Plan Review Details - Permit 22120266
Plan Review Stops For Permit 22120266
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-06-09 Cont ID  
Sent By lbond Date 2023-06-09 Time 10:03 Rev Time 0.00
Received By lbond Date 2023-06-09 Time 10:03 Sent To  
Notes
2023-06-09 11:35:03PROVISO SHEET A-301
  
 IBC 1030.2
  
 PLEASE PROVIDE MEAN OF EGRESS FOR SUN ROOM AS THIS ROOM
 HAS A WALK IN CLOSET AND IN SUITE BATHROOM.
 THIS MEETS THE DEFENITION OF A "BEDROOM"
  
 YOU SAY YOU ARE USING AS SUNROOM, BUT NEEDS TO FUNCTION
 FOR WORST CASE.
  
 IT SHOULD HAVE EMERGENCY ESCAPE OPENING.
 PLEASE UPDATE SIGNED AND SEALED SHEET AND PROVIDE NOA
 OF FBC FOR EGRESS WINDOW. MUST BE PROVIDED AT
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS,
 YOU CAN REACH ME AT
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-05 Cont ID  
Sent By lbond Date 2023-05-05 Time 08:44 Rev Time 0.00
Received By lbond Date 2023-05-05 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By lbond Date 2023-03-06 Time 11:18 Rev Time 0.00
Received By lbond Date 2023-03-06 Time 11:18 Sent To  
Notes
2023-03-06 11:21:19BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 22120266
  
 REVIEWED: MARCH 6, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 AS PER SECTION 107.2.1
 PROVIDE SUPPORTING DOCUMENT FOR NOA OR FPA APPROVED FOR
 NEW EGRESS WINDOWS TYPE A
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-06-13 Cont ID  
Sent By mpeterso Date 2023-06-13 Time 11:05 Rev Time 0.00
Received By mpeterso Date 2023-06-13 Time 11:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-05-10 Cont ID  
Sent By mpeterso Date 2023-05-10 Time 13:25 Rev Time 0.00
Received By mpeterso Date 2023-05-10 Time 13:25 Sent To  
Notes
2023-05-10 13:27:54ELECTRIC REVIEW FAILED
  
 1) OVERCURRENT PROTECTION IN ELECTRIC PANEL A FOR
 ELECTRIC PANEL B IS DETAILED AS 100 AMP. RISER DIAGRAM
 DETAILS ELECTRIC PANEL B AS 200 AMP. IT IS THE
 EXPERIENCE OF THIS REVIEWER THAT A 200 AMP BREAKER IS
 OVER THE MAXIMUM ALLOWED BY ELECTRIC PANEL MANUFACTURES
 AND THE ONLY CONFIGURATION I AM AWARE OF IS A 200 AMP
 FEED THROUGH PANEL FEEDING A 200 AMP SUB PANEL.
 UTILIZING AN ENGINEER OR QUALIFIED ELECTRICAL
 CONTRACTOR FAMILIAR WITH PREPARING RISER DIAGRAMS IS
 RECOMMENDED TO PREPARE A RISER DIAGRAM THAT WILL COMPLY
 WITH NEC CODES AND MANUFACTURER SPECIFICATIONS. NEC
 215.5
  
 2) PANEL SCHEDULES DETAIL 2 AIR HANDLERS WITH 60 AMP
 OVERCURRENT PROTECTION. IT IS THE EXPERIENCE OF THIS
 REVIEWER THAT AIR HANDLERS WITH THIS SIZE OCP CONTAIN A
 10KW HEAT STRIP NOT A 7.5 AS DETAILED IN LOAD
 CALCULATIONS SUBMITTED. PLEASE PROVIDE THE
 SPECIFICATIONS FOR BOTH AIR HANDLERS AND DETAIL THE
 CORRECT SIZE OCP AS APPLICABLE
  
