Plan Review Details - Permit 22120077
Plan Review Stops For Permit 22120077
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By pvalenti Date 2022-12-21 Time 15:39 Rev Time 0.00
Received By pvalenti Date 2022-12-21 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By jbrooks Date 2022-12-13 Time 08:50 Rev Time 0.00
Received By jbrooks Date 2022-12-13 Time 07:42 Sent To  
Notes
2022-12-13 08:51:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R30 SYSTEM NO. W-146 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED SYSTEM
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL27499.1-R4 SELECTED OPTION #1 MAXIMUM DESIGN
 PRESSURE -116 PSF. DO NOT MEET THE MINIMUM ZONE 3
 DESIGN PRESSURE REQUIREMENT OF -121 FOR EXPOSURE
 CATEGORY C AREAS WITH A GABLE ROOF; ROOF SLOPES
 2/12-4/12 MEAN ROOF HEIGHT UP TO 15 FT. SELECT OPTION
 THAT MEETS OR EXCEEDS THIS REQUIREMENT. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF
 DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD
 OF PROVIDING POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-12-22 Cont ID  
Sent By fmittner Date 2022-12-22 Time 10:57 Rev Time 0.00
Received By fmittner Date 2022-12-22 Time 10:57 Sent To  
Notes
2022-12-22 10:58:14APPROVING FOR DRY IN. FLAT TILE TO REPLACE REMOVED
 ROOFING MATERIAL. METAL REQUIRES HPB APPROVAL.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By amhamilt Date 2022-12-19 Time 10:39 Rev Time 0.00
Received By amhamilt Date 2022-12-19 Time 10:39 Sent To  
Notes
2022-12-19 10:40:55THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 MUST BE RE-ROOFED WITH FLAT WHITE TILE, PLEASE PROVIDE
 NOA FOR TILE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-22 Cont ID  
Sent By lmarchan Date 2022-12-22 Time 11:04 Rev Time 0.00
Received By lmarchan Date 2022-12-21 Time 14:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-20 Cont ID  
Sent By aoliver Date 2022-12-20 Time 11:05 Rev Time 0.00
Received By aoliver Date 2022-12-12 Time 06:49 Sent To  
Notes
***NONE***