| 2022-12-08 15:30:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE EXITS INDICATED ON THE LIFE SAFETY PLANS, |
| | |
| | PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH |
| | 7 MEANS OF EGRESS. |
| | |
| | 7.7 DISCHARGE FROM EXITS |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC |
| | WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| | PROVIDED IN 7.7.1.2 |
| | THROUGH 7.7.1.4. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE REQUIRED |
| | CODE. |
| | |
| | |
| | |
| | 2) THERE ARE TWO EXIT STAIRS INDICATED FROM THE 2ND |
| | FLOOR. |
| | |
| | PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH |
| | 7 MEANS OF EGRESS. |
| | |
| | 12.2.2.3 STAIRS. |
| | 12.2.2.3.1 GENERAL. STAIRS COMPLYING WITH 7.2.2 SHALL |
| | BE PERMITTED, |
| | UNLESS ONE OF THE FOLLOWING CRITERIA APPLIES: |
| | ( EXCEPTIONS NOT APPLICABLE) |
| | |
| | 38.2.2.3 STAIRS. |
| | 38.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE |
| | PERMITTED |
| | |
| | PLEASE PROVIDE STAIR DETAILS IN COMPLIANCE WITH THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | 3) THERE ARE INDICATIONS OF AN ELEVATOR; HOWEVER, THERE |
| | IS NO INDICATION OF AREA OF REFUGE FOR ACCESSIBILTIY. |
| | |
| | PER NFPA 101, CH 12 NEW ASSEMBLY, 38 NEW BUSINESS, & CH |
| | 7 MEANS OF EGRESS. |
| | |
| | 12.2.2.12 AREAS OF REFUGE. AREAS OF REFUGE COMPLYING |
| | WITH 7.2.12 |
| | SHALL BE PERMITTED |
| | |
| | 38.2.2.12 AREAS OF REFUGE. |
| | 38.2.2.12.1 AREAS OF REFUGE COMPLYING WITH 7.2.12 SHALL |
| | BE |
| | PERMITTED. |
| | |
| | PLEASE PROVIDE AREA OF REFUGE DETAILS IN COMPLIANCE |
| | WITH THE REQUIREMENTS. |
| | |
| | |
| | 4) SHEET A601 - THERE ARE INDICATIONS OF MAGNETIC LOCKS |
| | & CARD READERS ON THE DOOR SCHEDULE. |
| | |
| | THE INSTALLATION OF CARD READERS/ACCESS CONTROL SHALL |
| | BE INSTALLED UNDER SEPARATE PERMIT & SHOP DRAWING |
| | IN COMPLIANCE WITH NFPA 101, MEANS OF EGRESS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON |
| | THE PLAN SHEET. |
| | |
| | |
| | 5) SHEET T100 - THERE ARE INDICATIONS OF SEPARATE FIRE |
| | SPRINKLER SHOP DRAWING SUBMITTAL. |
| | |
| | IS THERE AN EXISTING FIRE SPRINKLER SYSTEM OR IS IT A |
| | NEW SYSTEM? |
| | |
| | PER F.A.C. |
| | |
| | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING |
| | DOCUMENTS. |
| | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF |
| | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR |
| | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING |
| | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER???S |
| | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, |
| | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: |
| | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS |
| | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A |
| | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND |
| | EXPERIENCE. |
| | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY |
| | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH |
| | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS |
| | ARE INTENDED TO CONFORM TO. |
| | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF |
| | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF |
| | THE SYSTEM. |
| | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT |
| | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING |
| | DOCUMENTS. |
| | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY |
| | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE |
| | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE |
| | STATED PURPOSE OF THESE RESPONSIBILITY RULES. |
| | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND |
| | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING |
| | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR |
| | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE |
| | OF SUCH DOCUMENTS. |
| | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN |
| | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR |
| | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO |
| | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER |
| | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS |
| | RESPONSIBILITY. |
| | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY |
| | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST |
| | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. |
| | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY |
| | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN |
| | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC |
| | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND |
| | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE |
| | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES |
| | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE |
| | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A |
| | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR |
| | AGENCY APPROVAL ACTION ON THE SAME PROJECT. |
| | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW |
| | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY???NEW |
| | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY???NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | THE DESIGN DOCUMENTS ARE REQUIRED TO BE SUBMITTED WITH |
| | THE MASTER PERMT. |
| | |
| | PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION |
| | PER THE F.A.C. |
| | |
| | |
| | 6) SHEET T100 - THERE ARE INDICATIONS OF SEPARATE FIRE |
| | ALARM SHOP DRAWING SUBMITTAL. |
| | |
| | IS THERE AN EXISTING FIRE ALARM SYSTEM OR IS IT A NEW |
| | SYSTEM? |
| | |
| | PER F.A.C. |
| | |
| | 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS, |
| | AND CONTROL SYSTEMS. |
| | (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE |
| | PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS, |
| | ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE |
| | SIGNALING OF EMERGENCY CONDITIONS. ITEMS TO BE |
| | CONSIDERED IN THE DESIGN OR ANALYSIS OF FIRE ALARM AND |
| | DETECTION SYSTEMS ARE, AS APPLICABLE TO THE PARTICULAR |
| | PROJECT: OCCUPANCY AND CLASSIFICATION, MONITORING, |
| | CONTROL AND COMMUNICATION, CABLING AND SUPERVISION |
| | REQUIREMENTS, INSTALLATION REQUIREMENTS, |
| | INTEROPERABILITY AND PERFORMANCE REQUIREMENTS. |
| | (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE |
| | FLORIDA BUILDING CODE, THE FLORIDA FIRE PREVENTION |
| | CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY HAVING |
| | JURISDICTION. THE FLORIDA BUILDING CODE AND THE FLORIDA |
| | FIRE PREVENTION CODE ARE INCORPORATED BY REFERENCE IN |
| | RULE 61G15-18.011, F.A.C. |
| | (3) FOR ENGINEERING DOCUMENTS PERTAINING TO FIRE |
| | PROTECTION SYSTEMS EXEMPTED BY THE THRESHOLD |
| | REQUIREMENTS FOR MANDATORY USE OF PROFESSIONAL |
| | ENGINEERING SERVICES, THE ENGINEER OF RECORD SHALL |
| | DETERMINE THE LEVEL OF DETAIL SHOWN ON PLANS FOR A FIRE |
| | PROTECTION SYSTEM. ALL SUCH PLANS SHALL INCLUDE A |
| | DISCLAIMER STATING THE FIRE PROTECTION SYSTEM IS EXEMPT |
| | FROM PROFESSIONAL ENGINEERING SERVICES AND SHALL |
| | PROVIDE A CLEAR UNDERSTANDING OF THE MINIMUM SYSTEM |
| | REQUIREMENTS EXPECTED TO BE INSTALLED BY THE CONTRACTOR |
| | AND PERMITTED BY THE AUTHORITY HAVING JURISDICTION |
| | (AHJ). IN THE EVENT THE ENGINEER OF RECORD PROVIDES |
| | MORE INFORMATION AND DIRECTION THAN IS MINIMALLY |
| | REQUIRED, HE OR SHE SHALL BE HELD RESPONSIBLE FOR THE |
| | TECHNICAL ACCURACY OF THE WORK IN ACCORDANCE WITH |
| | APPLICABLE CODES, STANDARDS, AND SOUND ENGINEERING |
| | PRINCIPLES. |
| | (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND |
| | DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS |
| | SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION |
| | WHEN APPLICABLE: |
| | (A) THE DOCUMENTS SHALL BE CLEAR, WITH A SYMBOLS |
| | LEGEND, SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND |
| | NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS. THE |
| | DOCUMENTS SHALL INDICATE LOCATIONS WHERE FIRE RATINGS |
| | ARE REQUIRED AS DETERMINED BY THE SYSTEM???S |
| | SURVIVABILITY REQUIREMENTS, AND SHALL IDENTIFY THE |
| | GENERAL OCCUPANCY OF THE PROTECTED PROPERTY AND EACH |
| | ROOM AND AREA UNLESS IT IS CLEAR FROM FEATURES SHOWN. |
| | (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND |
| | CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND |
| | SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS |
| | INCLUDE ELEVATOR CONTROLS, SMOKE CONTROL SYSTEMS, |
| | DAMPERS, DOOR RELEASE, ANY OTHER SYSTEMS OR ELEMENTS |
| | DIRECTLY OR INDIRECTLY CONTROLLED OR MONITORED. |
| | (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL |
| | NOTIFICATION DEVICES. |
| | (D) IDENTIFY THE CLASS OF CIRCUITS AS LISTED IN NFPA |
| | 72, WHICH IS CONTAINED WITHIN AND INCORPORATED INTO THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND |
| | CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY |
| | SIGNALS BEING MONITORED OR ANNUNCIATED. |
| | (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR |
| | ADDRESSABLE, AND INDICATE ALL ZONING. |
| | (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED |
| | PROTECTIVE FEATURES. |
| | (H) IDENTIFY AND LOCATE SYSTEM DEVICES THAT ARE SUBJECT |
| | TO ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR |
| | THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY |
| | OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR. |
| | (I) THE DOCUMENTS SHALL INCLUDE A SITE PLAN OF THE |
| | IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE |
| | OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE |
| | THE STRUCTURE. |
| | (J) IN BUILDINGS WHERE SMOKE DETECTION WILL BE |
| | OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE |
| | ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND |
| | DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE |
| | OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A |
| | PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH |
| | AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (K) FOR FIRE DETECTION SYSTEMS UTILIZING SMOKE |
| | DETECTION IN SITUATIONS WHERE SMOKE STRATIFICATION IS |
| | ANTICIPATED, THE DESIGN SHALL PROVIDE THE NECESSARY |
| | CRITERIA TO MITIGATE THE DETECTION PROBLEMS. |
| | (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA |
| | SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR |
| | STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING |
| | JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE |
| | FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING |
| | CODE. |
| | (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO |
| | PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED |
| | EVACUATION FOR ALL HIGH-RISE BUILDINGS OR |
| | MULTI-TENANTED PROPERTIES AS DEFINED IN SECTION 2 OF |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS, |
| | CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND |
| | BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE |
| | PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND |
| | INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED |
| | TO OPERATE THE SYSTEMS AS INTENDED OVER TIME. |
| | (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO |
| | SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED |
| | WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS) |
| | CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL |
| | BE COMPLETED USING THE EQUIPMENT MANUFACTURER???S DATA |
| | AND APPLICABLE NFPA 72 PROCEDURES. |
| | (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (7) WHEN THE ENGINEER OF RECORD DETERMINES THAT SPECIAL |
| | REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE |
| | UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE |
| | REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE |
| | ENGINEERING DESIGN DOCUMENTS. |
| | (8) NO LATER THAN 90 DAYS PRIOR TO DECEMBER 31, 2026, |
| | THE BOARD SHALL REVIEW AND AMEND, MODIFY, OR SUNSET |
| | THIS RULE IF IT DETERMINES THIS RULE CREATES BARRIERS |
| | TO ENTRY FOR PRIVATE BUSINESS COMPETITION, IS |
| | DUPLICATIVE, OUTDATED, OBSOLETE, OVERLY BURDENSOME, OR |
| | IMPOSES EXCESSIVE COSTS. FAILURE BY THE BOARD TO ACT IN |
| | ACCORDANCE WITH THIS PROVISION WILL RESULT IN THE |
| | EXPIRATION OF THIS RULE ON DECEMBER 31, 2026. |
| | RULEMAKING AUTHORITY 471.008, 471.033(2) FS. LAW |
| | IMPLEMENTED 471.033 FS. HISTORY???NEW 5-19-93, FORMERLY |
| | 21H-32.008, AMENDED 3-26-09, 3-28-17, 7-25-19, 3-23-22. |
| | |
| | |
| | PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTATION |
| | PER THE F.A.C. |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |