| Plan Review Stops For Permit 22120277 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-04-27 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-04-27 |
Time |
16:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-01-31 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-01-31 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2023-01-31 16:15:51 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEET 04.007-ALS1.106, THE EGRESS PATH OF TRAVEL | | | IS SHOWN GOING THROUGH A WALL WHERE THE DOOR TO THE | | | FIRE LOBBY WAS RELOCATED. PLEASE CORRECT. FBC 1017 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-05-03 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-05-03 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-19 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-01-18 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2023-01-19 09:53:51 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | E.001, E.616, E.617, AND E.702 ARE NOT INCLUDED IN THE | | | SUBMITAL??? |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2023-04-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-04-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-04-18 |
Time |
12:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-01-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-12-29 |
Time |
15:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-06-28 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-06-01 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-05-03 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-04-13 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-03 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-03 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-12-28 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-06-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2023-06-28 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2023-06-28 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2023-06-28 08:19:42 | PASS PROVISO | | | KITCHEN HOODS, WALK IN COOLERS AND FEEZERS | | | ALL REFRIGERATION REQUIRE SEPARATE APPLICATION PLAN AND | | | PERMIT | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-05-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-01 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-01 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2023-05-01 07:41:27 | 1ST REVIEW FMC | | | PERMIT: 22120277 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M.208B: ADD A NOTE TO THE MECHANICAL DRAWINGS | | | STATING THAT THE KITCHEN HOODS AND ALL DUCTS ASSOCIATED | | | WILL REQUIRE A SEPARATE PERMIT APPLICATION INCLUDING | | | SUBMITTAL AND A SEPARATE REVIEW AS IT WILL NOT BE | | | REVIEWED UNDER THIS PERMIT. | | | 2) I DO NOT SEE THE EF THAT IS EXHAUSTING THE NEW MENS | | | AND WOMENS RESTROOMS SHOWN ON SHEET M.208C. PLEASE | | | INCLUDE IT ON SHEET M.602. FBC 107.3.5 | | | 3) PLEASE SHOW EF-52 AND EF-55 ON SHEET M.602 AS WELL. | | | FBC 107.3.5 | | | 4) SHEET M.606: OUTDOOR AIR FOR AHU-10A AND 10B ??? | | | TENNIS COURT SPORT AND AMUSEMENT / ARENA- PLAY AREA: | | | THE OUTDOOR AIR SHOULD BE CALCULATED WITH AN OCCUPANT | | | DENSITY OF 7 ALSO WITH PEOPLE OUTDOOR AIR RATE OF 20 | | | CFM. THE AREA OUTDOOR AIRFLOW RATE SHOULD BE CALCULATED | | | WITH .18 CFM PER SQ.FT. THIS WOULD GIVE YOU 94 PEOPLE X | | | 20 = 1880; THE AREA OUTDOOR AIRFLOW RATE WOULD BE- | | | 13404 X .18 = 2413; 1880 + 2413 = 4293 CFMS OF REQUIRED | | | OUTDOOR AIR FOR THE SPACE. WE ARE CURRENTLY IN THE 2020 | | | 7TH EDITION OF THE FLORIDA MECHANICAL CODE. PLEASE | | | CORRECT THE NAME OF THE OUTDOOR AIR SHEET. FMC TABLE | | | 403.3.1.1 | | | 5) PROVIDE AN EQUIPMENT LIST FOR THE NEW LEVEL 08 EVENT | | | KITCHEN. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-10 |
Time |
06:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-09 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2023-01-10 06:40:07 | 1ST REVIEW FMC | | | PERMIT: 22120277 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE FOLLOWING SHEETS WERE NOT SUBMITTED BUT ARE | | | LISTED AS PART OF THIS REVISION. PLEASE PROVIDE THESE | | | DRAWINGS FOR REVIEW. M.208A; M.208B; M.209; M.602; | | | M.603; M.604. FBC 107.3.5 | | | | | | 2) SHEET M.208C; PLEASE IDENTIFY THE NEW VESTIBULE 0843 | | | AND THE NEW ADDED SUPPLY DUCT. FBC 107.3.5 | | | | | | 3) SHEET M.208D: THE SCHEDULE SHEETS WERE NOT SUBMITTED | | | FOR ME TO CHECK AC 7B CFM TO SEE IF A SMOKE DETECTOR IS | | | REQUIRED, PLEASE VERIFY IF IT IS OR NOT. FMC 606 | | | | | | 4) PROVIDE THE REVIEWER WITH A RISER DRAWING FOR THE | | | CHANGES TO M.209, M.210, M.211. FBC 107.3.5 | | | | | | 5) SHEET M.227: THE NEW AIR BALANCE CHART SHOULD ALSO | | | BE INCLUDED ON THE HOOD DETAIL SHEET FOR THE BANQUET | | | KITCHEN. PLEASE MAKE THE CHANGE AND SUBMIT THAT DRAWING | | | AS WELL. FBC 107.3.5 | | | | | | 6) SHEET M.227: PLEASE PROVIDE THE OUTDOOR AIR | | | CALCULATIONS FOR THE AREAS LISTED IN THE NEWLY ADDED | | | AIR BALANCE REPORT. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-07 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-07 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2023-04-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-04-21 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-04-21 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2023-04-21 12:02:31 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT-22120277 | | | 4/21/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P.106A, P.106B, P.106C, P.106D, P.107A, | | | P.107B, P.107C, P.107D, P.108A, P.108C SHOW SIDEWALL | | | ROOF DRAINS AND IN SOME CASES DRAIN PIPES PENETRATING | | | STAIRWAY WALLS. PLEASE REFER TO SEC. 1023.5 FBC B. AND | | | NOTE PENETRATIONS INTO FIRE-RATED INTERIOR EXIT | | | STAIRWAYS ARE PROHIBITED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS ST. | | | WEST PALM BEACH, FL. 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-30 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-12-30 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2022-12-30 13:12:44 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - PER YOUR NARRATIVE, PAGES | | | P-106A, P-106B, P-106C. P-107A, P-107B, P-107C, P-107D, | | | AND P-220 ARE MISSING. PLEASE CLARIFY. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - PER YOUR NARRATIVE, PAGES | | | P-105D HAVE BEEN SUBMITTED AND HAVE NO NARRATION. | | | PLEASE CLARIFY. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-06-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-06-07 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-06-07 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-05-03 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-05-03 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2023-04-21 12:03:54 | PLUMBING PLANS PASSED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-31 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-01-19 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-01-19 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2023-05-01 07:42:08 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | 2023-01-31 16:06:25 | THE STRUCTURAL PLANS ARE SELF-CERTIFIED BY THE | | | ENGINEER. THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS | | | REQUIRES AN APPROVED THIRD PARTY AGENCY TO CERTIFY AN | | | ENGINEER'S DIGITAL SIGNATURE. FS 471 | | 2023-01-10 06:40:44 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2023-02-02 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2023-02-02 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|