Plan Review Details - Permit 22120324
Plan Review Stops For Permit 22120324
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-23 Cont ID  
Sent By ppetty Date 2023-01-23 Time 12:43 Rev Time 0.00
Received By ppetty Date 2023-01-23 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-13 Cont ID  
Sent By ppetty Date 2023-01-13 Time 11:43 Rev Time 0.00
Received By ppetty Date 2023-01-10 Time 11:32 Sent To  
Notes
2023-01-13 11:43:26SEE F/D NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-20 Cont ID  
Sent By pleduc Date 2023-01-20 Time   Rev Time 0.00
Received By pleduc Date 2023-01-20 Time 10:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-01-05 Cont ID  
Sent By pleduc Date 2023-01-05 Time 14:12 Rev Time 0.00
Received By pleduc Date 2022-12-29 Time 15:28 Sent To  
Notes
2023-01-05 11:50:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE APPEARS TO BE AN INDICATION OF THE FACP BEING
 LOCATED IN THE SOUTH BUILDING.
  
 THERE DOES NOT APPEAR TO BE ANY INDICATION OF A SISTER
 PANEL NOR ANNUCIATOR PANEL AT THIS NORTH BUILDING.
  
 PER NFPA 101, CH 30
  
 30.3.4.3.2 ANNUNCIATION, AND ANNUNCIATION ZONING, IN
 ACCORDANCE WITH
 9.6.7 SHALL BE PROVIDED, UNLESS THE BUILDING COMPLIES
 WITH EITHER
 30.3.4.3.3 OR 30.3.4.3.4. ANNUNCIATION SHALL BE
 PROVIDED AT A LOCATION
 READILY ACCESSIBLE FROM THE PRIMARY POINT OF ENTRY FOR
 EMERGENCY
 RESPONSE PERSONNEL
  
 9.6.7.7 WHERE THE SYSTEM SERVES MORE THAN ONE BUILDING,
 EACH BUILDING
 SHALL BE ANNUNCIATED SEPARATELY
  
 PLEASE REVIEW AND CORRECT. COORDINATE THE PANEL THROUGH
 THE OFFICE OF THE FIRE MARSHAL BY EMAIL NOTED BELOW
 THRU PDF WITH PROPOSED LOCATIONS.
  
  
  
 2) THERE APPEARS TO BE AN INDICATION OF THE FACP BEING
 LOCATED IN THE SOUTH BUILDING.
  
 THE CALCULATIONS DO NOT APPEAR TO INDICATE THE SIZE AND
 LENGHT OF WIRE FROM THE SOUTH BLDG.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATION AND
 CONFIRMATION AND OR CORRECT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-23 Cont ID  
Sent By ppetty Date 2023-01-23 Time 12:43 Rev Time 0.00
Received By ppetty Date 2023-01-19 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-13 Cont ID  
Sent By ppetty Date 2023-01-13 Time 11:43 Rev Time 0.00
Received By ppetty Date 2022-12-28 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By medwards Date 2023-01-05 Time 11:14 Rev Time 0.00
Received By medwards Date 2023-01-05 Time 11:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By medwards Date 2023-01-05 Time 11:14 Rev Time 0.00
Received By medwards Date 2023-01-05 Time 11:14 Sent To  
Notes
***NONE***