Plan Review Details - Permit 22120224
Plan Review Stops For Permit 22120224
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-03-13 Cont ID  
Sent By cthroop Date 2023-03-13 Time 14:13 Rev Time 0.00
Received By cthroop Date 2023-03-13 Time 09:36 Sent To  
Notes
2023-03-13 14:18:022ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 RESPONSE NARRATIVE STATES THAT ONLY A KITCHEN WILL BE
 ADDED. PLANS STILL SHOW AN ADDITION INCLUDING A NEW
 BEDROOM. SUBMIT REVISED PLANS BASED ON THE NEW SCOPE OF
 WORK.
  
  
 1. CORRECTED
  
 2. CORRECTED
  
 3. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY
 LOCATION OF WORK.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDRY LINE SURVEY.
  
 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 5. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 6.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 WINDOWS AND SGD. (SGD PRODUCT APPROVAL NOT SUBMITTED
 FOR REVIEW)
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 7.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPEC. SHEET OF A FLUID APPLIED MEMBRANE.
 R703.4
  
 8.PROVIDE SMOKE ALARMS.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 16:58 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 15:19 Sent To  
Notes
2023-02-01 17:14:361ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: VALUE ADJUSTED TO $85,033 PER THE ICC BUILDING
 VALUATION DATA.
  
 1.PROVIDE PROJECT DATA/DESIGN PARAMETERS:
 PROJECT DATA: 1&2 FAMILY DWELLING UNIT
  OCCUPANCY CLASSIFICATION R3 SFR
  SCOPE OF WORK
 DESIGN PARAMETERS: 2020 FBC EXISTING BUILDING
  2020 FBC RESIDENTIAL
  2017 NEC
 CLASSIFICATION OF WORK: ADDITION
 BUILDING CLASSIFICATION: VB
 EXPOSURE CLASSIFICATION: (B/C/D)?
 RISK CATEGORY: II
 MEAN ROOF HEIGHT: STATE MRH ON ELEVATION PLAN PAGE.
 EXISTING UNDER AIR: 682/SF
 EXISTING COVERED: 313/SF
 NEW UNDER AIR: 512/SF
 NEW COVERED: 0/SF
 TOTALS: UNDER AIR 1194/SF
  COVERED 512/SF
  
 SITE SPECIFIC DESIGN WIND LOADS PER:
 FBC RESIDENTIAL CHPT. 3
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
 -OR-
 ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH)
  
 DESIGN WIND PRESSURES:
 WINDOWS AND DOORS ??? ZONE 4 INT. / ZONE 5 CORNER
 (POSITVE/NEGATIVE)
 ROOF ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS)
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 2.PROVIDE A COPY OF THE MOST RECENT BOUNDY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY
 LOCATION OF WORK.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDRY LINE SURVEY.
  
 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 5. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 6.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 WINDOWS AND SGD.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 7.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPEC. SHEET OF A FLUID APPLIED MEMBRANE.
 R703.4
  
 8.PROVIDE SMOKE ALARMS.
 FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-03-07 Cont ID  
Sent By mpeterso Date 2023-03-07 Time 15:21 Rev Time 0.00
Received By mpeterso Date 2023-03-07 Time 15:21 Sent To  
Notes
2023-03-07 15:27:112ND ELECTRIC REVIEW FAILED
  
 PREVIOUS COMMENTS NOT ADDRESSED. IN ADDITION , IT DOES
 APPEAR NEW MINI SPLIT AIR CONDITIONERS WILL BE ADDED.
 PLEASE SHOW ADDITIONAL WIRING TO BE ADDED FOR THESE
 MINI SPLITS. FBC 107.2
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By mpeterso Date 2023-01-23 Time 13:08 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 12:46 Sent To  
Notes
2023-01-23 13:10:23ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL COMPLIANCE WITH NEC 110.26 FOR
 ELECTRIC PANEL WORKING SPACE.
 2) PLEASE DETAIL ALL SMOKE/CARBON ALARMS AS REQUIRED
 FBC R314.3
 3) PLEASE DETAIL THE REQUIRED KITCHEN ISLAND
 RECEPTACLE. NES 210.52
 4) PLEASE DETAIL LOCATION OF EXISTING METER ON ELECTRIC
 FLOOR PLAN. FBC 107.2
 5) SEE SIGNATURE REVIEW
 6) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-13 Cont ID  
Sent By cthroop Date 2023-03-13 Time 14:19 Rev Time 0.00
Received By cthroop Date 2023-02-21 Time 22:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 17:14 Rev Time 0.00
Received By cthroop Date 2023-01-11 Time 06:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 15:29 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 15:19 Sent To  
Notes
2023-02-01 15:30:06IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 09:50 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 09:45 Sent To  
Notes
2023-02-27 09:48:07THIS NEW ADDITION WILL NEED TO MEET THE REQUIREMENTS OF
 THE ENERGY CODE. IF THE EXISTING MECHANICAL SYSTEM IS
 TO BE USED TO CONDITION THE NEW ADDITION A MECHANICAL
 EQUIPMENT SIZING CALCULATION SHALL BE PROVIDED. A
 MECHANICAL DRAWING SHALL BE PROVIDED SHOWING THE DUCT
 CONNECT, SIZE AND CFM'S TO THE NEW ADDITION.
 PROVIDE THE DOCUMENTATION REQUESTED IN THE 1ST CYCLE
 MECHANICAL REVIEW.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS ADDITION.
 FEC R101.5.1.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS EDITION. FEC R403.7.1
  
