Plan Review Details - Permit 22110893
Plan Review Stops For Permit 22110893
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-11-30 Cont ID  
Sent By cpuell Date 2022-11-30 Time 07:52 Rev Time 0.00
Received By cpuell Date 2022-11-30 Time 07:52 Sent To  
Notes
2022-11-30 08:19:44PLEASE CONTACT [email protected] ONCE ZONING
 APPROVES THE ADDITION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 14:33 Sent To  
Notes
2022-12-12 16:44:16NEW GARAGE WITH GUEST UNIT ABOVE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) WIND DESIGN SHOWN USING EXPOSURE "C" - WITH THE
 LOCATION OF THE PROPERTY NEXT TO THE WATERWAY EXPOSURE
 "D" SHOULD BE USED - FBC R301.2.1.4.3 EXPOSURE D SHALL
 ALSO APPLY WHERE THE GROUND SURFACE ROUGHNESS
 IMMEDIATELY UPWIND OF THE SITE IS B OR C, AND THE SITE
 IS WITHIN A DISTANCE OF 600 FEET (183 M) OR 20 TIMES
 THE BUILDING HEIGHT, WHICHEVER IS GREATER, FROM AN
 EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS
 SENTENCE.
  
 2) PLEASE SHOW THE REQUIRED ROOF CLADDING WIND
 PRESSURES PER FBC FIGURE R301.2(7)
  
 3) PLEASE PROVIDE A SOIL REPORT - FBC R401.4
  
 4) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL15180.7
  
 5) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 6) PLEASE PROVIDE DETAILS FOR THE GUARD RAILING FBC R
 312
  
 7) PLEASE PROVIDE DETAILS FOR THE STAIR HAND RAILS FBC
 R311.7.8
  
 8) FBC R311.7.5.1 OPEN RISERS ARE PERMITTED PROVIDED
 THAT THE OPENINGS LOCATED MORE THAN 30 INCHES (762 MM),
 AS MEASURED VERTICALLY, TO THE FLOOR OR GRADE BELOW DO
 NOT PERMIT THE PASSAGE OF A 4-INCH-DIAMETER (102 MM)
 SPHERE.
  
 9) FBC R318.5 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 10) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 11) A SEPARATE PERMIT IS REQUIRED FOR THE SITEWALL.
  
 12) STRUCTURAL DRAWINGS NEED TO BE SIGNED AND SEALED BY
 THE DESIGNER FBC 107 - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By mpeterso Date 2022-12-14 Time 11:03 Rev Time 0.00
Received By mpeterso Date 2022-12-14 Time 11:03 Sent To  
Notes
2022-12-14 11:05:05ELECTRIC REVIEW FAILED
 1) TWO ELECTRIC PLANS ARE SUBMITTED. PLEASE SUBMITT
 ONLY THE APPLICABLE ELECTRIC PLAN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-14 Cont ID  
Sent By mpeterso Date 2022-12-14 Time 11:05 Rev Time 0.00
Received By mpeterso Date 2022-11-29 Time 08:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 16:44 Sent To  
Notes
2022-12-12 16:44:52PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-13 Cont ID  
Sent By hmoser Date 2022-12-13 Time 13:34 Rev Time 0.00
Received By hmoser Date 2022-12-13 Time 13:34 Sent To  
Notes
2022-12-13 13:40:12PLAN DENIED
 1) NO AIR CONDITIONING PLAN SUBMITED.
 2) REFER TO SECTION M1401.3 EQUIPMENT AND
 APPLIANCE SIZING. FBC (R)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-12-05 Cont ID  
Sent By rwbrown Date 2022-12-05 Time 14:03 Rev Time 0.00
Received By rwbrown Date 2022-12-05 Time 14:03 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 16:45 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 16:45 Sent To  
Notes
2022-12-12 16:45:21SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 16:55 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 16:55 Sent To  
Notes
2022-12-12 16:56:32SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By kdefranc Date 2022-12-08 Time 11:42 Rev Time 0.00
Received By kdefranc Date 2022-12-08 Time 11:18 Sent To  
Notes
2022-12-08 11:41:5212/8/22 ??? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. PLEASE SUBMIT A REVISED APPLICATION REMOVING ANY
 REFERENCE/INDICATION/DEMONSTRATION OF AN ACCESSORY
 APARTMENT AND DWELLING UNIT ACCORDING TO THE
 DEFINITIONS IN THE CITY???S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR) SECTION 94-611.
 2. PLEASE IDENTIFY/INDICATE THE HEIGHT OF THE PROPOSED
 FENCE AND GATE ON THE LOWER FLOOR PLAN (SHEET A-1 OF
 11) ACCORDING TO THE ZLDR SUBSECTION 94-302(B)(1).
 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE SETBACK
 DIMENSIONS OF THE PROPOSED MINI-SPLIT A/C UNIT ON THE
 LOWER FLOOR PLAN (SHEET A-1 OF 11) ACCORDING TO THE
 ZLDR SUBSECTION 94-305(B)(4).
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  