Plan Review Stops For Permit 22111266
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-11-30 Cont ID  
Sent By shill Date 2022-11-30 Time 17:23 Rev Time 0.00
Received By shill Date 2022-11-30 Time 17:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-14 Cont ID  
Sent By jleahy Date 2022-12-14 Time 09:07 Rev Time 0.00
Received By jleahy Date 2022-12-14 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By jleahy Date 2022-12-13 Time 15:57 Rev Time 0.00
Received By jleahy Date 2022-12-13 Time 15:47 Sent To  
Notes
2022-12-13 15:58:15FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL CIRCUITS SHOWN ON PLANS AND WHERE THEY
 COME FROM. 215.5
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-04 Cont ID  
Sent By pleduc Date 2023-01-04 Time   Rev Time 0.00
Received By pleduc Date 2023-01-04 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-09 Cont ID  
Sent By pleduc Date 2022-12-09 Time   Rev Time 0.00
Received By pleduc Date 2022-12-09 Time 09:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-05 Cont ID  
Sent By pleduc Date 2022-12-05 Time   Rev Time 0.00
Received By pleduc Date 2022-12-05 Time 14:26 Sent To  
Notes
2022-12-05 14:32:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A HOOD INSTALLATION.
  
 THERE ARE NO INDICATIONS OF THE VENTING SYSTEM.
  
 PER NFPA 96
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EX HAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT
 AND PERFOR MANCE REQUIREMENTS OF THIS STANDARD.
  
 PLEASE PROVIDE DETAILS OF THE REQUIRED SYSTEM IN
 COMLIANCE WITH NFPA.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-04 Cont ID  
Sent By medwards Date 2023-01-04 Time 15:49 Rev Time 0.00
Received By medwards Date 2022-12-28 Time 07:01 Sent To  
Notes
2023-01-03 14:49:18M AFTER FIRE, AFFIDAVIT
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 12:01 Rev Time 0.00
Received By medwards Date 2022-12-08 Time 06:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-06 Cont ID  
Sent By shill Date 2022-12-06 Time 06:48 Rev Time 0.00
Received By shill Date 2022-12-02 Time 08:52 Sent To  
Notes
2022-12-05 12:34:47ADD E, M AFTER FIRE, AFFIDAVIT
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-01-04 Cont ID  
Sent By medwards Date 2023-01-03 Time 14:45 Rev Time 0.00
Received By medwards Date 2023-01-03 Time 14:45 Sent To  
Notes
2023-01-03 14:46:10MECHANICAL AUDIT ONLY ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 11:57 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 11:57 Sent To  
Notes
2022-12-15 11:57:421ST REVIEW FMC
 PERMIT: 22111266
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THIS SUBMISSION IS NOT COMPLETE. THIS REVIEWER
 CANNOT COMPLETE THE MECHANICAL AUDIT AT THIS TIME. THIS
 IS THE HOOD PERMIT FOR ALL KITCHEN HOODS, GREASE DUCTS
 AND MAKE-UP AIR FOR EACH. PLEASE SUBMIT DRAWINGS
 IDENTIFYING EACH HOOD IN THE KITCHEN, THE TERMINATION
 LOCATIONS WITH DETAILS SHOWING CLEARANCE COMPLIANCES,
 THE GREASE DUCT DRAWINGS THAT INCLUDE THE SIZES,
 CLEARANCES TO COMBUSTIBLES, CLEAN OUT LOCATIONS, THE
 MAKE-UP AIR DUCT WORK INCLUDING THE SIZES AND LOCATION
 OF THE MAKE-UP AIR UNITS. FBC 107.3.5
  
 2) PLEASE SHOW THAT THE IN-LINE KITCHEN EXHAUST FANS
 SHOWN ON THE MECHANICAL DRAWING WILL MEET THE
 PROTECTION REQUIREMENTS OF FMC 506.5.1.2.
  
 3) THE VALUE ON THE PERMIT APPLICATION SEEMS VERY LOW,
 PLEASE ADJUST THE VALUE TO INCLUDE ALL THE WORK LISTED
 ABOVE.
  
 4) CAPTIVE-AIRE DRAWING SHEET NO. 5: THIS DRAWING
 INDICATES THE HOOD FRONT DOES NOT MEET THE REQUIREMENTS
 IN FMC 507.4.1. PLEASE EXPLAIN WHAT APPLIANCE THAT WILL
 BE UNDER THIS HOOD.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2023-01-04 Cont ID  
Sent By medwards Date 2023-01-03 Time 13:39 Rev Time 0.00
Received By medwards Date 2023-01-03 Time 13:39 Sent To  
Notes
2023-01-03 13:40:19PP AFFIDAVIT ME

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-12-12 Cont ID  
Sent By shill Date 2022-12-12 Time 06:56 Rev Time 0.00
Received By shill Date 2022-12-12 Time 06:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-30 Cont ID  
Sent By mpeterso Date 2022-12-30 Time 09:21 Rev Time 0.00
Received By mpeterso Date 2022-12-30 Time 09:20 Sent To  
Notes
2022-12-30 09:21:2112/30/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-15 Cont ID  
Sent By medwards Date 2022-12-15 Time 11:59 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 11:59 Sent To  
Notes
2022-12-15 12:01:22ALL ENGINEERED DRAWINGS SUBMITTED DIGITALLY MUST HAVE
 THE DESIGNERS DIGITAL SIGNATURE. FS 471/481
 THE CAPTIVE AIRE DRAWINGS MUST INCLUDE THE NAME AND
 SIGNATURE OF THE DESIGNER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  