 3) PANEL SCHEDULES DETAIL 2 TANKLESS WATER HEATERS WITH
 40 AMP OVERCURRENT AND 50 AMP OCP PROTECTION. THE PANEL
 SCHEDULES SUGGEST A KW RATING OF THESE WATER HEATERS AS
 9600 AND 12000 KW. THE LOAD CALCULATION DETAILS THESE
 WATER HEATERS AS HAVING A 24,000 KW AND 18,000 KW
 RATING AS DETAILED IN LOAD CALCULATIONS SUBMITTED.
 PLEASE PROVIDE THE SPECIFICATIONS FOR BOTH TANKLESS
 WATER HEATERS AND DETAIL THE CORRECT SIZE OCP AS
 APPLICABLE.
  
 4) BOTH ELECTRIC PANELS ARE STILL DETAILED IN CLOSETS
 AND NOT IN COMPLIANCE WITH NEC 240.24 (D) PLEASE
 RELOCATE TO A CODE COMPLIANT LOCATION
 .
 5) LOAD CALCULATION PROVIDED IN SUBMITTAL IS STILL
 INCORRECT. LOADS LISTED APPEAR TO BE INCORRECT, SEE
 ABOVE, AND DEMAND FACTORS ARE STILL BEING USED FOR SUB
 PANEL B LOAD IN ELECTRIC PANEL A CALCULATION. PLEASE
 SUBMIT A CALCULATION IN COMPLIANCE WITH EITHER NEC
 220.40, STANDARD CALCULATION, OR NEC 220.80 OPTIONAL
 CALCULATION. AS STATED ABOVE UTILIZING AN ENGINEER OR
 QUALIFIED ELECTRICAL CONTRACTOR FAMILIAR WITH THESE
 CALCULATIONS IS RECOMMENDED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By mpeterso Date 2023-03-03 Time 16:30 Rev Time 0.00
Received By mpeterso Date 2023-03-02 Time 16:04 Sent To  
Notes
2023-03-03 15:50:23ELECTRIC REVIEW FAILED
  
 1) PROVIDE A CORRECT ELECTRIC LOAD CALCULATION FOR
 PANEL A. THE ELECTRIC LOAD CALCULATION SUBMITTED
 INCORRECTLY LISTS THE, CALCULATED DEMAND LOAD, FROM
 PANEL B INSTEAD OF THE ACTUAL ELECTRIC LOADS. THE
 CORRECT CALCULATION WILL CALCULATE ALL LOADS FOR THE
 MAIN SERVICE FEEDERS FROM THE METER TO PANEL A,
 ACCORDING TO NEC 220.40, STANDARD CALCULATION OR
 220.80, OPTIONAL CALCULATION
  
 2) PLEASE INDICATE ON ELECTRICAL FLOOR PLAN THE
 REQUIRED ELECTRICAL EQUIPMENT WORKING DEPTH OF 3??? FOR
 ALL AIR CONDITIONING CONDENSER DISCONNECTS AS REQUIRED
 PER NEC 110.26
  
 3) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT
 THE FRONT AND SIDE ENTRY OF THE HOUSE AS PER NEC
 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. BALCONIES,
 DECKS, AND PORCHES THAT ARE ATTACHED TO THE DWELLING
 UNIT AND ARE ACCESSIBLE FROM INSIDE THE DWELLING UNIT
 SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE
 FROM THE BALCONY, DECK, OR PORCH.
  
