Plan Review Details - Permit 22111013
Plan Review Stops For Permit 22111013
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-11-30 Cont ID  
Sent By cpuell Date 2022-11-30 Time 07:37 Rev Time 0.00
Received By cpuell Date 2022-11-30 Time 07:37 Sent To  
Notes
2022-11-30 07:37:36ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-01-12 Cont ID  
Sent By aoliver Date 2023-01-12 Time 11:16 Rev Time 0.00
Received By aoliver Date 2023-01-12 Time 11:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-12-27 Cont ID  
Sent By shill Date 2022-12-27 Time 19:48 Rev Time 0.00
Received By shill Date 2022-12-27 Time 19:48 Sent To  
Notes
2022-12-27 19:48:59PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-12-27 Cont ID  
Sent By shill Date 2022-12-27 Time 19:47 Rev Time 0.00
Received By shill Date 2022-12-27 Time 19:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-05 Cont ID  
Sent By jleahy Date 2023-01-05 Time 09:25 Rev Time 0.00
Received By jleahy Date 2023-01-05 Time 09:25 Sent To  
Notes
2023-01-05 09:26:49SEE PERMIT 22120866 FOR ELECTRICAL DEMO.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By mpeterso Date 2022-12-08 Time 08:28 Rev Time 0.00
Received By mpeterso Date 2022-12-08 Time 08:09 Sent To  
Notes
2022-12-08 08:31:2712/8/22 SENT EMAIL REQUESTING ELECTRICAL APPLICATION.
 MP

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By pleduc Date 2023-01-11 Time   Rev Time 0.00
Received By pleduc Date 2023-01-11 Time 11:19 Sent To  
Notes
2023-01-11 11:24:01FIRE PROVISO:
  
 THE LIFE SAFETY FEATURES AND EXITS FOR THE OCCUPANTS
 SHALL BE MAINTAINED THROUGHOUT THE DEMO AND
 RECONSTRUCTION PERIODS.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-12-05 Cont ID  
Sent By pleduc Date 2022-12-05 Time   Rev Time 0.00
Received By pleduc Date 2022-12-05 Time 11:33 Sent To  
Notes
2022-12-05 11:40:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE PREVIOUS INDICATIONS THAT THIS ADDRESS
 UNDER WENT AN OCCUPANCY CLASSIFICATION CHANGE TO
 EDUCATIONAL.
  
 THERE ARE ALSO INDICATIONS THAT THISS BUILDING IS
 OCCUPIED ON THE 1ST FLOOR BY STUDENTS AND TEACHERS PER
 THE OCCUPANCY CLASSIFICATION CHANGE.
  
 THERE ARE NO INDICATIONS ON THIS PRPOSED DEMO PERMIT OF
 THE INTENTIONS OR NON-INTENTIONS TO HAVE THIS BUILDING
 OCCUPOED DURING DEMO NOR RECONSTRUCTION.
  
 PER NFPA
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS
 AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND
 APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN
 SECTION 1.14.
  
  
 PLEASE REVIEW AND PROVIDED A DETAILED NARRATIVE
 EXXPLAINING THE INTENT TO OCCUPY OR NOT ANF INCLUEDE
 LIFE SAFETY DETAILS TO ENSURE THE OCUPANCT ARE PROTECED
 AT ALL TIMES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-12 Cont ID  
Sent By aoliver Date 2023-01-12 Time 11:16 Rev Time 0.00
Received By aoliver Date 2023-01-10 Time 17:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-27 Cont ID  
Sent By shill Date 2022-12-27 Time 19:49 Rev Time 0.00
Received By shill Date 2022-11-29 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By mpeterso Date 2022-12-08 Time 08:35 Rev Time 0.00
Received By mpeterso Date 2022-12-08 Time 08:35 Sent To  
Notes
***NONE***