| Plan Review Stops For Permit 22120266 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-06-09 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-06-09 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-06-09 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2023-06-09 11:35:03 | PROVISO SHEET A-301 | | | | | | IBC 1030.2 | | | | | | PLEASE PROVIDE MEAN OF EGRESS FOR SUN ROOM AS THIS ROOM | | | HAS A WALK IN CLOSET AND IN SUITE BATHROOM. | | | THIS MEETS THE DEFENITION OF A "BEDROOM" | | | | | | YOU SAY YOU ARE USING AS SUNROOM, BUT NEEDS TO FUNCTION | | | FOR WORST CASE. | | | | | | IT SHOULD HAVE EMERGENCY ESCAPE OPENING. | | | PLEASE UPDATE SIGNED AND SEALED SHEET AND PROVIDE NOA | | | OF FBC FOR EGRESS WINDOW. MUST BE PROVIDED AT | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, | | | YOU CAN REACH ME AT | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-05-05 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-05-05 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-06 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-06 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2023-03-06 11:21:19 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 22120266 | | | | | | REVIEWED: MARCH 6, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | AS PER SECTION 107.2.1 | | | PROVIDE SUPPORTING DOCUMENT FOR NOA OR FPA APPROVED FOR | | | NEW EGRESS WINDOWS TYPE A | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-06-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-06-13 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-06-13 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-05-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-05-10 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-05-10 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2023-05-10 13:27:54 | ELECTRIC REVIEW FAILED | | | | | | 1) OVERCURRENT PROTECTION IN ELECTRIC PANEL A FOR | | | ELECTRIC PANEL B IS DETAILED AS 100 AMP. RISER DIAGRAM | | | DETAILS ELECTRIC PANEL B AS 200 AMP. IT IS THE | | | EXPERIENCE OF THIS REVIEWER THAT A 200 AMP BREAKER IS | | | OVER THE MAXIMUM ALLOWED BY ELECTRIC PANEL MANUFACTURES | | | AND THE ONLY CONFIGURATION I AM AWARE OF IS A 200 AMP | | | FEED THROUGH PANEL FEEDING A 200 AMP SUB PANEL. | | | UTILIZING AN ENGINEER OR QUALIFIED ELECTRICAL | | | CONTRACTOR FAMILIAR WITH PREPARING RISER DIAGRAMS IS | | | RECOMMENDED TO PREPARE A RISER DIAGRAM THAT WILL COMPLY | | | WITH NEC CODES AND MANUFACTURER SPECIFICATIONS. NEC | | | 215.5 | | | | | | 2) PANEL SCHEDULES DETAIL 2 AIR HANDLERS WITH 60 AMP | | | OVERCURRENT PROTECTION. IT IS THE EXPERIENCE OF THIS | | | REVIEWER THAT AIR HANDLERS WITH THIS SIZE OCP CONTAIN A | | | 10KW HEAT STRIP NOT A 7.5 AS DETAILED IN LOAD | | | CALCULATIONS SUBMITTED. PLEASE PROVIDE THE | | | SPECIFICATIONS FOR BOTH AIR HANDLERS AND DETAIL THE | | | CORRECT SIZE OCP AS APPLICABLE | | | | | | 3) PANEL SCHEDULES DETAIL 2 TANKLESS WATER HEATERS WITH | | | 40 AMP OVERCURRENT AND 50 AMP OCP PROTECTION. THE PANEL | | | SCHEDULES SUGGEST A KW RATING OF THESE WATER HEATERS AS | | | 9600 AND 12000 KW. THE LOAD CALCULATION DETAILS THESE | | | WATER HEATERS AS HAVING A 24,000 KW AND 18,000 KW | | | RATING AS DETAILED IN LOAD CALCULATIONS SUBMITTED. | | | PLEASE PROVIDE THE SPECIFICATIONS FOR BOTH TANKLESS | | | WATER HEATERS AND DETAIL THE CORRECT SIZE OCP AS | | | APPLICABLE. | | | | | | 4) BOTH ELECTRIC PANELS ARE STILL DETAILED IN CLOSETS | | | AND NOT IN COMPLIANCE WITH NEC 240.24 (D) PLEASE | | | RELOCATE TO A CODE COMPLIANT LOCATION | | | . | | | 5) LOAD CALCULATION PROVIDED IN SUBMITTAL IS STILL | | | INCORRECT. LOADS LISTED APPEAR TO BE INCORRECT, SEE | | | ABOVE, AND DEMAND FACTORS ARE STILL BEING USED FOR SUB | | | PANEL B LOAD IN ELECTRIC PANEL A CALCULATION. PLEASE | | | SUBMIT A CALCULATION IN COMPLIANCE WITH EITHER NEC | | | 220.40, STANDARD CALCULATION, OR NEC 220.80 OPTIONAL | | | CALCULATION. AS STATED ABOVE UTILIZING AN ENGINEER OR | | | QUALIFIED ELECTRICAL CONTRACTOR FAMILIAR WITH THESE | | | CALCULATIONS IS RECOMMENDED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-03 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-02 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2023-03-03 15:50:23 | ELECTRIC REVIEW FAILED | | | | | | 1) PROVIDE A CORRECT ELECTRIC LOAD CALCULATION FOR | | | PANEL A. THE ELECTRIC LOAD CALCULATION SUBMITTED | | | INCORRECTLY LISTS THE, CALCULATED DEMAND LOAD, FROM | | | PANEL B INSTEAD OF THE ACTUAL ELECTRIC LOADS. THE | | | CORRECT CALCULATION WILL CALCULATE ALL LOADS FOR THE | | | MAIN SERVICE FEEDERS FROM THE METER TO PANEL A, | | | ACCORDING TO NEC 220.40, STANDARD CALCULATION OR | | | 220.80, OPTIONAL CALCULATION | | | | | | 2) PLEASE INDICATE ON ELECTRICAL FLOOR PLAN THE | | | REQUIRED ELECTRICAL EQUIPMENT WORKING DEPTH OF 3??? FOR | | | ALL AIR CONDITIONING CONDENSER DISCONNECTS AS REQUIRED | | | PER NEC 110.26 | | | | | | 3) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT | | | THE FRONT AND SIDE ENTRY OF THE HOUSE AS PER NEC | | | 210.52(E)(3) BALCONIES, DECKS, AND PORCHES. BALCONIES, | | | DECKS, AND PORCHES THAT ARE ATTACHED TO THE DWELLING | | | UNIT AND ARE ACCESSIBLE FROM INSIDE THE DWELLING UNIT | | | SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE | | | FROM THE BALCONY, DECK, OR PORCH. | | | | | | 4) PLEASE NOTE PANEL B IS LOCATED IN A STORAGE ROOM. | | | ELECTRICAL INSPECTORS MAY CONSIDER THIS ROOM AS NOT IN | | | COMPLIANCE WITH NEC 240.24 (D) NOT IN VICINITY OF | | | EASILY IGNITABLE MATERIAL. OVERCURRENT DEVICES SHALL | | | NOT BE LOCATED IN THE VICINITY OF EASILY IGNITABLE | | | MATERIAL, SUCH AS IN CLOTHES CLOSETS. A CHANGE OF | | | LOCATION SHOULD BE CONSIDERED OR A NOTE STATING | | | COMPLIANCE WITH THE ABOVE NEC CODE | | | | | | 5) PLEASE CHANGE THE ARC FAULT PROTECTION NOTE TO ONE | | | STATING COMPLIANCE WITH THE 2017 NEC CODE 210.12 AS | | | OUTLINED BELOW. ALL 120-VOLT, SINGLE PHASE, 15 AND 20 | | | AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING | | | UNIT KITCHENS, LAUNDRY ROOMS, FAMILY ROOMS, DINING | | | ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, | | | BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, | | | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI | | | PROTECTION. NEC 210.12; FBC RE3902.16 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-06-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-06-07 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-06-07 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-03-28 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-03-28 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-06-20 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-20 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-20 |
Time |
14:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-06-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-06-07 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-05-04 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-03-29 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-22 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-06-20 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-20 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-20 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-08 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-08 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2023-05-08 11:12:06 | APPROVED ME | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-23 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-23 |
Time |
17:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-09 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-06-09 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-06-09 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-05-05 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-05-05 |
Time |
07:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-23 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-23 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-06-09 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-06-09 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-06-09 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-05-05 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-05-05 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-05-05 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-03 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-03 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2023-03-03 14:22:19 | ARCHITECT SIGNATURE APPROVED | | 2023-02-23 17:18:31 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-06-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-06-07 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-06-07 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-03-28 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-03-28 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2023-03-28 14:44:27 | VALUATION OF WORK REQUIRES SUBMITTAL OF SEPERATE | | | LANDSCAPE PERMIT. | | | | | | DUE TO SITE MODIFICATIONS OF PORCH , WALKWAYS ETC, | | | PLEASE PROVIDE A SITE PLAN. |
|
|