Plan Review Details - Permit 22120419
Plan Review Stops For Permit 22120419
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-14 Cont ID  
Sent By cthroop Date 2023-03-14 Time 14:25 Rev Time 0.00
Received By cthroop Date 2023-03-14 Time 14:04 Sent To  
Notes
2023-03-14 14:26:35PROVISO ON PAGE 1 OF 4: PROVIDE A COPY OF THE ICC-ES
 REPORT FOR THE SPRAY FOAM INSULATION TO THE CITY
 INSPECTOR. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-24 Cont ID  
Sent By cthroop Date 2023-01-24 Time 11:02 Rev Time 0.00
Received By cthroop Date 2023-01-24 Time 06:23 Sent To  
Notes
2023-01-24 11:19:151ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. NOA 21-0728.02 (SGD) HAS EXPIRED.
 PROVIDE A COPY OF THE CURRENT NOA OR FLORIDA PRODUCT
 APPROVAL, APPROVED UNDER THE 2020 FBC FOR THE PROPOSED
 SGD.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. PROVIDE THE TYPE OF DEVICE TO BE INSTALLED ON THE
 WINDOW AND DOOR SCHEDULES. YOU MAY ALSO ELECT TO PLACE
 THIS INFORMATION ON THE PLANS NEXT TO EACH OPENING.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 3. PROVIDE A COPY OF THE ICC-ES RE[PORT FOR THE SPRAY
 FOAM INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. THE SMOKE ALARM IN THE HALLWAY APPEARS TOO CLOSE TO
 THE BATHROOM DOOR.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3
  
 NOTICE: BUILDING REVIEW APPROVAL IS PENDING THE
 APPROVAL OF THE SIGNATURE REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-03-20 Cont ID  
Sent By rperdomo Date 2023-03-20 Time 08:36 Rev Time 0.00
Received By rperdomo Date 2023-03-20 Time 08:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-03-02 Cont ID  
Sent By rperdomo Date 2023-03-02 Time 14:45 Rev Time 0.00
Received By rperdomo Date 2023-03-02 Time 14:45 Sent To  
Notes
2023-03-02 14:51:34FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. SERVICE CONDUCTORS FOR DWELLING UNIT (SIZING) AND
 MAIN BREAKER PROTECTION. NEC 230, TABLE 310.15(B)(16),
 240.6
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-28 Cont ID  
Sent By rperdomo Date 2022-12-28 Time 11:15 Rev Time 0.00
Received By rperdomo Date 2022-12-28 Time 08:49 Sent To  
Notes
2022-12-28 11:14:57FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. DWELLING UNIT BATHROOMS SHAL BE IN ACCORDANCE WITH
 NEC 210.11(C)(3).
  
 2. CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION (PANEL
 SCHEDULE) NEEDS TO MATCH WITH LOAD CALCULATION, NEC
 408.4.
  
 3. MINIMUM WIRE SIZE FUSE OR CIRCUIT BREAKER SIZE PER
 TABLE NEC 240-3.
  
 4. PROVIDE A NOTE ON THE DRAWING FOR UNDERGROUND
 SERVICE, LATERALS SHALL HAVE THEIR LOCATION IDENTIFIED
 BY A
 WARNING RIBBON THAT IS PLACED IN THE TRENCH AT LEAST 12
 INCHES ABOVE THE UNDERGROUND INSTALLATION AS
 PER NEC 300-5 UNDERGROUND SERVICEPER.
  
 5. PROVIDE A NOTE ON THE DRAWING FOR ELECTRICAL PANEL
 AND ELECTRIC METER INSTALLATION AS PER NEC 110.14(D)
 CONDUCTOR TERMINATION, TORQUE - WHERE TIGHTENING TORQUE
 VALUES ARE INDICATED ON EQUIPMENT OR INSTALLATION
 INSTRUCTIONS, A CALIBRATED TORQUE TOOL MUST BE USED TO
 ACHIEVE THE INDICATED TORQUE VALUE, UNLESS THE
 EQUIPMENT
 MANUFACTURER PROVIDES AN ALTERNATIVE METHOD OF
 ACHIEVING THE REQUIRED TORQUE.
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-21 Cont ID  
Sent By mpeterso Date 2023-03-21 Time 09:36 Rev Time 0.00
Received By mpeterso Date 2023-03-15 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-14 Cont ID  
Sent By cthroop Date 2023-03-14 Time 14:26 Rev Time 0.00
Received By cthroop Date 2023-03-01 Time 10:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-24 Cont ID  
Sent By cthroop Date 2023-01-24 Time 11:19 Rev Time 0.00
Received By cthroop Date 2022-12-27 Time 15:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-03-02 Cont ID  
Sent By rwbrown Date 2023-03-02 Time 13:22 Rev Time 0.00
Received By rwbrown Date 2023-03-02 Time 13:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 08:35 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 08:34 Sent To  
Notes
2022-12-30 08:43:371ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.1 - THE DRAWING IS NON-COMPLIANT. THE
 KITCHEN AND WASHING MACHINE CANNOT CONNECT WITHIN THE
 WET VENT. ONLY BATHROOM GROUP FIXTURES ARE ALLOWED TO
 CONNECT WITHIN AND BE VENTED BY A WET VENT. ALL OTHER
 FIXTURES MUST DISCHARGE DOWNSTREAM.
  
 2. 2017 WPB AMEND 107.3.5.3 (12) - YOUR RISER ONLY
 SHOWS ONE WATER CLOSET.
  
 3. 2017 WPB AMEND 107.3.5.3 (12) - YOUR RISER DOESN'T
 MATCH THE FLOOR PLAN. NOT ONLY IS IT DRAWN DIFFERENT,
 THE RISER SHOWS A SHOWER AND PLAN SHOWS A TUB, RISER
 SHOWS ONE WATER CLOSET AND PLAN SHOWS TWO. THE RISER
 SHOULD REFLECT THE SAME AS THE FLOOR PLAN, JUST IN 3D
 VIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-22 Cont ID  
Sent By mpeterso Date 2023-03-21 Time 09:33 Rev Time 0.00
Received By mpeterso Date 2023-03-22 Time 09:52 Sent To  
Notes
2023-03-21 09:36:22CHANGED SIGNATURE REVIEW RESULT TO PASS. DRAWINGS IN
 THE SUPPORTING DOCS FOLDER HAS VERIFIABLE SIGNATURES.
 MP
  
 SIGNATURE REVIEW FAILED
  
 THE REQUIRED DIGITAL SIGNATURE OF THE EOR/AOR ARE NOT
 ON PLANS. PLEASE CORRECT AS OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-14 Cont ID  
Sent By cthroop Date 2023-03-14 Time 14:25 Rev Time 0.00
Received By cthroop Date 2023-03-14 Time 14:04 Sent To  
Notes
2023-03-14 14:25:30IN SUPPORTING DOCS FOLDER. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-24 Cont ID  
Sent By cthroop Date 2023-01-24 Time 11:01 Rev Time 0.00
Received By cthroop Date 2023-01-24 Time 06:23 Sent To  
Notes
2023-01-24 11:02:231ST SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  