Plan Review Details - Permit 22111039
Plan Review Stops For Permit 22111039
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-09 Cont ID  
Sent By pleduc Date 2023-03-09 Time   Rev Time 0.00
Received By pleduc Date 2023-03-09 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-02 Cont ID  
Sent By pleduc Date 2023-03-02 Time   Rev Time 0.00
Received By pleduc Date 2023-03-02 Time 10:08 Sent To  
Notes
2023-03-02 10:17:39FIRE PROVISO:
  
 ENSURE REQUIRED FIRE SPRINKLER PROTECTION
 IS INSTALLED WITHIN THE COOLER
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-09 Cont ID  
Sent By aoliver Date 2023-03-09 Time 11:58 Rev Time 0.00
Received By aoliver Date 2023-03-08 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-06 Cont ID  
Sent By medwards Date 2023-03-06 Time 10:16 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 10:33 Rev Time 0.00
Received By medwards Date 2023-03-01 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-03-09 Cont ID  
Sent By medwards Date 2023-03-09 Time 08:11 Rev Time 0.00
Received By medwards Date 2023-03-09 Time 08:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-03-06 Cont ID  
Sent By medwards Date 2023-03-06 Time 10:07 Rev Time 0.00
Received By medwards Date 2023-03-06 Time 10:07 Sent To  
Notes
2023-03-06 10:13:20PLEASE SUBMIT A COMPLETE REFRIGERATION DESIGN. THE
 DRAWING SHOWS WHAT APPEARS TO BE THE WALK-INS BUT IT
 DOES NOT SHOW THE LOCATION OF THE CONDENSING UNITS FOR
 THESE WALK-INS. IT ALSO DOES NOT SHOW THE REFRIGERATION
 PIPING FOR EACH WALK-IN. THIS ALL MUST BE SUBMITTED FOR
 THE PROJECT REVIEW. FMC 1102.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 10:30 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 10:28 Sent To  
Notes
2023-03-02 10:30:03PROVIDE A DRAWING SHOWING THE LOCATIONS OF THE WALK-INS
 AND THE LOCATIONS OF THE CONDENSING UNITS FOR THE
 WALK-INS. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-11-23 Cont ID  
Sent By aoliver Date 2022-11-23 Time 11:21 Rev Time 0.00
Received By aoliver Date 2022-11-23 Time 11:21 Sent To  
Notes
2022-11-23 11:21:19PRIVATE PROVIDER INSPECTIONS ONLY TEW & TAYLOR

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 10:33 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 10:33 Sent To  
Notes
***NONE***