 3) PROVIDE MECHANICAL DRAWING FOR THE MECHANICAL DESIGN
 FOR THIS ADDITION. FBC 107.3.5
  
 4) SHOW THE BATHROOM EXHAUST FAN, DUCTWORK AND
 TERMINATION LOCATION. FRC R303.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-01-17 Cont ID  
Sent By medwards Date 2023-01-17 Time 11:06 Rev Time 0.00
Received By medwards Date 2023-01-17 Time 11:06 Sent To  
Notes
2023-01-17 11:06:431ST REVIEW FMC
 PERMIT: 22120224
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS ADDITION.
 FEC R101.5.1.1.1
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS EDITION. FEC R403.7.1
  
 3) PROVIDE MECHANICAL DRAWING FOR THE MECHANICAL DESIGN
 FOR THIS ADDITION. FBC 107.3.5
  
 4) SHOW THE BATHROOM EXHAUST FAN, DUCTWORK AND
 TERMINATION LOCATION. FRC R303.3
  
 5) PROVIDE THE CONDENSING UNIT TIE DOWN METHOD. FRC
 M1307.2
  
 6) PROVIDE THE CONDENSATE PIPING TERMINATION LOCATION.
 FRC M1411.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By rwbrown Date 2023-02-22 Time 06:50 Rev Time 0.00
Received By rwbrown Date 2023-02-22 Time 06:50 Sent To  
Notes
2023-02-22 06:50:39NOTE ADDED TO PLUMBING PAGE FOR FIELD INSPECTION -
 SHOWER CONNECTION ABOVE LAV CONNECTION NOT LOGICAL

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-01-17 Cont ID  
Sent By rwbrown Date 2023-01-17 Time 11:01 Rev Time 0.00
Received By rwbrown Date 2023-01-17 Time 11:01 Sent To  
Notes
2023-01-17 11:02:12NOTE ADDED TO PLUMBING PAGE FOR FIELD INSPECTION -
 SHOWER CONNECTION ABOVE LAV CONNECTION NOT LOGICAL

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 16:27 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 15:20 Sent To  
Notes
2023-02-01 16:28:44PROVISO ON PLAN PAGE S-2: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-13 Cont ID  
Sent By cthroop Date 2023-03-13 Time 14:18 Rev Time 0.00
Received By cthroop Date 2023-03-13 Time 09:36 Sent To  
Notes
2023-03-13 14:19:152ND SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ALL PLAN PAGES
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-23 Cont ID  
Sent By mpeterso Date 2023-01-23 Time 13:10 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 13:10 Sent To  
Notes
2023-01-23 13:14:07SIGNATURE REVIEW FAILED
 1) A TITLE BLOCK FOR A PE IS DETAILED ON THE SUBMITTED
 PLANS WITHOUT THE REQUIRED SEAL AND DIGITAL SIGNATURE.
 PLEASE CORRECT AS OUTLINED BELOW.
  
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-02-27 Cont ID  
Sent By asangele Date 2023-02-27 Time 16:38 Rev Time 0.00
Received By asangele Date 2023-02-27 Time 16:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-01-20 Cont ID  
Sent By ASangele Date 2023-01-20 Time 17:10 Rev Time 0.00
Received By asangele Date 2023-01-20 Time 17:10 Sent To  
Notes
2023-01-20 17:11:19FAILED
 1/20/2023
  
  
  
 PLEASE PROPERTY SURVEY WITH LABELED SETBACKS.
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]