Plan Review Details - Permit 22120565
Plan Review Stops For Permit 22120565
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-22 Cont ID  
Sent By medwards Date 2022-12-22 Time 16:06 Rev Time 0.00
Received By medwards Date 2022-12-20 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-22 Cont ID  
Sent By medwards Date 2022-12-22 Time 16:00 Rev Time 0.00
Received By medwards Date 2022-12-22 Time 16:00 Sent To  
Notes
2022-12-22 16:02:38PROVIDE THE BRANCH DUCT SIZES ON THE MECHANICAL
 DRAWING. FBC 107.3.5
  
 IF THE UNIT IS A LIKE FOR LIKE PLEASE SUBMIT THE
 COMPLETED LIKE FOR LIKE FORM FOR THE AHU.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-22 Cont ID  
Sent By medwards Date 2022-12-22 Time 16:03 Rev Time 0.00
Received By medwards Date 2022-12-22 Time 16:03 Sent To  
Notes
2022-12-22 16:05:55THE DESIGNER MUST DIGITALLY SIGN THE DOCUMENT AND THE
 ORIGINAL MUST BE SUBMITTED FOR REVIEW. THE DOCUMENT
 SUBMITTED IS A COPY OF THE ORIGINAL DRAWING WHICH
 REMOVES THE DIGITAL SIGNATURE LAYER FROM THE DRAWING.
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  