Plan Review Details - Permit 22120222
Plan Review Stops For Permit 22120222
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2023-03-01 Cont ID  
Sent By cpuell Date 2023-03-01 Time 13:46 Rev Time 0.00
Received By cpuell Date 2023-03-01 Time 13:46 Sent To  
Notes
2023-03-01 13:47:11FRONT ADDRESS READDRESSED TO 732 NEW YORK ST AND THE
 REAR BUILDING NOW IS 734 NEW YORK ST, UPDATED PERMIT TO
 REFLECT THE CORRECT ADDRESS FOR THE SCOPE OF WORK.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-02-18 Cont ID  
Sent By cpuell Date 2023-02-18 Time 08:30 Rev Time 0.00
Received By cpuell Date 2023-02-18 Time 08:30 Sent To  
Notes
2023-02-18 08:31:14PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By cpuell Date 2022-12-13 Time 12:31 Rev Time 0.00
Received By jbrooks Date 2022-12-13 Time 12:31 Sent To  
Notes
2022-12-13 12:32:09WORK TO BE DONE ON THE NORTH BUILDING ONLY. THE SOUTH
 BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO BE
 READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS
 THE HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-03-01 Cont ID  
Sent By jbrooks Date 2023-03-01 Time 13:20 Rev Time 0.00
Received By jbrooks Date 2023-03-01 Time 13:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By jbrooks Date 2022-12-14 Time 10:25 Rev Time 0.00
Received By jbrooks Date 2022-12-14 Time 07:51 Sent To  
Notes
2022-12-14 10:26:10JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL14645.3.-R4 COVERS MULTIPLE FASTENER
 SPACINGS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT
 CORRECT FASTENER SPACING FROM 5V-CRIMP UPLIFT LOADS
 CHART THAT MEET OR EXCEED THE MINIMUM DESIGN PRESSURE
 REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C AREA, 5/12
 SLOPE GABLE ROOF; MEAN ROOF HEIGHT < 15 FT. (-102). ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-19 Cont ID  
Sent By amhamilt Date 2022-12-19 Time 16:21 Rev Time 0.00
Received By amhamilt Date 2022-12-19 Time 16:21 Sent To  
Notes
2022-12-19 16:24:18METAL ROOF MUST HAVE A MILL FINISH, NO COLOR PERMITTED
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-01 Cont ID  
Sent By jbrooks Date 2023-03-01 Time 13:21 Rev Time 0.00
Received By jbrooks Date 2023-02-15 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-20 Cont ID  
Sent By aoliver Date 2022-12-20 Time 11:06 Rev Time 0.00
Received By aoliver Date 2022-12-13 Time 12:03 Sent To  
Notes
***NONE***