Plan Review Details - Permit 22111253
Plan Review Stops For Permit 22111253
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-06-27 Cont ID  
Sent By rmcdouga Date 2023-06-26 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2023-06-26 Time 15:54 Sent To  
Notes
2023-06-26 15:57:28AN ASBESTOS REPORT WAS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-27 Cont ID  
Sent By rmcdouga Date 2023-06-27 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2023-06-26 Time 16:25 Sent To  
Notes
2023-06-27 10:14:30PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT RESOLVED. ALSO SEE THE THRESHOLD REVIEW
 COMMENTS. PLEASE SEE THE CITY OF WPB THRESHOLD
 INSPECTION INSTRUCTIONS AND POLICY BOOKLET. THE
 THRESHOLD STATEMENT IS NOT ON THE STRUCTURAL DRAWINGS.]
 THIS PROJECT INVOLVES STRUCTURAL MODIFICATIONS TO A
 THRESHOLD BUILDING. A THRESHOLD INSPECTOR WILL BE
 REQUIRED. PLEASE ADDRESS THE FOLLOWING:
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) [RESOLVED.] PROVIDE A COMPLETE FLOOR PLAN OF THE
 BUILDING FOR EACH FLOOR OF THE PROJECT AND IDENTIFY THE
 WORK AREA ON EACH FLOOR. FBC 107.2.1
  
 3) [RESOLVED.] PROVIDE A COVER PAGE WITH THE DESIGN
 PARAMETERS AND RELAVENT CODES (FBC EXISTING BUILDING
 AND OTHERS). THIS INCLUDES DESIGN CRITERIA, LEVEL OF
 ALTERATION, AND CODE ANALYSIS. FBC 107.2.1
  
 4) YOU MAY WISH TO DEFER SUBMITTING SOME CONSTRUCTION
 DOCUMENTS (SHOP DRAWINGS, PRODUCT APPROVALS, ETC.)
 UNTIL A LATER TIME PRIOR TO INSTALLATION. FBC
 AMENDMENTS 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5) [RESOLVED.] PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT
 FROM THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 6) [NOT RESOLVED. YOU SUBMITTED DOCUMENT FOR TWO
 DIFFERENT PROFLEX PRODUCTS. THE FLAME SPREAD TEST
 REPORT FOR THE SUPER SIM-90 IS ACCEPTABLE. YOU WILL
 HAVE TO SUBMIT THE SUPER SIM-90 TEST REPORTS FOR THE
 AIR-BORNE AND STRUCTURE-BORNE SOUND.] THE SCOPE OF WORK
 FOR THIS PROJECT WILL REQUIRE THE INSTALLATION OF SOME
 TYPE OF NEW FLOORING IN THE UNIT. SPECIFY THE TYPE OF
 FINISH FLOORING AND THE SOUND INSULATION UNDERLAYMENT
 THAT WILL BE INSTALLED. YOU WILL ALSO NEED TO SUBMIT
 COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS. FBC 603.1
 FLAME SPREAD - ASTM E 84-09
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 7) [RESOLVED.] ON SHEET S100, THE FLOOR PENETRATION
 REPAIR DETAIL SPECIFIES PLYWOOD SHEATHING AND WOOD
 JOISTS. THIS IS NOT ALLOWED IN TYPE I AND II
 CONSTRUCTION. 718.5 COMBUSTIBLE MATERIALS IN CONCEALED
 SPACES IN TYPE I OR II CONSTRUCTION. COMBUSTIBLE
 MATERIALS SHALL NOT BE PERMITTED IN CONCEALED SPACES OF
 BUILDINGS OF TYPE I OR II CONSTRUCTION.
  
 8) [RESOLVED.] SHOW COMPLIANCE WITH FBC 1014.1 FOR
 HANDRAILS AT THE PROPOSED STAIRS.
  
 9) [RESOLVED.] SHOW COMPLIANCE WITH FBC 1015.1 FOR
 GUARDS AT THE PROPOSED STAIRS.
  
 10) [NOT RESOLVED. I DID NOT SEE ON THE PLANS WHERE THE
 CLEAR FLOOR SPACES AT FIXTURES OR THE REINFORCED WALL
 AREAS FOR GRAB BARS WERE SHOWN.] SHOW THAT THE
 REMODELED BATHROOMS AND KITCHENS COMPLY WITH FAIR
 HOUSING.
  
 11) [NOT RESOLVED. THE DESIGNER OF RECORD HAS NOT
 APPROVED THE PRODUCT APPROVALS IN WRITING. THE SPECIFIC
 ITEM TYPES, SIZES AND THEIR DESIGN PRESSURES HAVE NOT
 BEEN MARKED UP ON THE PRODUCT APPROVALS. ] FBC 107.3.4
 - PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH
 ARE REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. INDICATE THE
 SPECIFIC ITEMS AND THEIR DESIGN PRESSURES ON THE
 PRODUCT APPROVAL BY CIRCLING OR HI-LIGHTING THEM. THESE
 ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED.
  
 12) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. THIS WILL
 HELP SPEED THE REVIEW AND AID ME IN AVOIDING THINGS
 THAT WERE CORRECTED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-19 Cont ID  
Sent By rmcdouga Date 2023-04-19 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2023-04-17 Time 11:26 Sent To  
Notes
2023-04-18 15:52:41PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT INVOLVES STRUCTURAL MODIFICATIONS TO A
 THRESHOLD BUILDING. A THRESHOLD INSPECTOR WILL BE
 REQUIRED. PLEASE ADDRESS THE FOLLOWING:
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) PROVIDE A COMPLETE FLOOR PLAN OF THE BUILDING FOR
 EACH FLOOR OF THE PROJECT AND IDENTIFY THE WORK AREA ON
 EACH FLOOR. FBC 107.2.1
  
 3) PROVIDE A COVER PAGE WITH THE DESIGN PARAMETERS AND
 RELAVENT CODES (FBC EXISTING BUILDING AND OTHERS). THIS
 INCLUDES DESIGN CRITERIA, LEVEL OF ALTERATION, AND CODE
 ANALYSIS. FBC 107.2.1
  
 4) YOU MAY WISH TO DEFER SUBMITTING SOME CONSTRUCTION
 DOCUMENTS (SHOP DRAWINGS, PRODUCT APPROVALS, ETC.)
 UNTIL A LATER TIME PRIOR TO INSTALLATION. FBC
 AMENDMENTS 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5) PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 6) THE SCOPE OF WORK FOR THIS PROJECT WILL REQUIRE THE
 INSTALLATION OF SOME TYPE OF NEW FLOORING IN THE UNIT.
 SPECIFY THE TYPE OF FINISH FLOORING AND THE SOUND
 INSULATION UNDERLAYMENT THAT WILL BE INSTALLED. YOU
 WILL ALSO NEED TO SUBMIT COPIES OF THE ACTUAL TEST
 REPORTS FOR THE SOUND INSULATION INCLUDING FLAME SPREAD
 AND SMOKE DEVELOPED FOR THE APPLICABLE CONSTRUCTION
 CONDITIONS. FBC 603.1 FLAME SPREAD - ASTM E 84-09
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 7) ON SHEET S100, THE FLOOR PENETRATION REPAIR DETAIL
 SPECIFIES PLYWOOD SHEATHING AND WOOD JOISTS. THIS IS
 NOT ALLOWED IN TYPE I AND II CONSTRUCTION. 718.5
 COMBUSTIBLE MATERIALS IN CONCEALED SPACES IN TYPE I OR
 II CONSTRUCTION. COMBUSTIBLE MATERIALS SHALL NOT BE
 PERMITTED IN CONCEALED SPACES OF BUILDINGS OF TYPE I OR
 II CONSTRUCTION.
  
 8) SHOW COMPLIANCE WITH FBC 1014.1 FOR HANDRAILS AT THE
 PROPOSED STAIRS.
  
 9) SHOW COMPLIANCE WITH FBC 1015.1 FOR GUARDS AT THE
 PROPOSED STAIRS.
  
 10) SHOW THAT THE REMODELED BATHROOMS AND KITCHENS
 COMPLY WITH FAIR HOUSING.
  
 11) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. INDICATE
 THE SPECIFIC ITEMS AND THEIR DESIGN PRESSURES ON THE
 PRODUCT APPROVAL BY CIRCLING OR HI-LIGHTING THEM. THESE
 ITEMS CAN BE DEFERRED IF REQUESTED, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED.
  
 12) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By eroseber Date 2023-03-06 Time 11:54 Rev Time 0.00
Received By eroseber Date 2023-03-06 Time 11:54 Sent To  
Notes
2023-03-06 12:01:43(1) PLEASE SUBMIT PERMIT APPLICATION AND PLANS FOR UNIT
 RENOVATION. THIS INCLUDES DESIGN CRITERIA, LEVEL OF
 ALTERATION, AND CODE ANALYSIS. FBC 107.1, FBC 107.2 (2)
 PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO THE
 PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC
 B 1405.4.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-11 Cont ID  
Sent By rperdomo Date 2023-04-11 Time 13:49 Rev Time 0.00
Received By rperdomo Date 2023-04-11 Time 11:50 Sent To  
Notes
2023-04-11 13:48:59FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW
  
 SEPARATE PERMITS MUST BE SUBMITTED FOR GENERATOR AND
 LOW VOLTAGE.
  
 END OF COMMENTS
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-06-01 Cont ID  
Sent By parking Date 2023-06-01 Time 19:30 Rev Time 0.00
Received By lquinone Date 2023-06-01 Time 19:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-23 Cont ID  
Sent By pleduc Date 2023-05-23 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 13:45 Sent To  
Notes
2023-05-23 13:48:27FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-13 Cont ID  
Sent By pleduc Date 2023-04-13 Time   Rev Time 0.00
Received By pleduc Date 2023-04-10 Time 16:14 Sent To  
Notes
2023-04-13 16:14:53FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-19 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-28 Cont ID  
Sent By dbattles Date 2023-06-28 Time 14:59 Rev Time 0.00
Received By dbattles Date 2023-05-22 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-19 Cont ID  
Sent By rmcdouga Date 2023-04-19 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2023-04-06 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By eroseber Date 2023-03-06 Time 12:02 Rev Time 0.00
Received By eroseber Date 2023-02-03 Time 08:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-06-15 Cont ID  
Sent By hmoser Date 2023-06-15 Time 12:19 Rev Time 0.00
Received By hmoser Date 2023-06-15 Time 10:51 Sent To  
Notes
2023-06-15 12:19:37PASS PROVISO
 REFER TO SECTION 504.4.1 EXHAUST TERMINATION OUTLET
 AND PASSAGEWAY. DO NOT OVAL DRYED DUCT 2020 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-04-14 Cont ID  
Sent By medwards Date 2023-04-14 Time 10:55 Rev Time 0.00
Received By medwards Date 2023-04-14 Time 10:55 Sent To  
Notes
2023-04-14 10:55:191ST REVIEW FMC
 PERMIT: 22111253
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE DETAILS FOR THE VENTILATION OF THIS
 PENTHOUSE. EACH OCCUPIED SPACE SHALL BE VENTILATED BY
 NATURAL MEANS OR BY MECHANICAL MEANS. THE WINDOWS DO
 NOT APPEAR TO OPEN. FMC 401.2
  
 2) EACH BATHROOM EXHAUST SHALL BE PROVIDED ACCESS FOR
 MAINTENANCE AND CHANGE OUT. FMC 306.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By ccole Date 2023-05-24 Time 15:57 Rev Time 0.00
Received By ccole Date 2023-05-24 Time 15:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-11 Cont ID  
Sent By ccole Date 2023-04-11 Time 10:00 Rev Time 0.00
Received By ccole Date 2023-04-11 Time 08:45 Sent To  
Notes
2023-04-11 10:00:511ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22111253
 4/11/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.2: THE PLUMBING FIXTURE SCHEDULE REFERS TO
 THE ARCHITECTURAL DRAWINGS FOR NEW SHOWER PAN DETAILS
 HOWEVER THERE ARE NO DETAILS PROVIDED. PLEASE PROVIDE
 SHOWER COMPARTMENT, SHOWER WALL, AND SHOWER PAN DETAILS
 IN COMPLIANCE WITH SEC. 421.4, 421.4.1, & 421.5.2 FBC
 P.
  
 2) A5.2: PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 DETAILS FOR PLUMBING PIPING PENETRATIONS FOR THE
 EXISTING SLABS- SEC. 315.1 FBC P.
  
 3) P3.1: PLEASE CORRECT THE RISER SHOWING A LAV WITH
 2-INCH WASTE ARM ON THE 20TH FLOOR. THE FIXTURE AT THAT
 LOCATION IS THE KITCHEN SINK- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-06-28 Cont ID  
Sent By dbattles Date 2023-06-28 Time 14:59 Rev Time 0.00
Received By dbattles Date 2023-06-28 Time 14:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-26 Cont ID  
Sent By rmcdouga Date 2023-06-26 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2023-06-26 Time 16:25 Sent To  
Notes
2023-05-24 15:58:40PLUMBING SIGNATURES PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-19 Cont ID  
Sent By rmcdouga Date 2023-04-19 Time 12:45 Rev Time 0.00
Received By rmcdouga Date 2023-04-19 Time 12:45 Sent To  
Notes
2023-04-19 12:46:33SHEET A2.1, A2.2 AND A2.3 ARE FOR REFERENCE AND HAVE
 BEEN LOCKED.
2023-04-14 10:56:00MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-04-11 09:32:21PLUMBING (P) PLANS PASSED DIG/SIG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By eroseber Date 2023-03-06 Time 12:02 Rev Time 0.00
Received By eroseber Date 2023-03-06 Time 12:01 Sent To  
Notes
2023-03-06 12:02:29(1) PLEASE SUBMIT PERMIT APPLICATION AND PLANS FOR UNIT
 RENOVATION. THIS INCLUDES DESIGN CRITERIA, LEVEL OF
 ALTERATION, AND CODE ANALYSIS. FBC 107.1, FBC 107.2 (2)
 PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO THE
 PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC
 B 1405.4.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2023-06-26 Cont ID  
Sent By rmcdouga Date 2023-06-26 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2023-06-26 Time 16:43 Sent To  
Notes
2023-06-26 16:50:05SUBMIT THE THRESHOLD DOCUMENTS AS ONE FILE. IT APPEARS
 THAT YOU ONLY SUBMITTED THE CONTRACTOR'S INFORMATION.
 THERE ARE DOCUMENTS FOR THE OWNER AND THE THRESHOLD
 ENGINEER THAT WILL BE DOING THE STRUCTURAL INSPECTIONS.
 THE CITY HAS IT'S OWN GUIDELINES AND POLICIES BOOKLET
 WITH ALL OF THE REQUIRED FORMS. IF YOU WOULD LIKE A
 COPY JUST SEND ME AN EMAIL AND I WILL SEND IT TO YOU.
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  