Plan Review Details - Permit 22110878
Plan Review Stops For Permit 22110878
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 09:05 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-26 Cont ID  
Sent By rmcphers Date 2023-01-26 Time 13:15 Rev Time 0.00
Received By rmcphers Date 2023-01-26 Time 13:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-01-12 Cont ID  
Sent By rmcphers Date 2023-01-12 Time 13:55 Rev Time 0.00
Received By rmcphers Date 2023-01-12 Time 13:55 Sent To  
Notes
2023-01-12 13:55:57SEE PERMIT 22080820

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 09:06 Sent To  
Notes
2022-12-08 09:13:03SEE PERMIT 22080820

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-02-02 Cont ID  
Sent By mpeterso Date 2023-02-02 Time 08:08 Rev Time 0.00
Received By mpeterso Date 2023-02-02 Time 08:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-20 Cont ID  
Sent By mpeterso Date 2023-01-20 Time 12:52 Rev Time 0.00
Received By mpeterso Date 2023-01-20 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By mpeterso Date 2022-12-19 Time 15:43 Rev Time 0.00
Received By mpeterso Date 2022-12-19 Time 15:43 Sent To  
Notes
2022-12-19 15:44:31ELECTRIC REVIEW FAILED
 1) PLEASE INDICATE COMPLIANCE WITH NEC 210.62 FOR SHOW
 WINDOW RECEPTACLES IN COMMERCIAL SPACES.
 2) PLEASE INDICATE THE REQUIRED SIGN LIGHTING OUTLETS
 REQUIRED PER NEC 600.5 FOR EACH COMMERCIAL SPACE
 3) PLEASE INDICATE COMPLIANCE WITH THE F.B.C.E.C.
 C405.2 FOR LIGHTING CONTROLS IN COMMERCIAL SPACES
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-01-26 Cont ID  
Sent By pleduc Date 2023-01-26 Time   Rev Time 0.00
Received By pleduc Date 2023-01-26 Time 15:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-01-04 Cont ID  
Sent By pleduc Date 2023-01-04 Time   Rev Time 0.00
Received By pleduc Date 2023-01-04 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-11-22 Cont ID  
Sent By pleduc Date 2022-11-22 Time   Rev Time 0.00
Received By pleduc Date 2022-11-22 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status P Date 2023-03-01 Cont ID  
Sent By medwards Date 2023-03-01 Time 11:12 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-27 Cont ID  
Sent By lmarchan Date 2023-02-27 Time 09:41 Rev Time 0.00
Received By lmarchan Date 2023-02-10 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-02 Cont ID  
Sent By mpeterso Date 2023-02-02 Time 08:08 Rev Time 0.00
Received By mpeterso Date 2023-01-25 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-01-20 Cont ID  
Sent By mpeterso Date 2023-01-20 Time 12:52 Rev Time 0.00
Received By mpeterso Date 2023-01-03 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-12-19 Cont ID  
Sent By mpeterso Date 2022-12-19 Time 15:44 Rev Time 0.00
Received By mpeterso Date 2022-11-21 Time 08:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By lmarchan Date 2023-03-03 Time 11:02 Rev Time 0.00
Received By lmarchan Date 2023-03-02 Time 09:57 Sent To  
Notes
2023-03-03 11:02:22NO IMPACT FEES DUE. LEM
2023-03-02 09:57:463/2/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 09:15 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 09:15 Sent To  
Notes
2022-12-08 09:16:33PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-03-01 Cont ID  
Sent By medwards Date 2023-03-01 Time 11:11 Rev Time 0.00
Received By medwards Date 2023-03-01 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-02-14 Cont ID  
Sent By medwards Date 2023-02-14 Time 16:05 Rev Time 0.00
Received By medwards Date 2023-02-14 Time 16:05 Sent To  
Notes
2023-02-14 16:07:46SEE COMMENTS FOR PERMIT 22080820 AS THE DRAWINGS ARE
 SUBMITTED IN THAT PERMIT SUBMITTAL.
  
