Plan Review Details - Permit 22120464
Plan Review Stops For Permit 22120464
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-12-13 Cont ID  
Sent By cpuell Date 2022-12-13 Time 11:45 Rev Time 0.00
Received By cpuell Date 2022-12-13 Time 11:45 Sent To  
Notes
2022-12-13 11:45:27ADDRESS APPROPRIATE FOR PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 11:01 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 11:01 Sent To  
Notes
2023-04-04 11:01:37THE SITE WALL REQUIRES A SEPARATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-07 Cont ID  
Sent By rmcphers Date 2023-03-07 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2023-03-07 Time 12:30 Sent To  
Notes
2023-03-07 12:47:05NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ATTIC ACCESS ON THE DRAWINGS IS SHOWN AS 24X24 -
 PLEASE SHOW THE ATTIC ACCESS SIZE PER - FBC R807.1 THE
 ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 INCHES
 BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN
 A HALLWAY OR OTHER LOCATION WITH READY ACCESS.
  
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 3) PLEASE SHOW THE GENERATOR EXHAUST LOCATION TO BE 10
 FEET FROM BUILDING OPENINGS - FBC R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT
  
 4) THE PROVIDED APPROVED LIST OF PRODUCT APPROVALS FROM
 THE ARCHITECT IS MISSING SOME OF THE PRODUCT APPROVALS
 THAT ARE UPLOADED TO PROJECTDOX AND SOME OF THE PRODUCT
 APPROVALS IN PROJECTDOX ARE NOT LISTED ON THE PRODUCT
 APPROVAL LIST FROM THE ARCHITECT. THE LISTED PRODUCT
 APPROVALS SHOULD MATCH THE PRODUCT APPROVALS LOADED
 INTO PROJECTDOX. PLEASE REVIEW THE LIST AND THE PRODUCT
 APPROVALS UPLOADED TO PROJECTDOX. IF NEEDED PLEASE E
 MAIL THE PERMIT LIBRARIAN TO REMOVE PRODUCT APPROVALS
 NOT NEEDED OR NOT LISTED ON THE APPROVED LIST FROM THE
 ARCHITECT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By rmcphers Date 2023-01-17 Time 16:16 Rev Time 0.00
Received By rmcphers Date 2023-01-17 Time 13:54 Sent To  
Notes
2023-01-17 16:04:11NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION - FBC
 R807.1
  
 2) PLEASE SHOW THE CEILING INSULATION TYPE AND "R"
 VALUE ON THE DRAWINGS TO MATCH THE ENERGY CALCULATIONS
 - FBC ENERGY
  
 3) PLEASE SHOW THE ATTIC VENTILATION - FBC R806.1
  
 4) PLEASE SHOW THE DOOR FROM THE GARAGE TO THE LIVING
 SPACE TO COMPLY WITH FBC R302.5.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMBCORE
 STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR
 20-MINUTE FIRE-RATED DOORS.
  
 5) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 6) IN THE PRODUCT APPROVAL FOR THE ROOFING UNDERLAYMENT
 (FL5259) - PLEASE CIRCLE ALL OF THE PRODUCT TYPES AND
 ATTACHMENTS DETAILS TO BE USED.
  
 7) PLEASE SHOW THE STORM WATER DRAINAGE FLOW ON THE
 SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC
 WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 8) SEPARATE PERMITS ARE REQUIRED FOR - SITE
 WALL,DRIVEWAY, POOL, GUESTHOUSE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-13 Cont ID  
Sent By rperdomo Date 2023-03-13 Time 08:58 Rev Time 0.00
Received By rperdomo Date 2023-03-09 Time 16:56 Sent To  
Notes
2023-03-13 08:52:01FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW
  
