Plan Review Details - Permit 22111001
Plan Review Stops For Permit 22111001
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2023-01-19 Cont ID  
Sent By cpuell Date 2023-01-19 Time 10:44 Rev Time 0.00
Received By cpuell Date 2023-01-19 Time 10:44 Sent To  
Notes
2023-01-19 10:44:52ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2023-01-11 Cont ID  
Sent By cpuell Date 2023-01-11 Time 10:14 Rev Time 0.00
Received By cpuell Date 2023-01-11 Time 10:14 Sent To  
Notes
2023-01-11 10:16:01PERMIT APPLICATION AND COVER SHEET UPDATED HOWEVER TO
 THE INCORRECT ADDRESS, THE CORRECT ADDRESS FOR THIS
 PROJECT IS 931 VILLAGE BLVD 908. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESSING ISSUES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-11-30 Cont ID  
Sent By cpuell Date 2022-11-30 Time 07:43 Rev Time 0.00
Received By hmoser Date 2022-11-30 Time 07:43 Sent To  
Notes
2022-11-30 07:46:55THE APPLICATION FORM LIST THE ADDRESS AS 971 VILLAGE
 BLVD HOWEVER THE PLANS LIST THE ADDRESS AS 931 VILLAGE
 BLVD UNIT 908 PLEASE PROVIDE A SITE PLAN OR AERIAL MAP
 SHOWING THE EXACT LOCATION TO BE WORKED ON SO THAT THE
 ADDRESS CAN BE VERIFIED. PLEASEL RESPONSED TO
 [email protected] OR CALL 561-805-6659.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 13:00 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By jwitmer Date 2023-01-24 Time 07:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-24 07:33:35BUILDING PROVISO:
 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR,
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL USED IN
 SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 13:15 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-21 13:15:40BUILDING PROVISO:
 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR,
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL USED IN
 SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-25 Cont ID  
Sent By mpeterso Date 2023-01-25 Time 13:09 Rev Time 0.00
Received By mpeterso Date 2023-01-25 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-12-14 Cont ID  
Sent By mpeterso Date 2022-12-14 Time 10:28 Rev Time 0.00
Received By mpeterso Date 2022-12-14 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-06-26 Cont ID  
Sent By mpeterso Date 2023-06-26 Time 13:34 Rev Time 0.00
Received By mpeterso Date 2023-06-26 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-19 Cont ID  
Sent By cwalker Date 2023-01-19 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-11 Cont ID  
Sent By cwalker Date 2023-01-11 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-12-01 Cont ID  
Sent By cwalker Date 2022-12-01 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-12-01 10:39:11FIRE PROVISO COMMENTS:
  
 (1) DOOR LOCKING ARRANGEMENTS SHALL COMPLY WITH THE
 FOLLOWING:
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY
 FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE
 EGRESS SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO
 HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED
 THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43
 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 (2) PORTABLE FIRE EXTINGUISHERS SHALL BE OF THE
 APPROPRIATE SIZE AND TYPE FOR THE HAZARD AND MOUNTED IN
 A FIRE CODE COMPLIANT MANNER.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-03 Cont ID  
Sent By medwards Date 2023-02-03 Time 10:33 Rev Time 0.00
Received By medwards Date 2023-02-01 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-25 Cont ID  
Sent By mpeterso Date 2023-01-25 Time 13:09 Rev Time 0.00
Received By mpeterso Date 2023-01-18 Time 10:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-13 Cont ID  
Sent By lmarchan Date 2023-01-13 Time 12:50 Rev Time 0.00
Received By lmarchan Date 2023-01-10 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2022-11-29 Time 06:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2022-12-21 Time 13:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-02-03 Cont ID  
Sent By medwards Date 2023-02-03 Time 10:33 Rev Time 0.00
Received By medwards Date 2023-02-03 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-19 Cont ID  
Sent By medwards Date 2023-01-19 Time 15:03 Rev Time 0.00
Received By medwards Date 2023-01-19 Time 15:03 Sent To  
Notes
2023-01-19 15:04:031ST REVIEW FMC
 PERMIT: 22111001
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LS-1 INDICATES THERE IS THE KITCHEN PREP, STORAGE
 AND SALES AREA FOR CUSTOMERS. PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR EACH INCLUDING THE EXHAUST FOR THE
 KITCHEN PREP AREA. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 2) 2ND ATTEMPT, PLEASE PROVIDE THE MENU FOR THIS
 RESTAURANT TO SHOW WHY NO HOOD IS REQUIRED. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 11:07 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 11:07 Sent To  
Notes
2023-01-13 11:07:452ND REVIEW FMC
 PERMIT: 22111001
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE. THE OCCUPANCY CLASSIFICATION FROM TABLE
 403.3.1.1 MUST BE THE ONE THAT MOST RESEMBLES THE USE
 OF THE SPACES AND YOU WILL NEED TO NAME THE SPACE PER
 THE OCCUPANCY CLASSIFICATION CHOSEN FROM TABLE
 403.3.1.1.
  
