Plan Review Details - Permit 22120391
Plan Review Stops For Permit 22120391
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-20 Cont ID  
Sent By jgomez Date 2023-01-20 Time 11:51 Rev Time 0.00
Received By jgomez Date 2023-01-20 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-18 Cont ID  
Sent By jgomez Date 2023-01-18 Time 18:21 Rev Time 0.00
Received By jgomez Date 2023-01-18 Time 17:51 Sent To  
Notes
2023-01-18 18:22:08RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120391
 600 S DIXIE HWY # 504
  
  
 1-FLOORING SOUND INSULATION MATERIAL:
  
 ORIGINAL COMMENT:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 UNDERLAYMENT FLAME SPREAD INDEX AND SMOKE DEVELOPED
 INDEX TEST WAS NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 TEST SUBMITTED IS FOR LAMINATED WOOD OVER PROFLEX LV200
 UNDERLAYMENT. THE PERMIT APPLICATION CALLS FOR VINYL
 FLOORING. NEED TEST REPORT FOR VINYL FLOORING OVER
 PROFLEX LV200 UNDERLAYMENT.
  
 ORIGINAL COMMENT:
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 TEST SUBMITTED IS FOR LAMINATED WOOD OVER PROFLEX LV200
 UNDERLAYMENT. THE PERMIT APPLICATION CALLS FOR VINYL
 FLOORING. NEED TEST REPORT FOR VINYL FLOORING OVER
 PROFLEX LV200 UNDERLAYMENT.
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-11 Cont ID  
Sent By jgomez Date 2023-01-11 Time 18:59 Rev Time 0.00
Received By jgomez Date 2023-01-11 Time 18:59 Sent To  
Notes
2023-01-11 19:00:45RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22120391
 600 S DIXIE HWY # 504
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1-FLOORING SOUND INSULATION MATERIAL:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-19 Cont ID  
Sent By pleduc Date 2023-01-19 Time   Rev Time 0.00
Received By pleduc Date 2023-01-19 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-12-12 Cont ID  
Sent By pleduc Date 2022-12-12 Time   Rev Time 0.00
Received By pleduc Date 2022-12-12 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-20 Cont ID  
Sent By jgomez Date 2023-01-20 Time 11:51 Rev Time 0.00
Received By jgomez Date 2023-01-20 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-19 Cont ID  
Sent By jgomez Date 2023-01-19 Time 11:10 Rev Time 0.00
Received By jgomez Date 2023-01-17 Time 08:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-11 Cont ID  
Sent By jgomez Date 2023-01-11 Time 19:01 Rev Time 0.00
Received By jgomez Date 2022-12-09 Time 10:09 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-01-11 Cont ID  
Sent By jgomez Date 2023-01-11 Time 19:00 Rev Time 0.00
Received By jgomez Date 2023-01-11 Time 19:00 Sent To  
Notes
2023-01-11 19:01:15NO ARCHITECT OR ENGINEER. JG.