| Plan Review Stops For Permit 22120224 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-13 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-13 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2023-03-13 14:18:02 | 2ND BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | RESPONSE NARRATIVE STATES THAT ONLY A KITCHEN WILL BE | | | ADDED. PLANS STILL SHOW AN ADDITION INCLUDING A NEW | | | BEDROOM. SUBMIT REVISED PLANS BASED ON THE NEW SCOPE OF | | | WORK. | | | | | | | | | 1. CORRECTED | | | | | | 2. CORRECTED | | | | | | 3. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY | | | LOCATION OF WORK. | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE | | | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN | | | ACCURATE AND INCLUDED BOUNDRY LINE SURVEY. | | | | | | 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | | | | 5. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) | | | R401.2COMPLIANCE. | | | SECTION R405 AND THE PROVISIONS OF SECTIONS R401 | | | THROUGH R404 LABELED MANDATORY. | | | | | | 6.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED | | | WINDOWS AND SGD. (SGD PRODUCT APPROVAL NOT SUBMITTED | | | FOR REVIEW) | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE | | | SPEC. SHEET OF A FLUID APPLIED MEMBRANE. | | | R703.4 | | | | | | 8.PROVIDE SMOKE ALARMS. | | | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A | | | BUILDING. | | | SMOKE ALARMS | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-01 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-01 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2023-02-01 17:14:36 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: VALUE ADJUSTED TO $85,033 PER THE ICC BUILDING | | | VALUATION DATA. | | | | | | 1.PROVIDE PROJECT DATA/DESIGN PARAMETERS: | | | PROJECT DATA: 1&2 FAMILY DWELLING UNIT | | | OCCUPANCY CLASSIFICATION R3 SFR | | | SCOPE OF WORK | | | DESIGN PARAMETERS: 2020 FBC EXISTING BUILDING | | | 2020 FBC RESIDENTIAL | | | 2017 NEC | | | CLASSIFICATION OF WORK: ADDITION | | | BUILDING CLASSIFICATION: VB | | | EXPOSURE CLASSIFICATION: (B/C/D)? | | | RISK CATEGORY: II | | | MEAN ROOF HEIGHT: STATE MRH ON ELEVATION PLAN PAGE. | | | EXISTING UNDER AIR: 682/SF | | | EXISTING COVERED: 313/SF | | | NEW UNDER AIR: 512/SF | | | NEW COVERED: 0/SF | | | TOTALS: UNDER AIR 1194/SF | | | COVERED 512/SF | | | | | | SITE SPECIFIC DESIGN WIND LOADS PER: | | | FBC RESIDENTIAL CHPT. 3 | | | R301.2.1 WIND DESIGN CRITERIA. | | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | | FROM FIGURE R301.2(4). | | | -OR- | | | ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH) | | | | | | DESIGN WIND PRESSURES: | | | WINDOWS AND DOORS ??? ZONE 4 INT. / ZONE 5 CORNER | | | (POSITVE/NEGATIVE) | | | ROOF ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS) | | | R301.2.1 WIND DESIGN CRITERIA. | | | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN | | | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING | | | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED | | | FROM FIGURE R301.2(4). | | | | | | 2.PROVIDE A COPY OF THE MOST RECENT BOUNDY LINE SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 3. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY | | | LOCATION OF WORK. | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE | | | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN | | | ACCURATE AND INCLUDED BOUNDRY LINE SURVEY. | | | | | | 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | | | | 5. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) | | | R401.2COMPLIANCE. | | | SECTION R405 AND THE PROVISIONS OF SECTIONS R401 | | | THROUGH R404 LABELED MANDATORY. | | | | | | 6.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVALS APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED | | | WINDOWS AND SGD. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 7.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE | | | SPEC. SHEET OF A FLUID APPLIED MEMBRANE. | | | R703.4 | | | | | | 8.PROVIDE SMOKE ALARMS. | | | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A | | | BUILDING. | | | SMOKE ALARMS | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-03-07 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-03-07 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-03-07 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2023-03-07 15:27:11 | 2ND ELECTRIC REVIEW FAILED | | | | | | PREVIOUS COMMENTS NOT ADDRESSED. IN ADDITION , IT DOES | | | APPEAR NEW MINI SPLIT AIR CONDITIONERS WILL BE ADDED. | | | PLEASE SHOW ADDITIONAL WIRING TO BE ADDED FOR THESE | | | MINI SPLITS. FBC 107.2 | | | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-01-23 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-23 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-23 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2023-01-23 13:10:23 | ELECTRIC REVIEW FAILED | | | 1) PLEASE DETAIL COMPLIANCE WITH NEC 110.26 FOR | | | ELECTRIC PANEL WORKING SPACE. | | | 2) PLEASE DETAIL ALL SMOKE/CARBON ALARMS AS REQUIRED | | | FBC R314.3 | | | 3) PLEASE DETAIL THE REQUIRED KITCHEN ISLAND | | | RECEPTACLE. NES 210.52 | | | 4) PLEASE DETAIL LOCATION OF EXISTING METER ON ELECTRIC | | | FLOOR PLAN. FBC 107.2 | | | 5) SEE SIGNATURE REVIEW | | | 6) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, | | | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR | | | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-13 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-21 |
Time |
22:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-01 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-11 |
Time |
06:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-01 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-01 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2023-02-01 15:30:06 | IMPACT FEES | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-27 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-27 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2023-02-27 09:48:07 | THIS NEW ADDITION WILL NEED TO MEET THE REQUIREMENTS OF | | | THE ENERGY CODE. IF THE EXISTING MECHANICAL SYSTEM IS | | | TO BE USED TO CONDITION THE NEW ADDITION A MECHANICAL | | | EQUIPMENT SIZING CALCULATION SHALL BE PROVIDED. A | | | MECHANICAL DRAWING SHALL BE PROVIDED SHOWING THE DUCT | | | CONNECT, SIZE AND CFM'S TO THE NEW ADDITION. | | | PROVIDE THE DOCUMENTATION REQUESTED IN THE 1ST CYCLE | | | MECHANICAL REVIEW. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS ADDITION. | | | FEC R101.5.1.1.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS EDITION. FEC R403.7.1 | | | | | | 3) PROVIDE MECHANICAL DRAWING FOR THE MECHANICAL DESIGN | | | FOR THIS ADDITION. FBC 107.3.5 | | | | | | 4) SHOW THE BATHROOM EXHAUST FAN, DUCTWORK AND | | | TERMINATION LOCATION. FRC R303.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-17 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-17 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2023-01-17 11:06:43 | 1ST REVIEW FMC | | | PERMIT: 22120224 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS ADDITION. | | | FEC R101.5.1.1.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS EDITION. FEC R403.7.1 | | | | | | 3) PROVIDE MECHANICAL DRAWING FOR THE MECHANICAL DESIGN | | | FOR THIS ADDITION. FBC 107.3.5 | | | | | | 4) SHOW THE BATHROOM EXHAUST FAN, DUCTWORK AND | | | TERMINATION LOCATION. FRC R303.3 | | | | | | 5) PROVIDE THE CONDENSING UNIT TIE DOWN METHOD. FRC | | | M1307.2 | | | | | | 6) PROVIDE THE CONDENSATE PIPING TERMINATION LOCATION. | | | FRC M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-22 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-22 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2023-02-22 06:50:39 | NOTE ADDED TO PLUMBING PAGE FOR FIELD INSPECTION - | | | SHOWER CONNECTION ABOVE LAV CONNECTION NOT LOGICAL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-01-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-01-17 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-01-17 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2023-01-17 11:02:12 | NOTE ADDED TO PLUMBING PAGE FOR FIELD INSPECTION - | | | SHOWER CONNECTION ABOVE LAV CONNECTION NOT LOGICAL |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2023-02-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-01 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-01 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2023-02-01 16:28:44 | PROVISO ON PLAN PAGE S-2: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-13 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-13 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2023-03-13 14:19:15 | 2ND SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: ALL PLAN PAGES | | | | | | 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. | | | A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE | | | IS NOT CONSIDERED A VALID DIGITAL SIGNATURE. | | | | | | 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S. | | | 668.003 (3); | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS) | | | F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-01-23 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-23 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-23 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2023-01-23 13:14:07 | SIGNATURE REVIEW FAILED | | | 1) A TITLE BLOCK FOR A PE IS DETAILED ON THE SUBMITTED | | | PLANS WITHOUT THE REQUIRED SEAL AND DIGITAL SIGNATURE. | | | PLEASE CORRECT AS OUTLINED BELOW. | | | | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-02-27 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-02-27 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-02-27 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-01-20 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-01-20 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-01-20 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2023-01-20 17:11:19 | FAILED | | | 1/20/2023 | | | | | | | | | | | | PLEASE PROPERTY SURVEY WITH LABELED SETBACKS. | | | | | | | | | ALEXIS SANGELEER | | | PLANNER | | | [email protected] |
|
|