 4TH REVIEW FMC
 PERMIT: 22080820
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS SUBMITTED ARE FOR UNIT 434
 BUT THIS PERMIT APPLICATION IS FOR UNIT 432. PROVIDE
 THE CALCULATIONS FOR UNIT 432. FBC 107.3.5
  
 2) ACCORDING TO THE MECHANICAL CONTRACTOR THAT HAD
 SUBMITTED THE ORIGINAL DRAWINGS, THESE TENANT SPACES
 WERE TO BE A CHANGE OF USE FROM STORAGE TO A PET
 GROOMER. THE COVER SHEET SUBMITTED STATES THIS IS STILL
 A STORAGE. PLEASE EXPLAIN.
  
 3) ARE THE RTU???S LIKE FOR LIKE CHANGE OUTS? IF NOT
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 REQUESTED IN PREVIOUS REVIEW COMMENTS. FEC C403.2.1
  
 4) PROVIDE A SITE PLAN SHOWING THE NEW BATH EXHAUST FAN
 TERMINATION LOCATION WILL MEET THE 10 FEET REQUIREMENTS
 FROM THE PROPERTY LINE. FMC 501.3.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 12:49 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 12:49 Sent To  
Notes
2023-01-30 12:50:39SUBMIT THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 REQUESTED IN PREVIOUS REVIEW CYCLES.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-01-17 Cont ID  
Sent By medwards Date 2023-01-17 Time 06:58 Rev Time 0.00
Received By medwards Date 2023-01-17 Time 06:58 Sent To  
Notes
2023-01-17 06:59:47STILL MISSING THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By medwards Date 2022-12-19 Time 07:21 Rev Time 0.00
Received By medwards Date 2022-12-19 Time 07:21 Sent To  
Notes
2022-12-19 07:21:321ST REVIEW FMC
 PERMIT: 22110878
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS DO NOT SHOW THE DOORS.
 PLEASE PROVIDE ENERGY CALCULATIONS AND MECHANICAL
 EQUIPMENT SIZING CALCULATIONS THAT INCLUDE THE DOORS.
 FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-02-13 Cont ID  
Sent By ccole Date 2023-02-13 Time 10:53 Rev Time 0.00
Received By ccole Date 2023-02-13 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-01-27 Cont ID  
Sent By ccole Date 2023-01-27 Time 16:24 Rev Time 0.00
Received By ccole Date 2023-01-27 Time 15:29 Sent To  
Notes
2023-01-27 16:25:413RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22110878 UNIT #434
 1/27/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1 NEW DETAIL 1: THE FIXTURE DRAIN FOR THE
 SERVICE SINK SHALL NOT CONNECT TO THE HORIZONTAL WET
 VENT FOR THE NEW BATHROOM- SEC. 912.1 FBC P. THE DRAIN
 SHALL CONNECT DOWNSTREAM OF THE WET VENT.
  
 2) P-3 REVISED DETAIL 1: PROVIDE A MEANS OF LIMITING
 THE HOT WATER TEMPERATURE DELIVERY FROM THE SERVICE
 SINK- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-01-10 Cont ID  
Sent By ccole Date 2023-01-10 Time 17:06 Rev Time 0.00
Received By ccole Date 2023-01-10 Time 11:36 Sent To  
Notes
2023-01-10 17:08:552ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22110878 UNIT #434
 1/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 PRINTED BELOW
 STILL EXISTS. THE REQUIRED SERVICE SINK IN UNIT 434 WAS
 NOT PROVIDED.
  
 1) SHEET A-1.2: PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES. THE PLAN SHOWS COMPLIANCE FOR THE NUMBER OF
 WATER CLOSETS AND LAVATORIES, AND DRINKING FOUNTAINS
 ARE NOT REQUIRED FOR OCCUPANT LOADS OF 15 AND UNDER,
 HOWEVER A SERVICE SINK IS REQUIRED. PLEASE REVISE THE
 PLANS TO SHOW THE SINK LOCATION AND PLUMBING PIPING
 DETAILS- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-12 Cont ID  
Sent By ccole Date 2022-12-12 Time 16:58 Rev Time 0.00
Received By ccole Date 2022-12-12 Time 15:46 Sent To  
Notes
2022-12-12 16:59:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22110878
 12/12/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1.2: PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES. THE PLAN SHOWS COMPLIANCE FOR THE NUMBER OF
 WATER CLOSETS AND LAVATORIES, AND DRINKING FOUNTAINS
 ARE NOT REQUIRED FOR OCCUPANT LOADS OF 15 AND UNDER,
 HOWEVER A SERVICE SINK IS REQUIRED. PLEASE REVISE THE
 PLANS TO SHOW THE SINK LOCATION AND PLUMBING PIPING
 DETAILS- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-02-13 Cont ID  
Sent By ccole Date 2023-02-13 Time 11:01 Rev Time 0.00
Received By ccole Date 2023-02-13 Time 11:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2023-01-26 Cont ID  
Sent By rmcphers Date 2023-01-26 Time 13:15 Rev Time 0.00
Received By rmcphers Date 2023-01-26 Time 13:15 Sent To  
Notes
2023-01-26 13:15:56SEE PERMIT 22080820

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2023-01-12 Cont ID  
Sent By rmcphers Date 2023-01-12 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2023-01-12 Time 13:56 Sent To  
Notes
2023-01-12 13:56:26SEE PERMIT 22080820

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-12-08 Cont ID  
Sent By rmcphers Date 2022-12-08 Time 09:16 Rev Time 0.00
Received By rmcphers Date 2022-12-08 Time 09:16 Sent To  
Notes
2022-12-08 09:17:45FOR PLANS SEE PERMIT 22080820

Review Stop Z ZONING
Rev No 4 Status P Date 2023-02-27 Cont ID  
Sent By kdefranc Date 2023-02-27 Time 12:04 Rev Time 0.00
Received By kdefranc Date 2023-02-24 Time 12:04 Sent To  
Notes
2023-02-24 12:04:382/27/23 ??? PASSED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. THE VALUE OF THE CONSTRUCTION ($150,000.00) EXCEEDS
 50% OF THE STRUCTURES??? VALUE ($201,273.00) ACCORDING
 TO THE PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SUBSECTION 94-441(B) OF THE
 CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE IN
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. THEREFORE, PLEASE SUBMIT A
 LANDSCAPE PERMIT APPLICATION OR A LANDSCAPE CONDITIONAL
 APPROVAL PERMIT FORM. [SATISFIED]
 2. PLEASE CORRECTLY MATCH THE BUILDING UNIT #
 (NUMERICAL STREET ADDRESS) INDICATIONS FOR THE
 CORRESPONDING TWO BUILDINGS ON THE ELEVATIONS (SHEETS
 A-2 AND A-2.1). [SATISFIED]
 3. PLEASE IDENTIFY/INDICATE THE MAXIMUM HEIGHT (TOP) OF
 THE TWO BUILDINGS ON THE ELEVATIONS (SHEETS A-2 AND
 A-2.1). [SATISFIED]
 4. PLEASE REVISE THE ELEVATIONS (SHEET A-2) TO
 DEMONSTRATE THE PROPOSED IMPROVEMENTS IN COMPLIANCE
 WITH THE MINIMUM STOREFRONT TRANSPARENT CLEAR GLAZED
 AREA STANDARD ACCORDING TO THE ZLDR SUBSECTION
 94-209(2)(J)(1)(H)(I)(4). [SATISFIED PER PLANNING AND
 ZONING ADMINISTRATOR, ANGELLA JONES-VANN???S DIRECTION]
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-31 Cont ID  
Sent By kdefranc Date 2023-01-31 Time 16:32 Rev Time 0.00
Received By kdefranc Date 2023-01-31 Time 16:31 Sent To  
Notes
2023-01-31 16:32:081/31/23 ??? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. THE VALUE OF THE CONSTRUCTION ($150,000.00) EXCEEDS
 50% OF THE STRUCTURES??? VALUE ($201,273.00) ACCORDING
 TO THE PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SUBSECTION 94-441(B) OF THE
 CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE IN
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. THEREFORE, PLEASE SUBMIT A
 LANDSCAPE PERMIT APPLICATION OR A LANDSCAPE CONDITIONAL
 APPROVAL PERMIT FORM. [SATISFIED]
 2. PLEASE CORRECTLY MATCH THE BUILDING UNIT #
 (NUMERICAL STREET ADDRESS) INDICATIONS FOR THE
 CORRESPONDING TWO BUILDINGS ON THE ELEVATIONS (SHEETS
 A-2 AND A-2.1). [SATISFIED]
 3. PLEASE IDENTIFY/INDICATE THE MAXIMUM HEIGHT (TOP) OF
 THE TWO BUILDINGS ON THE ELEVATIONS (SHEETS A-2 AND
 A-2.1). [SATISFIED]
 4. PLEASE REVISE THE ELEVATIONS (SHEET A-2) TO
 DEMONSTRATE THE PROPOSED IMPROVEMENTS IN COMPLIANCE
 WITH THE MINIMUM STOREFRONT TRANSPARENT CLEAR GLAZED
 AREA STANDARD ACCORDING TO THE ZLDR SUBSECTION
 94-209(2)(J)(1)(H)(I)(4). [NOT SATISFIED]
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 2 Status F Date 2023-01-11 Cont ID  
Sent By kdefranc Date 2023-01-11 Time 11:59 Rev Time 0.00
Received By kdefranc Date 2023-01-11 Time 11:58 Sent To  
Notes
2023-01-11 11:59:101/11/23 ??? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. THE VALUE OF THE CONSTRUCTION ($150,000.00) EXCEEDS
 50% OF THE STRUCTURES??? VALUE ($201,273.00) ACCORDING
 TO THE PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SUBSECTION 94-441(B) OF THE
 CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE IN
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. THEREFORE, PLEASE SUBMIT A
 LANDSCAPE PERMIT APPLICATION OR A LANDSCAPE CONDITIONAL
 APPROVAL PERMIT FORM. [NOT SATISFIED]
 2. PLEASE CORRECTLY MATCH THE BUILDING UNIT #
 (NUMERICAL STREET ADDRESS) INDICATIONS FOR THE
 CORRESPONDING TWO BUILDINGS ON THE ELEVATIONS (SHEETS
 A-2 AND A-2.1). [NOT SATISFIED]
 3. PLEASE IDENTIFY/INDICATE THE MAXIMUM HEIGHT (TOP) OF
 THE TWO BUILDINGS ON THE ELEVATIONS (SHEETS A-2 AND
 A-2.1). [SATISFIED]
 4. PLEASE REVISE THE ELEVATIONS (SHEETS A-2 AND A2.1)
 TO DEMONSTRATE THE PROPOSED IMPROVEMENTS IN COMPLIANCE
 WITH THE MINIMUM STOREFRONT TRANSPARENT CLEAR GLAZED
 AREA STANDARD ACCORDING TO THE ZLDR SUBSECTION
 94-209(2)(J)(1)(H)(I)(4). [NOT SATISFIED]
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-12-09 Cont ID  
Sent By kdefranc Date 2022-12-09 Time 10:58 Rev Time 0.00
Received By kdefranc Date 2022-12-09 Time 10:58 Sent To  
Notes
2022-12-09 10:58:2712/9/22 ??? FAILED
  