 4) PLEASE NOTE PANEL B IS LOCATED IN A STORAGE ROOM.
 ELECTRICAL INSPECTORS MAY CONSIDER THIS ROOM AS NOT IN
 COMPLIANCE WITH NEC 240.24 (D) NOT IN VICINITY OF
 EASILY IGNITABLE MATERIAL. OVERCURRENT DEVICES SHALL
 NOT BE LOCATED IN THE VICINITY OF EASILY IGNITABLE
 MATERIAL, SUCH AS IN CLOTHES CLOSETS. A CHANGE OF
 LOCATION SHOULD BE CONSIDERED OR A NOTE STATING
 COMPLIANCE WITH THE ABOVE NEC CODE
  
 5) PLEASE CHANGE THE ARC FAULT PROTECTION NOTE TO ONE
 STATING COMPLIANCE WITH THE 2017 NEC CODE 210.12 AS
 OUTLINED BELOW. ALL 120-VOLT, SINGLE PHASE, 15 AND 20
 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING
 UNIT KITCHENS, LAUNDRY ROOMS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. NEC 210.12; FBC RE3902.16
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-06-07 Cont ID  
Sent By fmittner Date 2023-06-07 Time 07:54 Rev Time 0.00
Received By fmittner Date 2023-06-07 Time 07:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-03-28 Cont ID  
Sent By fmittner Date 2023-03-28 Time 14:42 Rev Time 0.00
Received By fmittner Date 2023-03-28 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-20 Cont ID  
Sent By cmontell Date 2023-06-20 Time 14:04 Rev Time 0.00
Received By cmontell Date 2023-06-20 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-07 Cont ID  
Sent By lmarchan Date 2023-06-07 Time 16:17 Rev Time 0.00
Received By lmarchan Date 2023-05-04 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-29 Cont ID  
Sent By aoliver Date 2023-03-29 Time 08:23 Rev Time 0.00
Received By aoliver Date 2023-02-22 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-06-20 Cont ID  
Sent By cmontell Date 2023-06-20 Time 14:03 Rev Time 0.00
Received By cmontell Date 2023-06-20 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-05-08 Cont ID  
Sent By medwards Date 2023-05-08 Time 11:09 Rev Time 0.00
Received By medwards Date 2023-05-08 Time 11:09 Sent To  
Notes
2023-05-08 11:12:06APPROVED ME
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-02-23 Cont ID  
Sent By medwards Date 2023-02-23 Time 17:17 Rev Time 0.00
Received By medwards Date 2023-02-23 Time 17:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-06-09 Cont ID  
Sent By rwbrown Date 2023-06-09 Time 09:20 Rev Time 0.00
Received By rwbrown Date 2023-06-09 Time 09:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-05-05 Cont ID  
Sent By rwbrown Date 2023-05-05 Time 07:36 Rev Time 0.00
Received By rwbrown Date 2023-05-05 Time 07:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-02-23 Cont ID  
Sent By rwbrown Date 2023-02-23 Time 10:19 Rev Time 0.00
Received By rwbrown Date 2023-02-23 Time 10:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-09 Cont ID  
Sent By lbond Date 2023-06-09 Time 10:03 Rev Time 0.00
Received By lbond Date 2023-06-09 Time 10:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-05 Cont ID  
Sent By lbond Date 2023-05-05 Time 08:44 Rev Time 0.00
Received By lbond Date 2023-05-05 Time 08:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-03 Cont ID  
Sent By lbond Date 2023-03-03 Time 14:21 Rev Time 0.00
Received By lbond Date 2023-03-03 Time 14:21 Sent To  
Notes
2023-03-03 14:22:19ARCHITECT SIGNATURE APPROVED
2023-02-23 17:18:31MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-06-07 Cont ID  
Sent By fmittner Date 2023-06-07 Time 07:54 Rev Time 0.00
Received By fmittner Date 2023-06-07 Time 07:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-28 Cont ID  
Sent By fmittner Date 2023-03-28 Time 14:43 Rev Time 0.00
Received By fmittner Date 2023-03-28 Time 14:43 Sent To  
Notes
2023-03-28 14:44:27VALUATION OF WORK REQUIRES SUBMITTAL OF SEPERATE
 LANDSCAPE PERMIT.
  
 DUE TO SITE MODIFICATIONS OF PORCH , WALKWAYS ETC,
 PLEASE PROVIDE A SITE PLAN.