Plan Review Details - Permit 22120665
Plan Review Stops For Permit 22120665
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-24 Cont ID  
Sent By cthroop Date 2023-02-24 Time 09:45 Rev Time 0.00
Received By cthroop Date 2023-02-24 Time 06:47 Sent To  
Notes
2023-02-24 09:51:091ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PERMIT TYPE HAS BEEN CHANGED TO COM-RFEMODEL
  
 1. PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN FOR EACH
 UNIT.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 2. IDENTIFY LOCATION OF DRYWALL WORK. PROVIDE TOTAL
 SQUARE FOOTAGE.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 3. IDENTIFY TYPE AND LOCATION OF PROPOSED FLOORING.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By mpeterso Date 2023-02-02 Time 08:15 Rev Time 0.00
Received By mpeterso Date 2023-02-02 Time 08:11 Sent To  
Notes
2023-02-02 08:18:45ELECTRIC REVIEW FAILED
 1) APPLICATION STATES TO CHANGE ELECTRIC PANEL. PLANS
 SUBMITTED DETAIL NUCH MORE E;LECTRIC WORK. IN ADDITION
 THERE IS 2 MORE UNITS WITHOUT DRAWINGS. PLEASE PROVIDE
 APPROPRIATE PLANS AS OUTLINED BELOW.
  
 .FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 TO ENSURE CLARITY, ELECTRIC WORK SUBMITTALS SHOULD
 INCLUDE ELECTRIC DRAWINGS DETAILING EXISTING
 CONDITIONS, ALL PROPOSED CHANGES AND A DETAILED WORK
 SCOPE. FLOOR PLANS, SITE PLANS, ELECTRIC RISER
 DIAGRAMS, LOAD CALCULATIONS, EQUIPMENT SIZES AND
 SPECIFICATIONS, CONDUCTOR SIZES AND TYPE AND PRODUCT
 SPECIFICATIONS OR ANY RELEVANT DETAILS, AS APPLICABLE,
 MAY BE REQUIRED. IN ADDITION, IT IS REQUIRED TO
 IDENTIFY THE DESIGNER OF RECORD ON ALL DRAWINGS/PLANS,
 THIS SHOULD INCLUDE THE DESIGNERS SIGNATURE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2023-03-03 Cont ID  
Sent By amhamilt Date 2023-03-03 Time 12:16 Rev Time 0.00
Received By amhamilt Date 2023-03-03 Time 12:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-06 Cont ID  
Sent By aoliver Date 2023-03-06 Time 08:32 Rev Time 0.00
Received By aoliver Date 2023-01-26 Time 09:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-27 Cont ID  
Sent By medwards Date 2023-01-27 Time 07:34 Rev Time 0.00
Received By medwards Date 2023-01-27 Time 07:34 Sent To  
Notes
2023-01-27 07:34:401ST REVIEW FMC
 PERMIT: 22120665
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR EACH UNIT. FEC C403.2.1 AND FMC 312.1
 2) THE ELECTRONIC SIGNATURES ON THE DRAWINGS ARE COPIES
 OF THE ORIGINAL. DIGITALLY SUBMIT THE ORIGINAL
 DIGITALLY SIGNED DRAWINGS INTO THE PROJECT???S PORTAL.
 FS 471/481
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-02-24 Cont ID  
Sent By rwbrown Date 2023-02-24 Time 08:38 Rev Time 0.00
Received By rwbrown Date 2023-02-24 Time 08:38 Sent To  
Notes
2023-02-24 08:39:161ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE SUBMIT THE
 PLUMBING SCOPE OF WORK.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-02-02 Cont ID  
Sent By mpeterso Date 2023-02-02 Time 08:20 Rev Time 0.00
Received By mpeterso Date 2023-02-02 Time 08:20 Sent To  
Notes
2023-02-02 08:22:16SIGNATURE REVIEW FAILED
  
 1) ALL PLANS DETAIL AN ENGINEERS DIGITAL SIGNATURE
 STAMP, HOWEVER. BLUEBEAM AND ADOBE SOFTWARE DO NOT
 INDICATE A DIGITAL SIGNATURE OR CERTIFICATION OF
 DIGITAL SIGNATURE BY A THIRD-PARTY AGENCY. PLEASE
 CORRECT AS OUTLINED BELOW.
  
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2023-01-27 07:37:12MECHANICAL DIGITAL SIGNATURES ARE COPIES OF THE
 ORIGINAL, SUBMIT THE ORIGINAL DIGITALLY SIGNED
 DOCUMENTS INTO THE PROJECT'S PORTAL. FS 471/481
  