 REVIEW COMMENTS TO BE ADDRESSED:
 1. THE VALUE OF THE CONSTRUCTION ($150,000.00) EXCEEDS
 50% OF THE STRUCTURES??? VALUE ($201,273.00) ACCORDING
 TO THE PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SUBSECTION 94-441(B) OF THE
 CITY???S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE IN
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. THEREFORE, PLEASE SUBMIT A
 LANDSCAPE PERMIT APPLICATION OR A LANDSCAPE CONDITIONAL
 APPROVAL PERMIT FORM.
 2. PLEASE CORRECTLY MATCH THE BUILDING UNIT #
 (NUMERICAL STREET ADDRESS) INDICATIONS FOR THE
 CORRESPONDING TWO BUILDINGS ON THE ELEVATIONS (SHEETS
 A-2 AND A-2.1).
 3. PLEASE IDENTIFY/INDICATE THE MAXIMUM HEIGHT (TOP) OF
 THE TWO BUILDINGS ON THE ELEVATIONS (SHEETS A-2 AND
 A-2.1).
 4. PLEASE REVISE THE ELEVATIONS (SHEETS A-2 AND A2.1)
 TO DEMONSTRATE THE PROPOSED IMPROVEMENTS IN COMPLIANCE
 WITH THE MINIMUM STOREFRONT TRANSPARENT CLEAR GLAZED
 AREA STANDARD ACCORDING TO THE ZLDR SUBSECTION
 94-209(2)(J)(1)(H)(I)(4).
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  