Plan Review Details - Permit 22120277
Plan Review Stops For Permit 22120277
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-27 Cont ID  
Sent By rmcdouga Date 2023-04-27 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2023-04-27 Time 16:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By rmcdouga Date 2023-01-31 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2023-01-31 Time 16:06 Sent To  
Notes
2023-01-31 16:15:51PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET 04.007-ALS1.106, THE EGRESS PATH OF TRAVEL
 IS SHOWN GOING THROUGH A WALL WHERE THE DOOR TO THE
 FIRE LOBBY WAS RELOCATED. PLEASE CORRECT. FBC 1017

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By jleahy Date 2023-05-03 Time 13:03 Rev Time 0.00
Received By jleahy Date 2023-05-03 Time 12:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By jleahy Date 2023-01-19 Time 09:43 Rev Time 0.00
Received By jleahy Date 2023-01-18 Time 15:37 Sent To  
Notes
2023-01-19 09:53:51FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 E.001, E.616, E.617, AND E.702 ARE NOT INCLUDED IN THE
 SUBMITAL???

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-18 Cont ID  
Sent By pleduc Date 2023-04-18 Time   Rev Time 0.00
Received By pleduc Date 2023-04-18 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-01-05 Cont ID  
Sent By pleduc Date 2023-01-05 Time   Rev Time 0.00
Received By pleduc Date 2022-12-29 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-28 Cont ID  
Sent By hmoser Date 2023-06-28 Time 08:20 Rev Time 0.00
Received By hmoser Date 2023-06-01 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-03 Cont ID  
Sent By jleahy Date 2023-05-03 Time 14:14 Rev Time 0.00
Received By jleahy Date 2023-04-13 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-03 Cont ID  
Sent By aoliver Date 2023-02-03 Time 08:51 Rev Time 0.00
Received By aoliver Date 2022-12-28 Time 16:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-06-28 Cont ID  
Sent By hmoser Date 2023-06-28 Time 08:13 Rev Time 0.00
Received By hmoser Date 2023-06-28 Time 08:13 Sent To  
Notes
2023-06-28 08:19:42PASS PROVISO
 KITCHEN HOODS, WALK IN COOLERS AND FEEZERS
 ALL REFRIGERATION REQUIRE SEPARATE APPLICATION PLAN AND
 PERMIT
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 07:41 Rev Time 0.00
Received By medwards Date 2023-05-01 Time 07:40 Sent To  
Notes
2023-05-01 07:41:271ST REVIEW FMC
 PERMIT: 22120277
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M.208B: ADD A NOTE TO THE MECHANICAL DRAWINGS
 STATING THAT THE KITCHEN HOODS AND ALL DUCTS ASSOCIATED
 WILL REQUIRE A SEPARATE PERMIT APPLICATION INCLUDING
 SUBMITTAL AND A SEPARATE REVIEW AS IT WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
 2) I DO NOT SEE THE EF THAT IS EXHAUSTING THE NEW MENS
 AND WOMENS RESTROOMS SHOWN ON SHEET M.208C. PLEASE
 INCLUDE IT ON SHEET M.602. FBC 107.3.5
 3) PLEASE SHOW EF-52 AND EF-55 ON SHEET M.602 AS WELL.
 FBC 107.3.5
 4) SHEET M.606: OUTDOOR AIR FOR AHU-10A AND 10B ???
 TENNIS COURT SPORT AND AMUSEMENT / ARENA- PLAY AREA:
 THE OUTDOOR AIR SHOULD BE CALCULATED WITH AN OCCUPANT
 DENSITY OF 7 ALSO WITH PEOPLE OUTDOOR AIR RATE OF 20
 CFM. THE AREA OUTDOOR AIRFLOW RATE SHOULD BE CALCULATED
 WITH .18 CFM PER SQ.FT. THIS WOULD GIVE YOU 94 PEOPLE X
 20 = 1880; THE AREA OUTDOOR AIRFLOW RATE WOULD BE-
 13404 X .18 = 2413; 1880 + 2413 = 4293 CFMS OF REQUIRED
 OUTDOOR AIR FOR THE SPACE. WE ARE CURRENTLY IN THE 2020
 7TH EDITION OF THE FLORIDA MECHANICAL CODE. PLEASE
 CORRECT THE NAME OF THE OUTDOOR AIR SHEET. FMC TABLE
 403.3.1.1
 5) PROVIDE AN EQUIPMENT LIST FOR THE NEW LEVEL 08 EVENT
 KITCHEN. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-10 Cont ID  
Sent By medwards Date 2023-01-10 Time 06:39 Rev Time 0.00
Received By medwards Date 2023-01-09 Time 17:11 Sent To  
Notes
2023-01-10 06:40:071ST REVIEW FMC
 PERMIT: 22120277
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FOLLOWING SHEETS WERE NOT SUBMITTED BUT ARE
 LISTED AS PART OF THIS REVISION. PLEASE PROVIDE THESE
 DRAWINGS FOR REVIEW. M.208A; M.208B; M.209; M.602;
 M.603; M.604. FBC 107.3.5
  
