Plan Review Details - Permit 22110694
| Plan Review Stops For Permit 22110694 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-11-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-11-29 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-11-21 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-11-17 |
Time |
07:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-30 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-30 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-11-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-11-18 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-11-18 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2022-11-18 07:25:41 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22110694 | | | 11/18/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PERMIT APPLICATION DOES INDICATE WHETHER THE | | | BACKFLOW REPLACEMENT IS FOR THE POTABLE WATER SERVICE | | | LINE OR FOR THE FIRE SERVICE LINE, ALTHOUGH IT APPEARS | | | TO BE FOR THE FIRE LINE BECAUSE IT IS A DCDA. PLEASE | | | CLARIFY AND NOTE AN RPZ BACKFLOW ASSEMBLY IS REQUIRED | | | FOR POTABLE WATER SERVICES- SEC. E- WPB UTILITIES CROSS | | | CONNECTION MANUAL. | | | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | | THE BACKFLOW- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-11-21 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-11-21 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |