| 2022-12-13 09:56:27 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT THE ACTUAL TEST REPORTS FOR SOUND AND FLAME |
| | SPREAD FOR THE SOUND UNDERLAYMENT FOR A 6" THICK SLAB |
| | WITHOUT A CEILING BELOW IT. |
| | |
| | 2) SUBMIT THE FIRE TEST REPORT FOR THE LAMINATE FLOOR |
| | COVERING. |
| | |
| | PROVIDE THE FOLLOWING INFORMATION FOR FLOORING |
| | SUBMITTALS: |
| | |
| | 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. |
| | DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS |
| | 107.2.1. |
| | 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. |
| | 3. TYPE OF PROPOSED (HARD) FINISH FLOOR COVERING (TILE, |
| | LAMINATE, WOOD, MARBLE, ETC.). |
| | 4. STATED VALUE OF WORK. |
| | 5. DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS |
| | OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED |
| | CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL). |
| | 6. PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT. |
| | 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON |
| | THE EXISTING SITE CONDITIONS. |
| | 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: |
| | E-84, E-90 & E-492. |
| | 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | (UNLESS SUBMITTING ELECTRONICALLY) |
| | |
| | SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND |
| | INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED |
| | FOR THE APPLICABLE CONSTRUCTION CONDITIONS. |
| | |
| | FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | |
| | SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND |
| | INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED |
| | FOR THE APPLICABLE CONSTRUCTION CONDITIONS. |
| | |
| | |
| | FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II |
| | CONSTRUCTION |
| | 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM |
| | PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 25. |
| | EXCEPTIONS: |
| | 1. INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | |