Plan Review Details - Permit 22120498
Plan Review Stops For Permit 22120498
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-28 Time 07:13 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-01-31 Cont ID  
Sent By rwbrown Date 2023-01-31 Time 15:29 Rev Time 0.00
Received By rwbrown Date 2023-01-31 Time 15:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-01-25 Cont ID  
Sent By rwbrown Date 2023-01-25 Time 09:56 Rev Time 0.00
Received By rwbrown Date 2023-01-25 Time 09:56 Sent To  
Notes
2023-01-25 10:09:411ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.5 - GAS - SUBMIT THE GAS
 DIAGRAM FOR THE WATER HEATER MANIFOLDING. INCLUDE PIPE
 SIZES FOR THE MANIFOLD.
  
 2. 2020 FGC 503.2.3 - SHOW THE INTENDED EXHAUST VENTING
 IN A DIAGRAM THAT INCLUDES THE PIPE SIZES OF THE VENT
 PIPES FOR THE WATER HEATERS. IF YOU ARE GOING TO
 MANIFOLD THE EXHAUSTS, INCLUDE THE MANUFACTURERS'
 INSTRUCTIONS AND GUIDELINES THAT DETAIL THE EXHAUST
 MANIFOLD.
  
 3. 2020 FGC 503.8 - SHOW THE TERMINATION OF THE VENT
 PIPING OF THE WATER HEATERS TO BE IN COMPLIANCE WITH
 THIS SECTION. SHOW THE REQUIRED SEPARATION DISTANCES
 BETWEEN THE EXHAUST TERMINATIONS FROM THE DIRECT VENT
 APPLIANCES AND OPENINGS INTO THE STRUCTURE, MECHANICAL
 INTAKES, ETC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-28 Time 07:13 Rev Time 0.00
Received By rwbrown Date 2023-02-27 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-31 Cont ID  
Sent By rwbrown Date 2023-01-31 Time 15:35 Rev Time 0.00
Received By rwbrown Date 2023-01-30 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-25 Cont ID  
Sent By rwbrown Date 2023-01-25 Time 10:12 Rev Time 0.00
Received By rwbrown Date 2023-01-24 Time 08:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-28 Time 07:13 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-31 Cont ID  
Sent By rwbrown Date 2023-01-31 Time 15:23 Rev Time 0.00
Received By rwbrown Date 2023-01-31 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-01-25 Cont ID  
Sent By rwbrown Date 2023-01-25 Time 09:18 Rev Time 0.00
Received By rwbrown Date 2023-01-25 Time 09:16 Sent To  
Notes
2023-01-25 09:56:061ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - SUBMIT A DIAGRAM THAT
 SHOWS THE MANIFOLDED LAYOUT OF THE WATERHEATERS WITH A
 WATER PIPING DIAGRAM. THE WATER PIPING DIAGRAM SHOULD
 INCLUDE WATER PIPE SIZES. I BELIEVE THIS IS PAGE P-8.3
 FROM THE MASTER PLANS. INCLUDE THE WATER HEATER
 SCHEDULE AS WELL.
  
 2. 2020 FPC 607.1.1 - IN THE DIAGRAM OF THE MANIFOLDED
 WATER HEATERS AND THE WATER PIPING DRAWING, INCLUDE A
 THERMOSTATIC MIXING VALVE AS REQUIRED BY THIS SECTION.
  
 3. 2020 FPC 607.2.2 - THE RETURN LINE SHALL CONNECT TO
 THE COLD WATER INLET PIPE OF THE WATER HEATER AND THE
 COLD WATER INLET PIPE OR THE HOT WATER RETURN
 CONNECTION OF THE THERMOSTATIC MIXING VALVE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-02-28 Cont ID  
Sent By rwbrown Date 2023-02-28 Time 07:13 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-01-31 Cont ID  
Sent By rwbrown Date 2023-01-31 Time 15:35 Rev Time 0.00
Received By rwbrown Date 2023-01-31 Time 15:35 Sent To  
Notes
2023-01-31 15:35:51SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
 * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-25 Cont ID  
Sent By rwbrown Date 2023-01-25 Time 10:09 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
2023-01-25 10:11:562017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME,
 AS WELL AS PUT THE CONTRACTOR'S NUMBER ON THE DRAWING
 AS REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1. IF THEY ARE DESIGNED BY AN ARCHITECT OR
 ENGINEER, THE FILES NEED TO BE ELECTRONICALLY SEALED IN
 ACCORDANCE WITH 61G15-23.005 F.A.C. OR 61G1-16.005
 F.A.C.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]