| Plan Review Stops For Permit 22110683 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-02-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-02-21 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-02-21 |
Time |
19:14 |
Sent To |
|
|
| Notes |
| 2023-02-21 19:15:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 703.4, FBC B 1405.4, A FLASHING DETAIL OR | | | SPECIFICATION IS REQUIRED. THIS COMMENT CAN BE RESOLVED | | | BY DOING ONE OF THE FOLLOWING: | | | | | | REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS | | | REQUIRED AND NOTE THE CODE REFERENCE - EXAMPLE | | | "FLASHING IN ACCORDANCE WITH FBC R 703.4/B 1405.4 WILL | | | BE INSTALLED". | | | PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS | | | MAY INCLUDE MORE THAN ONE OPTION | | | PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN | | | ONE OPTION | | | | | | 2. . FBC EB 702.5, REVISE PLAN TO SHOW ROOM | | | DESIGNATIONS (BEDROOM, KITCHEN, LIVING ROOM, ETC.). | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-02-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-02-21 |
Time |
19:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-01-18 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
|