.00
Received By rperdomo Date 2023-05-25 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-02 Cont ID  
Sent By rperdomo Date 2023-05-02 Time 13:28 Rev Time 0.00
Received By rperdomo Date 2023-05-02 Time 13:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-04-03 Cont ID  
Sent By rperdomo Date 2023-04-03 Time 16:14 Rev Time 0.00
Received By rperdomo Date 2023-04-03 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-06 Cont ID  
Sent By rperdomo Date 2023-02-06 Time 12:26 Rev Time 0.00
Received By rperdomo Date 2023-02-06 Time 11:30 Sent To  
Notes
2023-02-06 12:26:30FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. REVIEW EXISTING MAIN PANEL "A" SCHEDULE PROVIDED
 (VA, TRIP, WIRE) TO BE IN ACCORDANCE WITH NEC 220, 240,
 310.15(B)(16)
  
 2. PROVIDE MAIN PANEL SCHEDULE WITH EXISTING AND NEW
 LOAD ALONG WITH THE LOAD CALCULATION. NEC 220, NEC
 408.4(A)
  
 3. PROVIDE INFORMATION OF THE SERVICE. NEC 230
  
 4. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 5. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11
 THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-17 Time 13:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-06 Cont ID  
Sent By avolcy Date 2023-07-06 Time 11:21 Rev Time 0.00
Received By avolcy Date 2023-05-12 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-03 Cont ID  
Sent By avolcy Date 2023-05-03 Time 11:03 Rev Time 0.00
Received By avolcy Date 2023-04-20 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-19 Cont ID  
Sent By avolcy Date 2023-04-19 Time 13:59 Rev Time 0.00
Received By avolcy Date 2023-03-27 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 09:23 Rev Time 0.00
Received By rmcphers Date 2023-01-27 Time 13:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 09:21 Sent To  
Notes
2023-02-23 09:21:59PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-07-25 Cont ID  
Sent By jbaker Date 2023-07-25 Time 10:10 Rev Time 0.00
Received By jbaker Date 2023-07-25 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 10:43 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-04-03 Cont ID  
Sent By medwards Date 2023-04-03 Time 15:59 Rev Time 0.00
Received By medwards Date 2023-04-03 Time 15:59 Sent To  
Notes
2023-04-03 15:58:58THE ENERGY CALCULATIONS SUBMITTED THIS CYCLE IS FOR THE
 ENTIRE HOUSE WHICH IS 1472 SQUARE FEET. THE MECHANICAL
 DRAWING SHOWS THE NEW MECHANICAL SYSTEM IS FOR THE
 ADDITION ONLY. PROVIDE AN ENERGY CALCULATION FOR THE
 NEW ADDITION ONLY.
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS THAT WERE
 ASKED FOR IN THE FIRST CYCLE REVIEW WAS NOT SUBMITTED.
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS ADDITION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 15:51 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 15:51 Sent To  
Notes
2023-01-30 15:51:421ST REVIEW FMC
 PERMIT: 22120680
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THIS NEW
 ADDITION INCLUDING THE ENERGY CALCULATIONS, MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND A MECHANICAL DRAWING
 SHOWING THE DESIGNED SYSTEM. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-01-30 Cont ID  
Sent By ccole Date 2023-01-30 Time 16:23 Rev Time 0.00
Received By ccole Date 2023-01-30 Time 16:14 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 09:42 Sent To  
Notes
2023-07-21 09:43:14SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2023-05-15 Cont ID  
Sent By rmcphers Date 2023-05-15 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2023-05-15 Time 14:37 Sent To  
Notes
2023-05-15 14:37:50SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2023-04-21 Cont ID  
Sent By rmcphers Date 2023-04-21 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2023-04-21 Time 12:57 Sent To  
Notes
2023-04-21 12:58:02SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2023-03-30 Cont ID  
Sent By rmcphers Date 2023-03-30 Time 08:53 Rev Time 0.00
Received By rmcphers Date 2023-03-30 Time 08:53 Sent To  
Notes
2023-03-30 08:53:30SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 09:22 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 09:22 Sent To  
Notes
2023-02-23 09:22:34SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-07-21 Cont ID  
Sent By rmcphers Date 2023-07-21 Time 09:44 Rev Time 0.00
Received By rmcphers Date 2023-07-21 Time 09:44 Sent To  
Notes
2023-07-21 09:45:02SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP-1, E101, M1 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-05-15 Cont ID  
Sent By rmcphers Date 2023-05-15 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2023-05-15 Time 14:39 Sent To  
Notes
2023-05-15 14:42:30SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP-1, E101 DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-21 Cont ID  
Sent By rmcphers Date 2023-04-21 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2023-04-21 Time 12:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-30 Cont ID  
Sent By rmcphers Date 2023-03-30 Time 08:58 Rev Time 0.00
Received By rmcphers Date 2023-03-30 Time 08:58 Sent To  
Notes
2023-03-30 08:59:38SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SP-1, M1, E101 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-02-23 Cont ID  
Sent By rmcphers Date 2023-02-23 Time 09:23 Rev Time 0.00
Received By rmcphers Date 2023-02-23 Time 09:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2023-07-27 Cont ID  
Sent By avolcy Date 2023-07-27 Time 17:24 Rev Time 0.00
Received By avolcy Date 2023-07-27 Time 17:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2023-07-06 Cont ID  
Sent By avolcy Date 2023-07-06 Time 11:21 Rev Time 0.00
Received By avolcy Date 2023-07-06 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2023-05-03 Cont ID  
Sent By avolcy Date 2023-05-03 Time 11:03 Rev Time 0.00
Received By avolcy Date 2023-05-03 Time 11:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-19 Cont ID  
Sent By avolcy Date 2023-04-19 Time 13:59 Rev Time 0.00
Received By avolcy Date 2023-04-19 Time 13:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-02-07 Cont ID  
Sent By AVolcy Date 2023-02-07 Time 09:10 Rev Time 0.00
Received By avolcy Date 2023-02-07 Time 09:09 Sent To  
Notes
***NONE***