 2) SHEET M.208C; PLEASE IDENTIFY THE NEW VESTIBULE 0843
 AND THE NEW ADDED SUPPLY DUCT. FBC 107.3.5
  
 3) SHEET M.208D: THE SCHEDULE SHEETS WERE NOT SUBMITTED
 FOR ME TO CHECK AC 7B CFM TO SEE IF A SMOKE DETECTOR IS
 REQUIRED, PLEASE VERIFY IF IT IS OR NOT. FMC 606
  
 4) PROVIDE THE REVIEWER WITH A RISER DRAWING FOR THE
 CHANGES TO M.209, M.210, M.211. FBC 107.3.5
  
 5) SHEET M.227: THE NEW AIR BALANCE CHART SHOULD ALSO
 BE INCLUDED ON THE HOOD DETAIL SHEET FOR THE BANQUET
 KITCHEN. PLEASE MAKE THE CHANGE AND SUBMIT THAT DRAWING
 AS WELL. FBC 107.3.5
  
 6) SHEET M.227: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR THE AREAS LISTED IN THE NEWLY ADDED
 AIR BALANCE REPORT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-06-07 Cont ID  
Sent By ccole Date 2023-06-07 Time 15:22 Rev Time 0.00
Received By ccole Date 2023-06-07 Time 14:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-21 Cont ID  
Sent By ccole Date 2023-04-21 Time 11:57 Rev Time 0.00
Received By ccole Date 2023-04-21 Time 07:48 Sent To  
Notes
2023-04-21 12:02:312ND REVIEW FBC-2020 PLUMBING
 PERMIT-22120277
 4/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P.106A, P.106B, P.106C, P.106D, P.107A,
 P.107B, P.107C, P.107D, P.108A, P.108C SHOW SIDEWALL
 ROOF DRAINS AND IN SOME CASES DRAIN PIPES PENETRATING
 STAIRWAY WALLS. PLEASE REFER TO SEC. 1023.5 FBC B. AND
 NOTE PENETRATIONS INTO FIRE-RATED INTERIOR EXIT
 STAIRWAYS ARE PROHIBITED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-30 Cont ID  
Sent By rwbrown Date 2022-12-30 Time 11:51 Rev Time 0.00
Received By rwbrown Date 2022-12-30 Time 11:51 Sent To  
Notes
2022-12-30 13:12:441ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - PER YOUR NARRATIVE, PAGES
 P-106A, P-106B, P-106C. P-107A, P-107B, P-107C, P-107D,
 AND P-220 ARE MISSING. PLEASE CLARIFY.
  
 2. 2017 WPB AMENDS 107.2.1 - PER YOUR NARRATIVE, PAGES
 P-105D HAVE BEEN SUBMITTED AND HAVE NO NARRATION.
 PLEASE CLARIFY.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-07 Cont ID  
Sent By ccole Date 2023-06-07 Time 15:22 Rev Time 0.00
Received By ccole Date 2023-06-07 Time 15:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-03 Cont ID  
Sent By jleahy Date 2023-05-03 Time 14:14 Rev Time 0.00
Received By jleahy Date 2023-05-03 Time 14:14 Sent To  
Notes
2023-04-21 12:03:54PLUMBING PLANS PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-31 Cont ID  
Sent By jleahy Date 2023-01-19 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2023-01-19 Time 09:44 Sent To  
Notes
2023-05-01 07:42:08MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-01-31 16:06:25THE STRUCTURAL PLANS ARE SELF-CERTIFIED BY THE
 ENGINEER. THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 REQUIRES AN APPROVED THIRD PARTY AGENCY TO CERTIFY AN
 ENGINEER'S DIGITAL SIGNATURE. FS 471
2023-01-10 06:40:44MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 1 Status P Date 2023-02-02 Cont ID  
Sent By ckimmerl Date 2023-02-02 Time 08:57 Rev Time 0.00
Received By ckimmerl Date 2023-02-02 Time 08:57 Sent To  
Notes
***NONE***