Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By jleahy Date 2023-07-12 Time 12:36 Rev Time 0.00
Received By jleahy Date 2023-07-12 Time 12:31 Sent To  
Notes
2023-07-12 12:36:25FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A PLAN SHOWING WHATS NEW THAT IS BEING
 INSTALLED ELECTRICALLY 215.5
  
 PLEASE SUBMIT SIGNED PLANS FOR REVIEW. WPB 107,2,1
  
 PLEASE SUBMIT A RISER DIAGRAM, DOES SERVICE FEED BOTH
 PARTS OF BUILDING OR ARE THERE TWO SERVICES? 215.5
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By pleduc Date 2023-07-12 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 14:33 Sent To  
Notes
2023-07-12 11:33:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF SCOPE OF WORK ON THE COVER
 SHEET, HOWEVER, THE SUBMITTED FLOOR PLAN DOES NOT
 REFLECT THAT SCOPE OF WORK.
  
 WHAT IS THE EXTENT AND DETAIL OF THE INTERIOR
 PARTITION? I.E. WHAT IS EXISTING AND WHAT IS NEW
 CONSTRUCTION?
  
 THERE IS A REFERENCE TO A MINI SPLIT(SEE MECH. PLAN)
 BUT THERE IS NO MECHANICAL PLAN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE GREATER DETAIL
 OD THE WALL AND A MECHANICAL PLAN IN AGREEMENT OF THE
 SCOPE OF WORK.
  
  
  
 2) THERE IS REFENCE TO WALL CONSTRUCTION IN A BUILDING
 WITH A FIRE SPRINKLER.
  
 DUE TO THE DEMO & CONSTRUCTION IT REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE PER NFPA 13 & 72.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS, IN COMPLIANCE WITH NFPA 13 & 72
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-05 Time 12:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-21 Cont ID  
Sent By cmontell Date 2023-07-21 Time 14:05 Rev Time 0.00
Received By cmontell Date 2023-07-21 Time 14:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-12 Cont ID  
Sent By jleahy Date 2023-07-12 Time 12:36 Rev Time 0.00
Received By jleahy Date 2023-07-12 Time 12:36 Sent To  
Notes
2023-07-12 12:36:54FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A PLAN SHOWING WHATS NEW THAT IS BEING
 INSTALLED ELECTRICALLY 215.5
  
 PLEASE SUBMIT SIGNED PLANS FOR REVIEW. WPB 107,2,1
  
 PLEASE SUBMIT A RISER DIAGRAM, DOES SERVICE FEED BOTH
 PARTS OF BUILDING OR ARE THERE TWO SERVICES? 215.5
  