 2) PROVIDE A MENU FOR THIS TENANT SPACE. IS THERE TO BE
 ANY COOKING OF MEATS OR OTHER FOODS THAT WOULD PRODUCE
 COOKING VAPORS AND RESIDUES? FMC 507.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By hmoser Date 2022-12-13 Time 14:37 Rev Time 0.00
Received By hmoser Date 2022-12-13 Time 13:42 Sent To  
Notes
2022-12-13 14:50:14PLAN DENIED
 1) REFER TO SECTION 1204 TEMPERATURE CONTROL
 2020 FBC.
 2) REFER TO TABLE 403.3.1.1 MINIMUM VENTILATION RATES
 FOR KITCHEN, CUSTOMER AREA AND DININD AREA IF THERE
 IS ONE. FBC (M)
 WALK IN COOLERS AND KITCHEN HOODS REQUIRE SEPARATE
 APPLICATION PLANS AND PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-01-31 Cont ID  
Sent By rwbrown Date 2023-01-31 Time 15:16 Rev Time 0.00
Received By rwbrown Date 2023-01-31 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-01-19 Cont ID  
Sent By rwbrown Date 2023-01-19 Time 15:01 Rev Time 0.00
Received By rwbrown Date 2023-01-19 Time 15:01 Sent To  
Notes
2023-01-19 15:02:173RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. PLEASE LET ME KNOW WHEN THE PERMIT FOR THE GREASE
 INTERCEPTOR HAS BEEN APPLIED FOR.
 2017 WPB AMENDS 105.1 - THE GREASE INTERCEPTOR REQUIRES
 IT'S OWN SEPARATE PERMIT. IT IS REQUIRED TO BE
 SUBMITTED BEFORE THIS COMMENT CAN BE RELEASED. IF
 NECESSARY, YOU CAN SUBMIT A PERMIT APPLICATION FOR THE
 GREASE TRAP WITH THE CONTRACTOR LISTED AS "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, RESPOND TO THIS COMMENT IN A
 NARRATIVE AND I CAN RELEASE THE COMMENT.
  
 4. DONE
  
 5. DONE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-12 Cont ID  
Sent By rwbrown Date 2023-01-12 Time 11:08 Rev Time 0.00
Received By rwbrown Date 2023-01-12 Time 11:08 Sent To  
Notes
2023-01-12 11:08:041ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. PLEASE LET ME KNOW WHEN THE PERMIT FOR THE GREASE
 INTERCEPTOR HAS BEEN APPLIED FOR.
 2017 WPB AMENDS 105.1 - THE GREASE INTERCEPTOR REQUIRES
 IT'S OWN SEPARATE PERMIT. IT IS REQUIRED TO BE
 SUBMITTED BEFORE THIS COMMENT CAN BE RELEASED. IF
 NECESSARY, YOU CAN SUBMIT A PERMIT APPLICATION FOR THE
 GREASE TRAP WITH THE CONTRACTOR LISTED AS "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, RESPOND TO THIS COMMENT IN A
 NARRATIVE AND I CAN RELEASE THE COMMENT.
  
 4. DONE
  
 5. DONE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-05 Cont ID  
Sent By rwbrown Date 2022-12-05 Time 14:35 Rev Time 0.00
Received By rwbrown Date 2022-12-05 Time 14:35 Sent To  
Notes
2022-12-05 15:02:071ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.8 - DIRECT CONNECTION - THE
 DISCHARGE PIPING FROM A GREASE INTERCEPTOR SHALL BE
 DIRECTLY CONNECTED TO THE SANITARY DRAINAGE SYSTEM.
  
 2. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE SUBMIT THE
 DETAILS FOR THE GREASE INTERCEPTOR.
  
 3. 2017 WPB AMENDS 105.1 - THE GREASE INTERCEPTOR
 REQUIRES IT'S OWN SEPARATE PERMIT. IT IS REQUIRED TO BE
 SUBMITTED BEFORE THIS COMMENT CAN BE RELEASED. IF
 NECESSARY, YOU CAN SUBMIT A PERMIT APPLICATION FOR THE
 GREASE TRAP WITH THE CONTRACTOR LISTED AS "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, RESPOND TO THIS COMMENT IN A
 NARRATIVE AND I CAN RELEASE THE COMMENT.
  
 4. 2020 FPC 2020 FPC 1003.3.1 - THE FLOOR DRAIN AND THE
 SINGLE COMPARTMENT SINK IN THE FOOD PREP AREA IS
 SUBJECT TO FAT/OIL/GREASE WASTE AND SHOULD BE CONNECTED
 TO THE GREASE TRAP. IF YOU FEEL THE SINGLE COMPARTMENT
 SINK DOES NOT NEED TO GO TO GREASE WASTE, YOU CAN
 DETAIL IT'S USE.
  
 5. 2020 FPC 2020 FPC 607.1.1 - HOT WATER DELIVERY - PER
 THIS SECTION, THE THERMOSTAT ON THE WATER HEATER CANNOT
 SERVE AS THE LIMITING DEVICE FOR HOT OR TEMPERED WATER
 DELIVERY. A MIXING DEVICE MUST LIMIT THE TEMPERATURE.
 THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST BE
 INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC 613.1.
 THIS IS IN ADDITION TO THE REQUIREMENTS FOR PUBLIC
 HANDWASHING PROTECTION FOR TEMPERED WATER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-24 Cont ID  
Sent By jwitmer Date 2023-01-24 Time 07:34 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-13 11:08:19MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-12-14 Cont ID  
Sent By mpeterso Date 2022-12-14 Time 10:28 Rev Time 0.00
Received By mpeterso Date 2022-12-14 Time 10:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-01-20 Cont ID  
Sent By vbroglia Date 2023-01-20 Time 14:08 Rev Time 0.00
Received By vbroglia Date 2023-01-20 Time 14:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-12-19 Cont ID  
Sent By vbroglia Date 2022-12-19 Time 13:33 Rev Time 0.00
Received By vbroglia Date 2022-12-19 Time 13:33 Sent To  
Notes
***NONE***