| Plan Review Stops For Permit 22111044 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2023-04-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-04-11 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-04-11 |
Time |
06:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-11 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-11 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2023-01-11 11:25:28 | 1ST BUILDING REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: VALUE WAS ADJUSTED TO $108,284 PER THE ICC | | | BUILDING VALUATION DATA. | | | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE | | | SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | | | | 3.PROVIDE THE ENERGY CALCULATIONS PER FBC EC | | | R101.5.1.1. | | | | | | 4.PROVIDE LOCATION OF ATTIC ACCESS PER R807.1.7. | | | R807.1.7 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF | | | CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO | | | ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES | | | (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30 | | | SQUARE FEET (2.8 M2). | | | | | | 5.ROOF VENTILATION | | | R806.1VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | 6.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE | | | SPEC. SHEET OF A FLUID APPLIED MEMBRANE. | | | R703.4 | | | APPROVED METAL FLASHING, VINYL FLASHING, SELF-ADHERED | | | MEMBRANES AND MECHANICALLY ATTACHED FLEXIBLE FLASHING | | | SHALL BE APPLIED SHINGLE-FASHION OR IN ACCORDANCE WITH | | | THE MANUFACTURER???S INSTRUCTIONS. | | | | | | 7. PROVIDE VENTILATION FOR THE BATHROOM PER | | | R303.3BATHROOMS. | | | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR | | | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN | | | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2), | | | ONE-HALF OF WHICH MUST BE OPENABLE. | | | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE | | | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE | | | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE | | | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST | | | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE | | | OUTDOORS. | | | | | | 8.PROVIDE SMOKE ALARMS. | | | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A | | | BUILDING. | | | SMOKE ALARMS | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-04-03 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-04-03 |
Time |
16:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-12-14 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2022-12-14 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2022-12-14 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2022-12-14 13:45:20 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. | | | NEC 215.2, 220, 408.30 | | | | | | 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON | | | MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN | | | ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315 | | | | | | 3. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT PER | | | NEC 440.14 OR IRC E4101.5 | | | DISCONNECTING MEANS IS REQUIRED TO BE LOCATED ???WITHIN | | | SIGHT FROM AND READILY ACCESSIBLE??? FROM THE | | | AIR-CONDITIONING EQUIPMENT. | | | | | | 4. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES | | | | | | 5. A ONE-LINE DIAGRAM SHOWINGS SERVICE EQUIPMENT, | | | SERVICE-ENTRANCE CONDUCTORS, SERVICE DISCONNECT, | | | SERVICE OVERCURRENT PROTECTION, MAIN POWER FEEDER, | | | FEEDER CONDUCTORS, PANELBOARDS A AND B, MAIN BONDING | | | JUMPER, AND GROUNDING ELECTRODE | | | CONDUCTOR PER NEC 230 AND 250 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-05-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-08 |
Time |
06:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-25 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-04-11 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-28 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-11 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-12 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-04-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-04-13 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-04-12 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2023-04-13 15:45:04 | NO IMPACT FEES DUE. LEM | | 2023-04-12 10:08:54 | 4/12/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-11 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-11 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2023-01-11 11:09:46 | IMPACT FEES | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-08 |
Time |
06:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-08 |
Time |
06:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-04 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-04 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2023-04-04 11:05:17 | PROVIDE AN EXHAUST FAN IN THE SHOWER/SINK AREA IN THE | | | MASTER BEDROOM AREA. FRC 303.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-21 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-21 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2022-12-21 16:36:36 | 1ST REVIEW FMC | | | PERMIT: 22111044 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW | | | ADDITION. FRC R101.5.1.1.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FRC R403.7.1 | | | | | | 3) PROVIDE AN EXHAUST FAN IN THE WATER CLOSET | | | COMPARTMENT IN THE MASTER BEDROOM AREA. FRC 303.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-03-29 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-03-29 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-03-29 |
Time |
07:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-16 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-12-16 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2022-12-16 11:15:12 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - THE DRAIN AND VENT | | | ISOMETRIC DOES NOT MATCH THE DRAINAGE LAYOUT ON THE | | | FLOOR PLAN. PLEASE CORRECT AND SUBMIT MATCING, CODE | | | COMPLIANT DRAWINGS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-11 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-11 |
Time |
07:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-05-08 |
Time |
06:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-05-08 |
Time |
06:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-04-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-04 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-04 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2023-04-04 11:10:55 | THE DRAWING SUBMITTED FOR REVIEW IS A COPY OF THE | | | ORIGINAL DRAWING. PROVIDE THE ORIGINAL DIGITALLY SIGNED | | | DRAWING. FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-01-11 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-11 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2022-12-21 16:38:32 | THE DESIGNER OF THE MECHANICAL DRAWING WILL NEED TO | | | DIGITALLY SIGN THE DRAWING. FS 471/481 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-03 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-03 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-03 |
Time |
13:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-12-21 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-12-21 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2022-12-21 11:07:23 | 12/20/2022 FAILED | | | | | | SITE PLAN SHOWS NEW ADDITION DOES NOT MEET PRIMARY | | | STRUCTURE SETBACKS REQUIREMENTS PER THE CODE FOR SF7 | | | PLEASE SHOW ALL SETBACKS ON A SURVEY OR SITE PLAN | | | | | | ALL NEW CONSTRUCTION MUST MEET THE FOLLOWING: | | | | | | MINIMUM SETBACKS FOR PRINCIPAL BUILDING. | | | A.FRONT: 25 FEET; | | | B.CORNER: 12.5 FEET; | | | C.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER | | | IS LESS; | | | D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | | | | |
|
|