| 2023-01-23 11:15:15 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22110671 GREASE INTERECEPTOR |
| | MP#22070634 4065 N HAVERHILL RD # B1 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. THE MASTER FOR THIS PROJECT PERMIT NUMBER 22070634 |
| | HAS NOT BEEN APPROVED AS THERE AS THERE ARE UNRESOLVED |
| | COMMENTS TO THE PLUMBING DESIGN SUBMITTED FOR THIS |
| | PROJECT INCLUDING THOSE CONCERNING THE GREASE |
| | INTERCEPTOR. NOTE THAT THE MASTER PLUMBING DESIGN WHEN |
| | APPROVED AND THIS PERMIT SUBMITTAL SHALL BE RECONCILED |
| | WITH EACH OTHER FOR APPROVAL. |
| | |
| | 2. PROVIDE CALCULATIONS AND STANDARD FOR SIZING OF THE |
| | GREASE INTERCEPTOR. FBC PL 1003.3.5 |
| | |
| | 3. PROVIDE FLOOR PLAN AND RISER DIAGRAM SHOWING |
| | LOCATION OF INTERCEPTOR, ITEMS DISCHARGING TO THE UNIT |
| | AND DRAINAGE PIPING |
| | |
| | 4. SEE COMMENTS FROM MASTER PERMIT 2ND REVIEW |
| | CONCERNING THE GREASE INTERCEPTOR BELOW WHICH MUST BE |
| | RESOLVED. |
| | 1A: ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| | 107.2.1, 107.3.4. |
| | 2A: NEW COMMENT: CALCULATIONS FOR GREASE INTERCEPTOR |
| | SHALL NOT INCLUDE HAND SINKS. FBC PL 1003.2. IF MOP |
| | SINK AND PREP SINK DISCHARGE TO GREASY WASTE THEN THEY |
| | SHALL BE INCLUDED IN CALCULATIONS. |
| | 3A: NEW COMMENT: GREASE TRAP SUBMITTAL DOES NOT |
| | INDICATE THE SIZE OF THE INTERCEPTOR TO BE USED. PLEASE |
| | INDICATE THE MODEL NUMBER/SIZE ON THE SUBMITTAL. THE |
| | INLET/OUTLET PORTS SHALL BE SIZED TO ACCOMMODATE IN |
| | SIZE OF THE INLET AND OUTLET SIZE OF THE PIPING. FBC PL |
| | 704.2 |
| | 4A: NEW COMMENT: RISER DIAGRAM SHOWS A 2-WAY CLEANOUT |
| | UPSTREAM AND DOWNSTREAM OF THE INTERCEPTOR BUT THEY |
| | APPEAR TO BE A CROSS TEE IN THE DIAGRAM. PLEASE SHOW A |
| | 2WAY CO TEE WITH A SMOOTH HORIZONTAL BOTTOM. A |
| | DEPRESSED/TRAPPED BOTTOM IS NOT ALLOWED |
| | 5A: NEW COMMENT: PROVIDE VTR FOR GREASY WASTE SYSTEM. |
| | FBC PL 904.1, 904.1.1, 904.1.2 |
| | 6A: 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN |
| | REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD |
| | ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE |
| | SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP. |
| | TO BE CLEAR, PROVIDE DETAIL |
| | NEW COMMENT: DOES THIS DRAIN CONTRIBUTE FAT, OIL OR |
| | GREASE (FOG) TO THE SYSTEM. IF SO, DISCHARGE THE |
| | RECEPTOR TO THE GREASY WASTE AND ADD TO THE |
| | CALCULATIONS FOR THE INTERCEPTOR. IF NOT, DISCHARGE TO |
| | SANITARY |
| | 7A: 31. SECOND REQUEST: ICE MAKER(S), HAND SINKS, STEAM |
| | TABLE AND SERVICE SINKS SHALL NOT DISCHARGE TO THE |
| | GREASY WASTE PER FBC PL 1003.2. |
| | TO BE CLEAR, #11 STEAM TABLE, #2 ICE MAKER DRAIN, #4 |
| | ICE MAKER DRAIN SHALL NOT DISCHARGE TO GREASE |
| | INTERCEPTOR. FBC PL 1003.2. IT IS DETERMINED THE #7 MOP |
| | SINK (SERVICE SINK) MAY DISCHARGE TO THE GREASE |
| | INTERCEPTOR. |
| | 9A: NEW COMMENT: PROVIDE WASTE, HOT AND COLD WATER FOR |
| | #8 PREP SINK PER FBC PL 301.3, 602.2, 607.1; IS IT A |
| | FOOD PREP SINK? IF SO, COMPLY WITH FBC PL 802.1.1 OR |
| | 801.1.7 AS APPLICABLE. |
| | IF THE WASTE CONTRIBUTES FAT, OIL OR GREASE (FOG) WASTE |
| | RECEPTOR SHALL CONNECT TO GREASY WASTE. IF NOT, CONNECT |
| | RECEPTOR TO SANITARY. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |