| Plan Review Stops For Permit 22120022 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-17 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-17 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2023-03-01 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2023-03-01 |
Time |
18:02 |
Sent To |
|
|
| Notes |
| 2023-03-01 18:03:36 | PREVIOUS COMMENT #3 STILL NOT ADDRESSED, AND FOLLOWS. | | | PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO THE | | | PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC | | | B 1405.4. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2023-01-30 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2023-01-30 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2023-01-30 10:36:29 | 1. GENERAL NOTE 9 IN ENGINEERING STATES THIS IS NOT | | | SITE SPECIFIC. THIS PROJECT REQUIRES SITE SPECIFIC | | | ENGINEERED DESIGN PRESSURES. FBC 107.1 2. SUBMITTED | | | DESIGN PRESSURE FOR UNITS 3A, 3B, AND 3C REQUIRE | | | -110.9. FBC/NOA SUBMISSION IS TESTED AT -110.0, AND | | | DOES NOT COMPLY. FBC 107.2. 3. PLEASE PROVIDE A | | | FLASHING DETAIL, OR ADD A NOTE TO THE PLAN, | | | DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC B | | | 1405.4. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-31 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2022-12-31 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2022-12-31 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2022-12-31 16:13:04 | 1. THIS PROJECT REQUIRES SITE SPECIFIC ENGINEERED | | | DESIGN PRESSURE REQUIREMENTS. THIS IS A REQUIREMENTS | | | FOR ANY PROJECT OVER 60' MRH. THESE CALCULATIONS CANNOT | | | BE REUSED FOR ANY OTHER PROJECT. I AM UNABLE TO | | | COMPLETE THIS REVIEW WITHOUT PROPER DESIGN PRESSURE | | | REQUIREMENTS. 2. PLEASE PROVIDE A FLASHING DETAIL, OR | | | ADD A NOTE TO THE PLAN, DEMONSTRATING COMPLIANCE WITH | | | FBC R 703.4 OR FBC B 1405.4. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-17 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-07 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
F |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2023-03-01 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2023-02-01 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2023-01-30 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2023-01-03 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-31 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2022-12-31 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2022-12-02 |
Time |
07:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-03-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-17 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-17 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2023-03-01 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2023-03-01 |
Time |
18:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-01-30 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2023-01-30 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2023-01-30 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2023-01-30 10:37:56 | 1. GENERAL NOTE 9 IN ENGINEERING STATES THIS IS NOT | | | SITE SPECIFIC. THIS PROJECT REQUIRES SITE SPECIFIC | | | ENGINEERED DESIGN PRESSURES. FBC 107.1 2. SUBMITTED | | | DESIGN PRESSURE FOR UNITS 3A, 3B, AND 3C REQUIRE | | | -110.9. FBC/NOA SUBMISSION IS TESTED AT -110.0, AND | | | DOES NOT COMPLY. FBC 107.2. 3. PLEASE PROVIDE A | | | FLASHING DETAIL, OR ADD A NOTE TO THE PLAN, | | | DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC B | | | 1405.4. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-12-31 |
|
|
Cont ID |
|
| Sent By |
eroseber |
Date |
2022-12-31 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
eroseber |
Date |
2022-12-31 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2022-12-31 16:13:51 | 1. THIS PROJECT REQUIRES SITE SPECIFIC ENGINEERED | | | DESIGN PRESSURE REQUIREMENTS. THIS IS A REQUIREMENTS | | | FOR ANY PROJECT OVER 60' MRH. THESE CALCULATIONS CANNOT | | | BE REUSED FOR ANY OTHER PROJECT. I AM UNABLE TO | | | COMPLETE THIS REVIEW WITHOUT PROPER DESIGN PRESSURE | | | REQUIREMENTS. 2. PLEASE PROVIDE A FLASHING DETAIL, OR | | | ADD A NOTE TO THE PLAN, DEMONSTRATING COMPLIANCE WITH | | | FBC R 703.4 OR FBC B 1405.4. |
|
|