| 2023-02-02 08:18:45 | ELECTRIC REVIEW FAILED |
| | 1) APPLICATION STATES TO CHANGE ELECTRIC PANEL. PLANS |
| | SUBMITTED DETAIL NUCH MORE E;LECTRIC WORK. IN ADDITION |
| | THERE IS 2 MORE UNITS WITHOUT DRAWINGS. PLEASE PROVIDE |
| | APPROPRIATE PLANS AS OUTLINED BELOW. |
| | |
| | .FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | TO ENSURE CLARITY, ELECTRIC WORK SUBMITTALS SHOULD |
| | INCLUDE ELECTRIC DRAWINGS DETAILING EXISTING |
| | CONDITIONS, ALL PROPOSED CHANGES AND A DETAILED WORK |
| | SCOPE. FLOOR PLANS, SITE PLANS, ELECTRIC RISER |
| | DIAGRAMS, LOAD CALCULATIONS, EQUIPMENT SIZES AND |
| | SPECIFICATIONS, CONDUCTOR SIZES AND TYPE AND PRODUCT |
| | SPECIFICATIONS OR ANY RELEVANT DETAILS, AS APPLICABLE, |
| | MAY BE REQUIRED. IN ADDITION, IT IS REQUIRED TO |
| | IDENTIFY THE DESIGNER OF RECORD ON ALL DRAWINGS/PLANS, |
| | THIS SHOULD INCLUDE THE DESIGNERS SIGNATURE. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |