Plan Review Details - Permit 22111092
Plan Review Stops For Permit 22111092
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-14 Cont ID  
Sent By cthroop Date 2023-01-14 Time 10:00 Rev Time 0.00
Received By cthroop Date 2023-01-14 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By cthroop Date 2022-12-12 Time 14:01 Rev Time 0.00
Received By cthroop Date 2022-12-12 Time 06:05 Sent To  
Notes
2022-12-12 14:08:531ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 2. PROVIDE COVER SHEETS FOR THE OVERHEAD DOOR PRODUCT
 APPROVALS.
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE CURRENT PRODUCT APPROVALS OR NOA FOR
 PROPOSED EXTERIOR DOORS.
 PRODUCT APPROVALS INCLUDE THE COVER SHEET, EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4.PROVIDE A WINDOW AND DOOR FLASHING DETAIL PER
 R703.4FLASHING.
 APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED
 MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING
 SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTRUCTIONS.
  
 5. CLARIFICATION REQUIRED.
 NOA 19-0227.07 FOR TARIMATEC HOLLOW COMPOSITE DECK HAS
 BEEN SUBMITTED FOR REVIEW. PLEASE IDENTIFY THE LOCATION
 OF THIS PRODUCT ON THE PLANS. IF NOT USED, PLEASE
 REMOVE IT FROM YOUR SUBMITTAL DOCUMENTS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-18 Cont ID  
Sent By rperdomo Date 2023-01-18 Time 11:37 Rev Time 0.00
Received By rperdomo Date 2023-01-18 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-01 Cont ID  
Sent By rperdomo Date 2022-12-01 Time 16:09 Rev Time 0.00
Received By rperdomo Date 2022-12-01 Time 14:53 Sent To  
Notes
2022-12-01 16:09:13FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. SERVICE RECEPTACLE
 A SERVICE RECEPTACLE NEEDS TO BE INSTALLED NEAR THE
 EQUIPMENT FOR THIS PURPOSE. A 125-VOLT, 15- AND
 20-AMPERE RECEPTACLE FOR SERVICING AIR-CONDITIONING AND
 REFRIGERATION EQUIPMENT IS REQUIRED TO BE LOCATED NOT
 LESS THAN 7.5 M (25 FT) FROM,
 AND ON THE SAME LEVEL AS, THE EQUIPMENT ITSELF. THE
 RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION
 FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS
 APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING
 OCCUPANCIES NEC 210.63 OR IRC
 E3901.11
  
 END OF COMMENTS
  
 THANK YOU,
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2023-02-03 Cont ID  
Sent By ccole Date 2023-02-03 Time 10:19 Rev Time 0.00
Received By ccole Date 2023-02-03 Time 09:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2023-01-25 Cont ID  
Sent By ccole Date 2023-01-25 Time 10:01 Rev Time 0.00
Received By ccole Date 2023-01-25 Time 07:38 Sent To  
Notes
2023-01-25 10:23:25FBC-0202 RES. FUEL GAS REVIEW.
 PERMIT- 22111092
 1/25/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2 ARE NOT DIGITALLY SIGNED AND SEALED
 BY THE ARCHITECT OF RECORD- FL. STATUTE 481.221 AND
 SEC. 61G1-16.005 FAC.
  
 2) SHEET P2 GAS RISER: THE PVC SLEEVES SPECIFIED FOR
 THE PE PIPING ARE NOT APPROVED. REFER TO SEC.
 G2415.17.1 & G2415.17.2 FBC RES AND PROVIDE ANODELESS
 RISERS OR SERVICE HEAD ADAPTER RISERS FOR THE PE
 PIPING. PLESASE NOTE ANODELESS RISERS AND TRANSITION
 FITTINGS BETWEEN THE PE AND METALLIC PIPING SHALL
 CONFORM TO ASTM D2513 CAT. 1 OR ASTM F1973 - SECS.
 G2415.17.1 & G2415.17.2.
  
 3) SHEET P2: PLEASE CORRECT THE 11 IN.WC. MAX PRESSURE
 FOR THE TAKAGI WATER HEATERS. THE MAN. SPECS INDICATE
 MAX 10.5 IN. W.C.- SEC. G2448.1 FBC RES.
  
 4) P2 GAS RISER: PLEASE CORRECT THE 2LB. SYSTEM LABEL
 TO INDICATE A LOW PRESSURE LESS THAN 2PSI SYSTEM BASED
 ON THE PIPE SIZING TABLE 402.4(2) SPECIFIED ON THE
 DRAWING- SEC. G2413.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-01-13 Cont ID  
Sent By ccole Date 2023-01-13 Time 10:02 Rev Time 0.00
Received By ccole Date 2023-01-13 Time 08:09 Sent To  
Notes
2023-01-13 10:03:062ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22111092
 1/3/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2: THE GAS RISER SHOWS A 2LB METER, OR 2PSI,
 HOWEVER THE NEW GAS PIPING NOTES ON THE PLAN REFERENCE
 TABLE 402.4(2) WHICH IS A SIZING TABLE FOR LOW PRESSURE
 (LESS THAN 2PSI) SCHED. 40 METALLIC. USING THE SIZING
 TABLE AND THE 72 FT. DEVELOPED LENGTH OF THE SYSTEM THE
 3/4-INCH BRANCH LINE FROM THE TEE TO THE 199 MBH WATER
 HEATER SHALL BE INCREASED TO MINIMUM 1-INCH, AND THE
 3/4-INCH SUPPLYING THE 120 MBH WATER HEATER SHALL BE
 INCREASED TO 1-INCH. THE 1/2-INCH PIPE TO THE DRYER IS
 SIZED ADEQUATELY.
  
 1) SHEET M-1: THE COMBUSTION AIR THROUGH THE WALL VENTS
 ARE NOT DESIGNED IN COMPLIANCE WITH SEC. G2407.5.3.1
 (304.5.3.1) FBC RES WHICH STATES EACH OPENING SHALL BE
 NOT LESS THAN 100 SQUARE INCHES. THE 6X18 INCH LOUVERS
 ALLOW ONLY 75 % FREE AREA OR 81 SQ. INCHES- SEC.
 G2407.10 (304.10). PLEASE INCREASE THE SIZE OF THE
 LOUVERS TO MEET COMPLIANCE. PLEASE NOTE A MINIMUM 1000
 CU. FT. INDOOR AIR VOLUME IS REQUIRED FOR COMBUSTION
 AIR FOR THE DRYER- 2ND REQUEST TO PROVIDE THE
 CALCULATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-12-02 Cont ID  
Sent By rwbrown Date 2022-12-02 Time 08:44 Rev Time 0.00
Received By ccole Date 2022-12-02 Time 08:26 Sent To  
Notes
2022-12-02 08:44:561ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22111092
 12/2/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-2: PROVIDE COMBUSTION AIR PLANS AND
 CALCULATIONS FOR THE RANGE, FIREPLACE, DRYER AND
 TANKLESS WATER HEATER IN THE LAUNDRY ROOM- SECS G2407.1
 FBC RES. IT APPEARS THE STANDARD METHOD OF USING INDOOR
 AIR FOR THE RANGE AND FIREPLACE CAN BE USED WHICH IS 50
 CUBIC FT. OF SPACE PER 1000 BTU, HOWEVER THE DRYER AND
 THE WATER HEATER ARE IN CONFINED SPACE AND CANNOT USE
 THIS METHOD- SEE SECS. G2407.6- G2407.11 FOR ALTERNATE
 METHODS. IF THE WATER HEATER USES A DIRECT
 VENT/COMBUSTION AIR INTAKE SYSTEM, REFER TO SECS.
 G2427.2.1, G2427.8 ITEM 3.
  
 2) P-2: PROVIDE VENTING PLANS FOR THE FIREPLACE AND
 WATER HEATER- SEC. G2427.1 FBC RES.
 A) FIREPLACE- REFER TO SECS. G2429.1.1- G2435.1 AND
 DETAIL REQUIRED VENTING SYSTEM FOR THE FIREPLACE BASED
 ON MANUFACTURER'S SPECIFICATIONS. PLEASE INCLUDE A
 DIAGRAM INDICATING TYPE AND SIZE OF VENT FLUE, FLUE RUN
 AND TERMINATION LOCATION.
 B) WATER HEATER- REFER TO SEC. G2448.1 AND PROVIDE A
 VENTING PLAN BASED ON MANUFACTURER'S SPECIFICATIONS.
 PLEASE INCLUDE A DIAGRAM INDICATING TYPE AND SIZE OF
 VENT FLUE, FLUE RUN AND TERMINATION LOCATION.
  
 3) CORRECT THE ENERGY FORM R405 TO SHOW COMPLIANCE DATA
 FOR A GAS-FIRED TANKLESS WATER HEATER, NOT ELECTRIC-
 SEC. R101.5 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By fmittner Date 2023-01-24 Time 09:19 Rev Time 0.00
Received By fmittner Date 2023-01-24 Time 09:19 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By fmittner Date 2022-12-08 Time 10:51 Rev Time 0.00
Received By fmittner Date 2022-12-08 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-06 Cont ID  
Sent By medwards Date 2023-02-06 Time 05:47 Rev Time 0.00
Received By medwards Date 2023-02-02 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-26 Cont ID  
Sent By medwards Date 2023-01-26 Time 13:38 Rev Time 0.00
Received By medwards Date 2023-01-24 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-24 Cont ID  
Sent By lmarchan Date 2023-01-24 Time 09:20 Rev Time 0.00
Received By lmarchan Date 2023-01-12 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-12 Cont ID  
Sent By cthroop Date 2022-12-12 Time 14:08 Rev Time 0.00
Received By cthroop Date 2022-11-30 Time 07:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-01-26 Cont ID  
Sent By aoliver Date 2023-01-26 Time 11:19 Rev Time 0.00
Received By aoliver Date 2023-01-24 Time 09:20 Sent To  
Notes
2023-01-26 11:19:591/26/23 NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2023-01-24 09:21:061/24/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By cthroop Date 2022-12-12 Time 10:49 Rev Time 0.00
Received By cthroop Date 2022-12-12 Time 06:05 Sent To  
Notes
2022-12-12 10:50:22IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-02-06 Cont ID  
Sent By medwards Date 2023-02-06 Time 05:46 Rev Time 0.00
Received By medwards Date 2023-02-06 Time 05:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-26 Cont ID  
Sent By medwards Date 2023-01-26 Time 13:36 Rev Time 0.00
Received By medwards Date 2023-01-26 Time 13:36 Sent To  
Notes
2023-01-26 13:37:59THE ARCHITECT MUST DIGITALLY SIGN THE MECHANICAL
 DOCUMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 08:15 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 08:15 Sent To  
Notes
2023-01-13 08:15:542ND REVIEW FMC
 PERMIT: 22111092
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS REVISION HAS A NEW POOL HOUSE. THIS WILL
 REQUIRE A SEPARATE PERMIT. FBC 107.3.5
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING FOR THE NEW
 POOL HOUSE. FEC R403.7.1
  
 3) SHOW THAT THE TRANSFER GRILLES FOR RETURN AIR FROM
 THE BEDROOM AREA WILL MEET FRC M1602.3 EXCEPTION 1. 1.5
 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCT
 ENTERING THE ROOM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By medwards Date 2022-12-01 Time 17:12 Rev Time 0.00
Received By medwards Date 2022-12-01 Time 17:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-02-03 Cont ID  
Sent By ccole Date 2023-02-03 Time 10:20 Rev Time 0.00
Received By ccole Date 2023-02-03 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-01-25 Cont ID  
Sent By ccole Date 2023-01-25 Time 10:00 Rev Time 0.00
Received By ccole Date 2023-01-25 Time 07:37 Sent To  
Notes
2023-01-25 10:24:50FBC- 2020 RES. PLUMBING REVIEW
 PERMIT- 22111092
 1/25/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2 ARE NOT DIGITALLY SIGNED AND SEALED
 BY THE ARCHITECT OF RECORD- FL. STATUTE 481.221 AND
 SEC. 61G1-16.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-01-13 Cont ID  
Sent By ccole Date 2023-01-13 Time 09:24 Rev Time 0.00
Received By ccole Date 2023-01-13 Time 08:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-02 Cont ID  
Sent By rwbrown Date 2022-12-02 Time 08:45 Rev Time 0.00
Received By ccole Date 2022-12-02 Time 08:26 Sent To  
Notes
2022-12-02 08:46:391ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22111092
 12/1/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1 & P-2: THE PLANS SHOW TWO DWELLINGS ON
 THE SAME LOT WHICH WILL REQUIRE WATER USERS TO INSTALL
 A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF
 DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL
 BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST
 PALM CROSS UTILITIES DEPARTMENT AND SECS. C, D, & E WPB
 CROSS-CONNECTION MANUAL.
  
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 2) P1 & P2: PROVIDE A CLEANOUT AT THE JUNCTION OF THE
 MAIN HOUSE BUILDING DRAIN AND SEWER- SEC. P3005.2.3 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2023-01-14 Cont ID  
Sent By cthroop Date 2023-01-14 Time 10:00 Rev Time 0.00
Received By cthroop Date 2023-01-14 Time 09:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-12-12 Cont ID  
Sent By cthroop Date 2022-12-12 Time 13:19 Rev Time 0.00
Received By cthroop Date 2022-12-12 Time 06:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-02-03 Cont ID  
Sent By ccole Date 2023-02-03 Time 09:37 Rev Time 0.00
Received By ccole Date 2023-02-03 Time 09:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-25 Cont ID  
Sent By ccole Date 2023-01-25 Time 10:11 Rev Time 0.00
Received By ccole Date 2023-01-25 Time 07:38 Sent To  
Notes
2023-01-25 10:11:55DIGITAL SIGNATURE REVIEW
 PERMIT- 22111092
 1/25/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS T1, M1, P1, & P2 ARE NOT DIGITALLY SIGNED AND
 SEALED BY THE ARCHITECT OF RECORD- FL. STATUTE 481.221
 AND SEC. 61G1-16.005 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-14 Cont ID  
Sent By cthroop Date 2023-01-14 Time 10:00 Rev Time 0.00
Received By cthroop Date 2023-01-14 Time 09:49 Sent To  
Notes
2023-01-13 08:18:33DIGITAL MECHANICAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-12 Cont ID  
Sent By cthroop Date 2022-12-12 Time 14:01 Rev Time 0.00
Received By cthroop Date 2022-12-12 Time 06:05 Sent To  
Notes
2022-12-01 17:15:21MECHANICAL DIGITAL SIGNATURE APPROVED ME

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By fmittner Date 2023-01-24 Time 09:19 Rev Time 0.00
Received By fmittner Date 2023-01-24 Time 09:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By fmittner Date 2022-12-08 Time 10:51 Rev Time 0.00
Received By fmittner Date 2022-12-08 Time 10:51 Sent To  
Notes
***NONE***