 1. THIS ELECTRICAL REVIEW IS ONLY FOR THE MAIN HOUSE
 (GENERATOR SYSTEM, SWIMMIMG POOL, AND GUESS HOUSE EACH
 OF THESE SYSTEMS AND STRUCTURE REQUIRE A SEPARATE
 PERMIT).
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-01-04 Cont ID  
Sent By rperdomo Date 2023-01-04 Time 13:03 Rev Time 0.00
Received By rperdomo Date 2023-01-04 Time 12:39 Sent To  
Notes
2023-01-04 13:03:00FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 1. GENERATOR SYSTEM AND SWIMMIMG POOL, EACH OF THESE
 SYSTEMS REQUIRE A SEPARATE PERMIT APPLICATION.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-03-06 Cont ID  
Sent By rrossano Date 2023-03-06 Time   Rev Time 0.00
Received By rrossano Date 2023-03-06 Time   Sent To  
Notes
2023-03-06 14:23:38SEPARATE DRIVEWAY PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2023-04-12 Cont ID  
Sent By rwbrown Date 2023-04-12 Time 09:57 Rev Time 0.00
Received By rwbrown Date 2023-04-12 Time 09:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2023-04-05 Cont ID  
Sent By rwbrown Date 2023-04-05 Time 14:49 Rev Time 0.00
Received By rwbrown Date 2023-04-05 Time 14:49 Sent To  
Notes
2023-04-05 14:49:333RDGAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. DONE
  
 4. NOT ADDRESSED - PAGE P3.2 STILL SHOWS GAS ROUGHED IN
 FOR THE DRYER. PLEASE REMOVE THIS IF THE INTENTION IS
 FOR AN ELECTRIC DRYER. IF GAS IS ROUGHED IN, THEN
 PROVISIONS FOR COMBUSTION AND/OR MAKE-UP AIR MUST STILL
 BE PROVIDED.
 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED COMBUSTION
 AIR CALCULATIONS FOR THE DRYER IN THE MAIN HOUSE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-03-06 Cont ID  
Sent By rwbrown Date 2023-03-06 Time 11:33 Rev Time 0.00
Received By rwbrown Date 2023-03-06 Time 11:33 Sent To  
Notes
2023-03-06 12:22:042ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. DONE
  
 4. PAGE P3.2 STILL SHOWS GAS ROUGHED IN FOR THE DRYER.
 PLEASE REMOVE THIS IF THE INTENTION IS FOR AN ELECTRIC
 DRYER. IF GAS IS ROUGHED IN, THEN PROVISIONS FOR
 COMBUSTION AND/OR MAKE-UP AIR MUST STILL BE PROVIDED.
 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED COMBUSTION
 AIR CALCULATIONS FOR THE DRYER IN THE MAIN HOUSE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 09:23 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 09:23 Sent To  
Notes
2022-12-30 09:31:141ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC R303.5.1 - VERIFY AND NOTATE THAT THE
 GENERATOR MUST BE 10 FEET FROM OPENINGS INTO THE
 STRUCTURE.
  
 2. 2020 FRC G2427.8 - VERIFY AND NOTATE THAT THE POOL
 HEATER MUST BE 4 FEET FROM OPENINGS INTO THE STRUCTURE.
  
 3. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED
 COMBUSTION AIR CALCULATIONS FOR THE RANGE IN THE MAIN
 HOUSE.
  
 4. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED
 COMBUSTION AIR CALCULATIONS FOR THE DRYER IN THE MAIN
 HOUSE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-04-06 Cont ID  
Sent By fmittner Date 2023-04-06 Time 13:29 Rev Time 0.00
Received By fmittner Date 2023-04-06 Time 13:29 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-30 Cont ID  
Sent By fmittner Date 2022-12-30 Time 16:21 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-12 Cont ID  
Sent By rwbrown Date 2023-04-12 Time 09:59 Rev Time 0.00
Received By rwbrown Date 2023-04-11 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-07 Cont ID  
Sent By aoliver Date 2023-04-07 Time 07:10 Rev Time 0.00
Received By aoliver Date 2023-04-03 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-15 Cont ID  
Sent By lmarchan Date 2023-03-15 Time 16:56 Rev Time 0.00
Received By lmarchan Date 2023-03-03 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By rmcphers Date 2023-01-17 Time 16:31 Rev Time 0.00
Received By rmcphers Date 2022-12-22 Time 16:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-04-06 Cont ID  
Sent By aoliver Date 2023-04-06 Time 08:15 Rev Time 0.00
Received By aoliver Date 2023-03-16 Time 11:32 Sent To  
Notes
2023-04-05 13:53:11RECEIPT MU-2023-012448 - $16,335.89 PAID
2023-03-16 11:32:203/16/23 EMAILED IMPACT OFFICE TO REVIEW - OK PER
 RMCPHERSON. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By rmcphers Date 2023-01-17 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2023-01-17 Time 16:17 Sent To  
Notes
2023-01-17 16:19:03PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-03-06 Cont ID  
Sent By medwards Date 2023-03-06 Time 14:14 Rev Time 0.00
Received By medwards Date 2023-03-06 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By medwards Date 2022-12-30 Time 14:35 Rev Time 0.00
Received By medwards Date 2022-12-30 Time 14:35 Sent To  
Notes
2022-12-30 14:35:441ST REVIEW FMC
 PERMIT: 22120464
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ZONE-1 MECHANICAL EQUIPMENT SIZING CALCULATIONS CALL
 FOR 2.4 TON WITH A TOTAL OF 29,541 BTUH AND SPECIFIES
 TRANE 4TTR6030 CU. SHEET M2.1 INDICATES 46,700 BTUH
 WITH A 4TTR6042J. PLEASE SHOW THAT THIS DESIGN WOULD
 MEET THE REQUIREMENTS OF FRC R403.7.1.2.1 HEAT PUMPS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-04-12 Cont ID  
Sent By rwbrown Date 2023-04-12 Time 09:57 Rev Time 0.00
Received By rwbrown Date 2023-04-12 Time 09:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-05 Cont ID  
Sent By rwbrown Date 2023-04-05 Time 14:49 Rev Time 0.00
Received By rwbrown Date 2023-04-05 Time 14:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-06 Cont ID  
Sent By rwbrown Date 2023-03-06 Time 11:29 Rev Time 0.00
Received By rwbrown Date 2023-03-06 Time 11:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 09:14 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 09:14 Sent To  
Notes
2022-12-30 09:14:401ST PLUMBING REVIEW - MAIN HOUSE
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. P4.1 - UPSTAIRS MASTER BATH - THE SHOWER AND TUB ARE
 BOTH ON THE HIGH SIDE OF THE VENT CONNECTION. ONLY ONE
 TRAPPED FIXTURE IS ALLOWED ON THE HIGH SIDE OF THE VENT
 CONNECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2023-03-07 Cont ID  
Sent By rmcphers Date 2023-03-07 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2023-03-07 Time 12:47 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By rmcphers Date 2023-01-17 Time 16:19 Rev Time 0.00
Received By rmcphers Date 2023-01-17 Time 16:19 Sent To  
Notes
2023-01-17 16:19:33SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-04-12 Cont ID  
Sent By rwbrown Date 2023-04-12 Time 09:58 Rev Time 0.00
Received By rwbrown Date 2023-04-12 Time 09:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-04-04 Cont ID  
Sent By rmcphers Date 2023-04-04 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2023-04-04 Time 11:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-07 Cont ID  
Sent By rmcphers Date 2023-03-07 Time 12:52 Rev Time 0.00
Received By rmcphers Date 2023-03-07 Time 12:52 Sent To  
Notes
2023-03-06 14:15:50MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-17 Cont ID  
Sent By rmcphers Date 2023-01-17 Time 16:30 Rev Time 0.00
Received By rmcphers Date 2023-01-17 Time 16:30 Sent To  
Notes
2022-12-30 14:36:22MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2023-04-06 Cont ID  
Sent By fmittner Date 2023-04-06 Time 13:29 Rev Time 0.00
Received By fmittner Date 2023-04-06 Time 13:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-03-15 Cont ID  
Sent By fmittner Date 2023-03-15 Time 12:38 Rev Time 0.00
Received By fmittner Date 2023-03-15 Time 12:38 Sent To  
Notes
2023-03-15 12:38:53REQUIRES SUBMITTAL OF SEPERATE LANDSCAPE PERMIT

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By hist Date 2022-12-30 Time 16:21 Rev Time 0.00
Received By fmittner Date 2022-12-30 Time 16:21 Sent To  
Notes
2022-12-30 16:27:02REQUIRES SEPERATE LANDSCAPE PERMIT